Correspondence op i f August 22, 2003 R.R. Towle Architect 2210 Broadway Phone: (208) 343 -5511 Boise ID 83706 Fax: (208) 343 -5556 RE: ELECTRICAL PLANS REVIEW Dear Mr. Towle: Project Information Permit: ELC 2003 -00042 Tenant: B.A.P.S. Temple Address: 11365 SW Tigard Street This plans review is based on the 2002 edition of the National Electrical Code (NEC). The revised plans received on August 21, 2003 for this project have been reviewed and are approved for construction subject to the following: 1. The approved plans including all schedules, calculations, specifications, and reports must be available at the job site for the field inspector at the time of inspection. 2. Changes to the approved plans shall be submitted and must be approved by the City before the installation covering the changes can be inspected If I can be of any additional assistance, please feel free to contact me at (503) 624 -9036. Sincerely, Herb Stabenow Plans Reviewer HS /file L.G. bo 3 bo o Z N ij K VI E u n id g er ineering Incorporated 4094 Chinden Boulevard, Ste. 200 Boise, Idaho 83714 Phone (208) 336 -0245 -. Fax (208) 345 -1774 August 19, 2003 Design Resources 1014 LaPointe Street Boise ID 83702 Attention: Gary E. Re: B.A.P.S. Temple - Tigard, OR Dear Gary, Below is our response to the City of Tigard review comments by Herb Stabenow dated August 5, 2003. Item 1: An additional signed electrical plan set is attached. Item 2: Per the attached fax, the available fault current at the 'MSB' is 26,469 amps. The specified rating of the panel is .42,000 A.I.C. We calculate the available fault current at Panel 'M' to be 23,036 amps. The specified rating of Panel 'M' shall be 24,000 A.I.C. We calculate the available fault current at Panel 'K' to be 19,706 amps. The specified rating of Panel 'K' is 22,000 A.I.C. We calculate the available fault current at Panel 'A' to be 19,386 amps. The specified- rating of Panel 'A' is 22,000 A.I.C. Item 3: Elevator supplier shall provide motor nameplate information. Item 4: The requirement to comply with UBC 1632 has been added to the contract documents. Anchoring styles are manufacturer specific. If you have any questions, feel free to give us a call at your convenience. Sincerely Limi John Rimbey, P.E. JR/st (1) Attachment E -Mail: muldereng @qwest.net • --_Lai' �• I 1 1 �� OR:801M August 5, 2003 R.R. Towle Architect 2210 Broadway Phone: (208) 343 -5511 Boise ID 83706 Fax: (208) 343 -5556 RE: ELECTRICAL PLANS REVIEW Dear Mr. Towle: Project Information Permit: ELC 2003 -00042 Tenant: B.A.P.S. Temple Address: 11365 SW Tigard Street Tigard, OR This plans review is based on the 2002 edition of the National Electrical Code (NEC). The revisions received on January 31, 2003 have been reviewed and are not approved as submitted. The following items shall be revised (revisions clouded) on the plans and addressed in a response letter. Three complete sets of the revised plans and the response letter shall be submitted to this office for review and approval prior to issuance of the electrical permit. Please note: Loose pages are not acceptable. 1. The plans submitted plans do not comply with OAR 918 for electrical plans review. They will require the stamp and signature of an engineer registered in the State of Oregon or the signature and license number of the signing supervisor of the electrical contractor applying for the electrical permit. I attached a copy of the plan review requirements for your convenience. 2. Provide the available fault current at the Main switchboard (MSB) and panel boards "A ", "K" and "M" to verify the compliance with Article(s) 110.9 and 110.10. This information is 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Mr. Towle August 5, 2003 Page 2 contingent on the available fault current from the utility transformer. The information from the utility indicates that no request for engineering or design has been received yet. 3. Please provide the nameplate rating of the elevator motor to show compliance with Article 620.13. See also Article 430.22 and the associated Table "E ". 4. Please clarify the anchorage of the Main switchboard. UBC Section 1632 can be used for the design If I can be of any additional assistance, please feel free to contact me at (503) 781 -2446. Sincerely, Herb Stabenow Plans Reviewer c: Gary Eichelberger, Design Resources Nick Paresh Hap Watkins. Inspection Supervisor file • • F CITY OF TIGARD ® 1 OREGON August 5, 2003 • R.R. Towle Architect 2210 Broadway Phone: (208) 343 -5511 Boise ID 83706 Fax: (208) 343 -5556 RE: ELECTRICAL PLANS REVIEW Dear Mr. Towle: Project Information Permit: ELC 2003 -00042 Tenant: B.A.P.S. Temple Address: 11365 SW Tigard Street Tigard, OR This plans review is based on the 2002 edition of the National Electrical Code (NEC). The revisions received on January 31, 2003 have been reviewed and are not approved as submitted. The following items shall be revised (revisions clouded) on the plans and addressed in a response letter. Three complete sets of the revised plans and the response letter shall be submitted to this office for review and approval prior to issuance of the electrical permit. Please note: Loose pages are not acceptable. 1. The plans submitted plans do not comply with OAR 918 for electrical plans review. They will require the stamp and signature of an engineer registered in the State of Oregon or the signature and license number of the signing supervisor of the electrical contractor applying for the electrical permit. I attached a copy of the plan review requirements for your convenience. 2. Provide the available fault current at the Main switchboard (MSB) and panel boards "A ", "K" and "M" to verify the compliance with Article(s) 110.9 and 110.10. This information is 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 1 Mr. Towle August 5, 2003 Page 2 contingent on the available fault current from the utility transformer. The information from the utility indicates that no request for engineering or design has been received yet. 3. Please provide the nameplate rating of the elevator motor to show compliance with Article 620.13. See also Article 430.22 and the associated Table "E ". 4. Please clarify the anchorage of the Main switchboard. UBC Section 1632 can be used for the design If I can be of any additional assistance, please feel free to contact me at (503) 781 -2446. Sincerely, Herb Stabenow Plans Reviewer c: Gary Eichelberger, Design Resources Nick Paresh Hap Watkins. Inspection Supervisor file • • • • • *14 r�7 DATE: P S C ECK NO '1 - a5 - 03 L1 ov 3 - Ooc5b PROJECT TITLE. COUNTYWIDE 8./ Ps• r3 TRAFFIC IMPACT FEE WORKSHEET APPLIC T (FOR NON - SINGLE FAMILY USES) MAILINpDj �� es/ 174.4e/ ESSp „)( J O CITY/ZIPSFRE : Se C 95 /410 TAX MAP tKK7 I 34 D -b0700 SITES NO.ADDRESS: LAND USE CATEGORY RATE PER TRIP /1 3 (v S SW Ti rd S ' RESIDENTIAL $2 & asq.00 BUSINESS AND COMMERCIAL $ 64.00 OFFICE $ 233.00 Nol e ' � Lk�i0Y1 (AJ S SGc,b ht 1 r INDUSTRIAL $ 244.00 rr 4-0 S u ( I � av 3 . En-AV/e, INSTITUTIONAL $1Q :e6 QB. p o +0 a Id rife PAYMENT METHOD: T CASH /CHECK CREDIT BANCROFT (PROMISSORY NOTE) INSTITUTIONAL ONLY DEFER TO OCCUPANCY LAD �II C N S I �lEEKG / I WND AVG TRIP RATE BASIS: 5(0 0 U o A Z eZ E o ORY C SU rcfi / OF U (t7 r4 ItRIP RATE DAY AV 7.7 0�G.�/D EEKE � �• � � �I /// /�6 it e 4 n'f /'s C077 SIC e G / q I 7 e iip/ . wait ?a c - t eked afar -� J it CALCULATIONS: w kly -1-)- o ta ♦ wk d 4 p rd e- ie ne e. TI F ' r )( 770. S F g ra-{e. 71F = 7.70 /q•,qq x 4 41. oo ? x �?s fIr Iq. ply g Qg oa es !. it 14. I it 4V. 00 Y � d la. 00 -7 / # IPGENE� y , FEE: (p �$ '17o.op FOR ACCOUNTING PURPOSES ONLY ADDITIONAL NOTES: /I -n r = (.(hiT5 A GV i - o r' e te. X rk�e- �✓er 7ir+f I X 4.10 A C.131 = ��ysS. ROAD AMTS , (o.00 TRANSIT AMT 4 i ns-f / $/, 3SU re5i . rd-f4/ Tip = $ 101A +: +: = $ �;y7o 60 PREPARED 7 3 �- Ada ita 1\ July 25, 2003 CITY OF TIGARD Paresh Patel OREGON PO Box 41160 San Jose, CA 95160 TRAFFIC IMPACT FEE FOR B.A.P.S. TEMPLE, 11365 SW TIGARD ST. Enclosed with this letter you will find a calculation sheet showing the computation that has been performed to determine the amount of the Traffic Impact Fee (TIF) to be paid for the project noted above. The amount of the TIF is $8,470.00. You have three payment options available to you. The first is to pay the TIF at the time you are issued a building permit. The second is to arrange for payment over time by signing a promissory note (if you wish to exercise this second option please contact me for additional details). The third option is to defer payment until occupancy. Please note that with the third option, you will be subject to the annual increase that went into effect on July 1, 2003, and will also be subject to annual increases of up to 6% if not paid or financed prior to July 1 of each subsequent year. You may appeal the discretionary decisions made in determining the appropriate category and the amount of the fee based on that category. A notice of appeal must be received by the City Recorder no later than 5:00 p.m. on August 8, 2003 and must be accompanied by the $1,170.00 appeal fee required by Washington County. Although filed with the City Recorder, an appeal would be heard by the Washington County Hearings Officer. Also enclosed with this letter, you will find a "Countywide Traffic Impact Fee Payment Option Form ". Please choose a payment option, obtain the necessary signatures, and return to me as soon as possible. We must receive this form before permits can be issued. If you have any questions, please contact me at 503 - 639 -4171. rree 4r ( tr il471 xecutive Assistant Enclosures (2) c: TIF file Building file 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772