Correspondence op i f
August 22, 2003
R.R. Towle
Architect
2210 Broadway Phone: (208) 343 -5511
Boise ID 83706 Fax: (208) 343 -5556
RE: ELECTRICAL PLANS REVIEW
Dear Mr. Towle:
Project Information
Permit: ELC 2003 -00042
Tenant: B.A.P.S. Temple
Address: 11365 SW Tigard Street
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The revised plans received on August 21, 2003 for this project have been reviewed and are
approved for construction subject to the following:
1. The approved plans including all schedules, calculations, specifications, and reports must be
available at the job site for the field inspector at the time of inspection.
2. Changes to the approved plans shall be submitted and must be approved by the City before
the installation covering the changes can be inspected
If I can be of any additional assistance, please feel free to contact me at (503) 624 -9036.
Sincerely,
Herb Stabenow
Plans Reviewer
HS /file
L.G. bo 3 bo o Z
N ij K VI E u n id g er
ineering
Incorporated
4094 Chinden Boulevard, Ste. 200
Boise, Idaho 83714
Phone (208) 336 -0245 -.
Fax (208) 345 -1774
August 19, 2003
Design Resources
1014 LaPointe Street
Boise ID 83702
Attention: Gary E.
Re: B.A.P.S. Temple - Tigard, OR
Dear Gary,
Below is our response to the City of Tigard review comments by Herb Stabenow dated
August 5, 2003.
Item 1: An additional signed electrical plan set is attached.
Item 2: Per the attached fax, the available fault current at the 'MSB' is 26,469 amps. The
specified rating of the panel is .42,000 A.I.C. We calculate the available fault
current at Panel 'M' to be 23,036 amps. The specified rating of Panel 'M' shall be
24,000 A.I.C. We calculate the available fault current at Panel 'K' to be 19,706
amps. The specified rating of Panel 'K' is 22,000 A.I.C. We calculate the
available fault current at Panel 'A' to be 19,386 amps. The specified- rating of
Panel 'A' is 22,000 A.I.C.
Item 3: Elevator supplier shall provide motor nameplate information.
Item 4: The requirement to comply with UBC 1632 has been added to the contract
documents. Anchoring styles are manufacturer specific.
If you have any questions, feel free to give us a call at your convenience.
Sincerely
Limi
John Rimbey, P.E.
JR/st
(1) Attachment
E -Mail: muldereng @qwest.net •
--_Lai' �• I 1 1 ��
OR:801M
August 5, 2003
R.R. Towle
Architect
2210 Broadway Phone: (208) 343 -5511
Boise ID 83706 Fax: (208) 343 -5556
RE: ELECTRICAL PLANS REVIEW
Dear Mr. Towle:
Project Information
Permit: ELC 2003 -00042
Tenant: B.A.P.S. Temple
Address: 11365 SW Tigard Street Tigard, OR
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The revisions received on January 31, 2003 have been reviewed and are not approved as submitted.
The following items shall be revised (revisions clouded) on the plans and addressed in a response
letter. Three complete sets of the revised plans and the response letter shall be submitted to this
office for review and approval prior to issuance of the electrical permit. Please note: Loose pages
are not acceptable.
1. The plans submitted plans do not comply with OAR 918 for electrical plans review. They
will require the stamp and signature of an engineer registered in the State of Oregon or the
signature and license number of the signing supervisor of the electrical contractor applying
for the electrical permit. I attached a copy of the plan review requirements for your
convenience.
2. Provide the available fault current at the Main switchboard (MSB) and panel boards "A ", "K"
and "M" to verify the compliance with Article(s) 110.9 and 110.10. This information is
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Mr. Towle
August 5, 2003
Page 2
contingent on the available fault current from the utility transformer. The information from
the utility indicates that no request for engineering or design has been received yet.
3. Please provide the nameplate rating of the elevator motor to show compliance with Article
620.13. See also Article 430.22 and the associated Table "E ".
4. Please clarify the anchorage of the Main switchboard. UBC Section 1632 can be used for the
design
If I can be of any additional assistance, please feel free to contact me at (503) 781 -2446.
Sincerely,
Herb Stabenow
Plans Reviewer
c: Gary Eichelberger, Design Resources
Nick Paresh
Hap Watkins. Inspection Supervisor
file
•
•
F CITY OF TIGARD
®
1 OREGON
August 5, 2003
•
R.R. Towle
Architect
2210 Broadway Phone: (208) 343 -5511
Boise ID 83706 Fax: (208) 343 -5556
RE: ELECTRICAL PLANS REVIEW
Dear Mr. Towle:
Project Information
Permit: ELC 2003 -00042
Tenant: B.A.P.S. Temple
Address: 11365 SW Tigard Street Tigard, OR
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The revisions received on January 31, 2003 have been reviewed and are not approved as submitted.
The following items shall be revised (revisions clouded) on the plans and addressed in a response
letter. Three complete sets of the revised plans and the response letter shall be submitted to this
office for review and approval prior to issuance of the electrical permit. Please note: Loose pages
are not acceptable.
1. The plans submitted plans do not comply with OAR 918 for electrical plans review. They
will require the stamp and signature of an engineer registered in the State of Oregon or the
signature and license number of the signing supervisor of the electrical contractor applying
for the electrical permit. I attached a copy of the plan review requirements for your
convenience.
2. Provide the available fault current at the Main switchboard (MSB) and panel boards "A ", "K"
and "M" to verify the compliance with Article(s) 110.9 and 110.10. This information is
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
1
Mr. Towle
August 5, 2003
Page 2
contingent on the available fault current from the utility transformer. The information from
the utility indicates that no request for engineering or design has been received yet.
3. Please provide the nameplate rating of the elevator motor to show compliance with Article
620.13. See also Article 430.22 and the associated Table "E ".
4. Please clarify the anchorage of the Main switchboard. UBC Section 1632 can be used for the
design
If I can be of any additional assistance, please feel free to contact me at (503) 781 -2446.
Sincerely,
Herb Stabenow
Plans Reviewer
c: Gary Eichelberger, Design Resources
Nick Paresh
Hap Watkins. Inspection Supervisor
file
•
•
•
•
•
*14
r�7 DATE: P S C ECK NO
'1 - a5 - 03 L1 ov 3 - Ooc5b
PROJECT TITLE.
COUNTYWIDE 8./ Ps• r3
TRAFFIC IMPACT FEE
WORKSHEET APPLIC T
(FOR NON - SINGLE FAMILY USES) MAILINpDj �� es/ 174.4e/ ESSp „)( J O
CITY/ZIPSFRE : Se C 95 /410
TAX MAP tKK7 I 34 D -b0700
SITES NO.ADDRESS:
LAND USE CATEGORY RATE PER TRIP /1 3 (v S SW Ti rd S '
RESIDENTIAL $2 & asq.00
BUSINESS AND COMMERCIAL $ 64.00
OFFICE $ 233.00 Nol e ' � Lk�i0Y1 (AJ S SGc,b ht 1 r
INDUSTRIAL $ 244.00 rr 4-0 S u ( I � av 3 . En-AV/e,
INSTITUTIONAL $1Q :e6 QB. p o +0 a Id rife
PAYMENT METHOD: T
CASH /CHECK
CREDIT
BANCROFT (PROMISSORY NOTE)
INSTITUTIONAL ONLY
DEFER TO OCCUPANCY LAD �II C N S I �lEEKG / I WND AVG TRIP RATE
BASIS:
5(0 0 U o A Z eZ E o ORY C SU rcfi / OF U (t7 r4 ItRIP RATE DAY AV 7.7 0�G.�/D EEKE � �• � �
�I ///
/�6 it e 4 n'f /'s C077 SIC e G / q I 7 e iip/ . wait ?a c
- t eked afar -� J
it
CALCULATIONS: w kly -1-)- o ta ♦ wk d 4 p rd e-
ie ne e. TI F ' r )( 770. S F g ra-{e.
71F = 7.70 /q•,qq x 4 41. oo
? x
�?s fIr Iq. ply g Qg oa es
!. it 14. I it 4V. 00 Y � d la. 00 -7 / # IPGENE� y ,
FEE: (p
�$ '17o.op
FOR ACCOUNTING PURPOSES ONLY
ADDITIONAL NOTES: /I
-n r = (.(hiT5 A GV i - o r' e te. X rk�e- �✓er 7ir+f
I X 4.10 A C.131 = ��ysS.
ROAD AMTS ,
(o.00
TRANSIT AMT
4 i ns-f / $/, 3SU re5i .
rd-f4/ Tip = $ 101A +: +: = $ �;y7o 60 PREPARED 7 3 �-
Ada ita 1\
July 25, 2003 CITY OF TIGARD
Paresh Patel
OREGON
PO Box 41160
San Jose, CA 95160
TRAFFIC IMPACT FEE FOR B.A.P.S. TEMPLE, 11365 SW TIGARD ST.
Enclosed with this letter you will find a calculation sheet showing the computation that has
been performed to determine the amount of the Traffic Impact Fee (TIF) to be paid for the
project noted above. The amount of the TIF is $8,470.00.
You have three payment options available to you. The first is to pay the TIF at the time you
are issued a building permit. The second is to arrange for payment over time by signing a
promissory note (if you wish to exercise this second option please contact me for additional
details). The third option is to defer payment until occupancy. Please note that with the third
option, you will be subject to the annual increase that went into effect on July 1, 2003, and
will also be subject to annual increases of up to 6% if not paid or financed prior to July 1 of
each subsequent year.
You may appeal the discretionary decisions made in determining the appropriate category
and the amount of the fee based on that category. A notice of appeal must be received by
the City Recorder no later than 5:00 p.m. on August 8, 2003 and must be accompanied by
the $1,170.00 appeal fee required by Washington County. Although filed with the City
Recorder, an appeal would be heard by the Washington County Hearings Officer.
Also enclosed with this letter, you will find a "Countywide Traffic Impact Fee Payment Option
Form ". Please choose a payment option, obtain the necessary signatures, and return to me
as soon as possible. We must receive this form before permits can be issued.
If you have any questions, please contact me at 503 - 639 -4171.
rree 4r ( tr il471
xecutive Assistant
Enclosures (2)