August 1, 1988
Wyatt Fire Protection. Inc.
9095 S.W. Burnham
Tigard, Oregon 97223
Attn: Claton
RE: Air -Teq Paint Booth
9806 Tigard Avenue
Tigard, Oregon
Gentlemen:
A fire and life safety plan review was conducted on the above captioned
project for compliance with the 1985 editions of the Uniform Building Code
(UBC), Uniform Mechanical Code (UMC), and Uniform Fire Code (UFC) as amended
by Tualatin Rural Fire Protection District's Ordinance 86 -5.
Plans are approved as submitted conditional to the following items:
1. Job Site Inspection: Please contact this office for an appointment to
have inspection after completion of job while fitter is still on the
job site. Twenty -four hour notification is preferable.
2. Approved Plans on Job Site: One set of approved plans bearing the
stamps of the Tigard Building Department and this office must be
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. (UBC Sec. 303)
3. Inspections Required: Inspection and approval of construction by a
representative of this office is required: (a) prior to the cover of
any new framing elements following the installation of all utility
runs which will be concealed within wall and partition cavities; (b)
upon completion of construction and prior to occupancy of the tenant
space. (UBC Sec. 305)
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS DURING
THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO COMPLY WITH FIRE
SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED WITHOUT THE WRITTEN
AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING DEPARTMENT AND THIS OFFICE.
4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, Oregon 97076 • (503) 526 -2469
Wyatt Fire Protection
August 1, 1988
Page 2
If I can be of any further assistance to you, please feel free to contact me
at 526 -2502.
Sincerely,
Ak /
Gene Birchill
Deputy Fire Marshal
GB:kw
cc: Tigard Building Department
District Inspectors
kli.cgC5i 7//9/#
CONSOLIDATED FIRE AND RESCUE
® �P �� 7" A el / Washington County Fire District No. 1
1 City of Beaverton Fire Department
r 0 Tualatin Fire District
• r►
FIRE MARSHALS OFFICE
July 18, 1988
Mr. Grant Davies
9806 S.W. Tigard Street
Tigard, Oregon 97223
RE: AIR /TEQ
9806 S.W. Tigard Street
Tigard, Oregon 97223
Dear Mr. Davies:
A fire and life safety plan review was conducted on the above captioned
project for compliance with the 1985 editions of the Uniform Building Code
(UBC). Uniform Mechanical Code (UMC), and Uniform Fire Code (UFC) as amended
by Tualatin Rural Fire Protection District's Ordinance 86 -5.
Plans are approved for construction subject to the following items:
1. Paint Spray Booth: The Binks Floor Type Paint Spray Booth you intend
to install appears to be an acceptable unit. It must be installed in
accordance with the provisions set forth in Article 45 of the Uniform
Fire Code. Please see attached photocopy for additional details.
2. Dip Tanks: Please provide the material safety data sheets for the
products being used in your dip tank operation. If these products are
flammable or combustible liquids, the installation of the dip tanks
will be subject to the requirements set forth in Article 45 of the
Uniform Fire Code.
3. Mechanical Equipment Approval: All heat producing and electrical
equipment and appliances installed in conjunction with the
construction or occupancy of this project must be approved by
Underwriters Laboratories, Inc. or other nationally recognized testing
agency and installed in accordance with the testing agency's
specifications. (UMC Sec. 502)
4. Address Required: The tenant space number must be prominently
displayed on the street front where it is readily visible to drivers
and officers of responding fire apparatus and other emergency
• vehicles. (UFC Sec. 10.208)
4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, Oregon 97076 • (503) 526 -2469
Mr. Grant Davies
July 18, 1988
Page 2
5. Approved Plans on Job Site: One set of approved plans bearing the
stamps of the Tigard Building Department and this office must be
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. (UBC Sec. 303)
6. Inspections Required: Inspection and approval of construction by a
representative of this office is required: (a) prior to the cover of
any new framing elements following the installation of all utility
runs which will be concealed within wall and partition cavities; (b)
upon completion of construction and prior to occupancy of the tenant
space. (UBC Sec. 305)
7. Required Occupancy Certificate: Prior to the use and occupancy of the
project (space), a certificate of occupancy or other written
instrument of approval must be obtained from the Washington County
Building Department. (UBC Sec. 307)
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS DURING
THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO COMPLY WITH FIRE
SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED WITHOUT THE WRITTEN
AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING DEPARTMENT AND THIS OFFICE.
If I can be of any further assistance to you, please feel free to contact me
at 526 -2469.
Sincerely,
c ;&4:
Jerry Renfro
Deputy Fire Marshal
JR:kw
cc: Tigard Building Department
District Inspectors
NOTE TO INSPECTORS:
A second exit from the second floor office area was ordered by Brad Roast
(Tigard Building Department) and was in place at the time of an information
inspection on July 15, 1988. Please include this new exit in the final
inspection. This exit is the stairway from the upper story leading to the
warehouse near the north wall of the building.
/Ul z2-y
d4 k Ahlraimmam
CITY OF TIQA R®
June 27, 1988 OREGOP!
Mr. Grant Davis
Airteq
9806 SW Tigard St
Tigard, OR 97223
Dear Mr. Davies:
A plan review has been conducted for the installation of a spray paint booth
at the above location. The following shall apply:
1. The booth and exhaust duct shall be protected by an approved automatic
sprinkler system.
2. Electrical wiring shall comply as for:
o Class I, Division 1, inside the booth
o Class I, Division 2, outside the booth
3. The electrical equipment shall be interlocked with the ventilation of
spraying area so that the equipment cannot be operated without the exhaust
fans in operation.
4. The exhaust duct shall have a minimum of 18 -inch clearance to combustible
material.
If you have any questions, please call 639 -4171.
Sincerely,
Brad Roast
Building Official
ht /5580D
13125 SW Hall Blvd., P.O. Box 23397, Tigard, Oregon 97223 (503) 639 -4171
/7 2ZV
MEP !CIF - ®® ® ® ®
M® �® -
MUMMY ■ilr ONMEOW .911217 6119N, NMI 41M117
® ® ® trlatiSMIN
_
A DIVISION OF PACIFIC SECURITY SYSTEMS. INC
June 23, 1988
Dear Mr. Roast,
Per Fire Marshall Bob Ray's recommendations, during his visit
this week, we are moving the exit. We are moving steps from the
back of the office to the side to give immediate access to the
front door. Also we are beefing up the hand rail for more
stability.
Internally, also to Fire Marshall Bob Ray's recommendation, we
are replacing the hand rail on the stairs with another style
which will curve down at each end to avoid snagging sleeves.
We hope this is helpful.
Sincerely,
Grant Davies
GD /rb
•
1 1735 N.E. Sumner St. • Portland, OR 97220 • (503) 257 - 7770 FAX (503) 255 -7851
RECEIVED JUN 9 3 1988
•
#07.- „N , i Washington County Fire District No. 1*
` J City of Beaverton Fire Department
Tualatin Rural Fire Protection District
June 16, 1988
A.S.I. Heating & Air Conditioning
17555 S.W. 65th Avenue
Lake Oswego, Oregon 97035
RE: Air Teq
9806 S.W. Tigard Street
Tigard, Oregon
Gentlemen:
A fire and life safety plan review was conducted on the above captioned
project for compliance with the 1985 editions of the Uniform Building Code
(UBC), Uniform Mechanical Code (UMC), and Uniform Fire Code (UFC) as amended
by Tualatin Rural Fire Protection District's Ordinance 86 -5.
Plans are approved conditional to the following items:
1. Approved Plans on Job Site: One set of approved plans bearing the
stamps of the Tigard Building Department and this office must be
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. (UBC Sec. 303)
2. Inspections Required: Inspection and approval of construction by a
representative of this office is required: (a) prior to the cover of
any new framing elements following the installation of all utility
runs which will be concealed within wall and partition cavities; (b)
upon completion of construction and prior to occupancy of the tenant
space. (UBC Sec. 305)
3. Certificate of Occupancy Required: Prior to the use and occupancy of
the project (space), a certificate of occupancy or other written
instrument of approval must be obtained from the City of Tigard
Building Department. (UBC Sec. 307)
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS DURING
THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO COMPLY WITH FIRE
SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED WITHOUT THE WRITTEN
AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING DEPARTMENT AND THIS OFFICE.
!}
A A.S.I. Heating & Air Conditioning
June 16, 1988
Page 2
If I can be of any further assistance to you, please feel free to contact me
at 649 -8577.
Sincerely,
TUALATIN FIRE DISTRICT
0411111,/4-- aLSIA
Gene Birchill
Building Official
20665 S.W. Blanton Street
Aloha, Oregon 97007
GB:kw
cc: Tigard Building Dept.
District Inspectors
4 � , 0 ` ��� Washington County Fire District No. 1
City of Beaverton Fire Department
e, fgt Tualatin Rural Fire Protection District
. 1,x,1
June 3, 1988
R.A. Gray & Company
P.O. Box 23516
Tigard, Oregon 97223
RE: Tenant Modification - Air -Teq
9806 S.W. Tigard Street
Tigard, Oregon
Gentlemen:
A fire and life safety plan review was conducted on the above -
captioned project for compliance with the 1985 editions of the
Uniform Building Code (UBC), Uniform Mechanical Code (UMC), and
Uniform Fire Code (UFC) as amended by Tualatin Rural Fire Protec-
tion District's Ordinance 86 -5.
Plans are approved as submitted subject to the following items:
1. Firestopping: In all wood - framed walls and partitions, fire -
stopping consisting of 2 -inch nominally -sized lumber or
other approved materials must be installed at all floor and
ceiling levels. Penetrations in this prescribed firestopping
to accommodate wiring, plumbing, and other similar utility
runs must be packed with noncombustible materials in an .
approved manner so as to prevent the passage of flame.
(UBC Sec. 2516)
2. Approved Plans on Job Site: One set of approved plans bear-
ing the stamps of the Tigard Building Department and this
office must be maintained on the project site throughout all
phases of construction and must be made available to build-
ing and fire inspectors for reference during required con-
struction inspections.
(UBC Sec. 303)
3. Certificate of Occupancy Required: Prior to the use and
occupancy of the project (space), a certificate of occu-
pancy or other written instrument of approval must be
obtained from the City of Tigard Building Department.
(UBC Sec. 307)
R.A. Gray & Company
June 2, 1988 -
Page 2
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY- APPROVED
PLANS DURING THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE
NECESSARY TO COMPLY WITH FIRE SAFETY REQUIREMENTS AS LISTED HEREIN,
ARE PROHIBITED WITHOUT THE WRITTEN AUTHORIZATION OF THE WASHINGTON
COUNTY BUILDING DEPARTMENT AND THIS OFFICE.
If I can be of any further assistance to you, please feel free to
contact me at 649 -8577.
Sincerely,
TUALATIN F STRICT
t t *l
Bert •:rke
Fire •rsh.l
20665 S.W. :lanton Street
Aloha, Oregon 97007
BP:kw
cc: Tigard Building Dept.
District Inspectors