Plans /, ELc 00 0 3 ).390 5=J 51! LOAD CALCULATIONS PANEL H1 BASED ON THE 1996 NEC CONNECTED LOAD LINE L1 75,413 VA LINE L2 69,873 VA LINE L3 54,361 VA LARGEST LINE LOAD X 3 * * * * * ** VA RECEPTACLE LOAD DIVERSITY RECEPTACLE LOAD 0 VA LESS 1ST 10,000 VOLTAMPS * * * * * * *VA REMAINING VOLTAMPS 0 VA 50% OF THE REMAINING VOLTAMPS 0 VA DIVERSITY (NEC 220 -13) 0 VA CONTINUOUS LOAD LINE L1 2,700 VA LINE L2 2,700 VA LINE L3 2,700 VA LARGEST LINE LOAD X 3 8,100 VA 25% OF THE CONTINUOUS LOAD (NEC 220 -20) 2,025 VA LARGEST MOTOR LOAD LINE L1 5,540 VA LINE L2 5,540 VA LINE L3 6,648 VA LARGEST LINE LOAD X 3 19,944 VA 25% OF LARGEST MOTOR LOAD (NEC 430 -24) 4,986 VA TOTAL LOAD VOLTAMPS * * * * * ** VA TOTAL LOAD AMPS * * * * * *VA/ 480 V / 1.73 = 281 A ADJUSTMENT 0 % 0 A 0 VA ADJUSTED DESIGN LOAD 281 A * * * * * ** VA VOLTAGE DROP 2 X L X R X I / 1000 X 0.866 = VD 2 X 10 X * * * * * *X 281 / 1000 X 0.866 = 0.21 VD INC. VOLTAGE DROP % VD / VOLTS = VD % * * ** / 480 = * * * *$ HARMONIC CURRENTS LINE L1 30,400 VA LINE L2 30,400 VA LINE L3 2,700 VA TOTAL HARMONIC LOAD (LARGEST LOAD X 3) 91,200 VA DIVIDED BY CONNECTED LOAD / * * * * * * *VA HARMONIC LOAD % 40 % PANEL H1 # CONDUITS 1 # CIRCUITS 42 C -SIZE 3 IN FED FROM TRANSFORMERC -TYPE GENERAL HI VOLTAGE 480 # WIRES 4 LOW VOLTAGE 277 WIRE SIZE #500 PHASE 3 GND SIZE # HERTZ 60 WIRE TYPE THHN NEUT BUS Y/N Y WIRE CU /AL CU GND BUS Y/N Y WIRE AMPS 400 GND WIRE Y/N Y WIRE TYPE THHN WIRE CU /AL? CU WIRE TEMP C 75 WIRE LENGTH 10 CONDUIT TYPE GENERAL MINIMUM AMPS 0 % FACTOR 0 MAIN BKR Y /N? Y MAIN BKR AMPS 400 # BKR CIRCUIT DESCRIPTH I VA VA I H CIRCUIT DESCRIPT.BKR 1 100A- 2PTRANSFORMER H G 27,700 L15,540 M EQUIPMENT 40A -3P 3 H G 27,700 L25,540 M 5 40A -2P EQUIPMENT G 5,540 L35,540 M 7 G 5,540 L15,540 M EQUIPMENT 40A -3P 9 30A -3P EQUIPMENT M 4,155 L25,540 M 11 M 4,155 L35,540 M 13 M 4,155 L15,540 M EQUIPMENT 40A -3P 15 30A -3P EQUIPMENT M 4,155 L25,540 M 17 M 4,155 L35,540 M 19 M 4,155 L15,540 M EQUIPMENT 40A -3P 21 30A -3P EQUIPMENT M 4,155 L25,540 M 23 M 4,155 L35,540 M 25 M 4,155 L12,770 M EQUIPMENT 20A -3P 27 15A -3P EQUIPMENT M 2,078 L22,770 M 29 M 2,078 L32,770 M 31 M 2,078 L1 G SPARE 20A -1P 33 20A -1P SITE LTG H C 2,700 L2 G SPARE 20A -1P 35 30A -1P M 6,648 L32,700 C H WASH TUNNEL LTG 20A -1P 37 SPACE G L12,700 C H WASH TUNNEL LTG 20A -1P 39 SPACE G L2 G SPACE 41 SPACE G L3 G SPACE PREPARED BY ... RURAL ELECTR PANEL L1 # CONDUITS 1 # CIRCUITS 42 C -SIZE 2 IN FED FROM TRANSFORMER C -TYPE GENERAL HI VOLTAGE 240 # WIRES 3 LOW VOLTAGE 120 WIRE SIZE #3/0 PHASE 1 GND SIZE #4 HERTZ 60 WIRE TYPE THHN NEUT BUS Y/N Y WIRE CU /AL CU GND BUS Y/N Y WIRE AMPS 200 GND WIRE Y/N Y , WIRE TYPE THHN WIRE CU /AL? CU WIRE TEMP C 75 WIRE LENGTH 150 CONDUIT TYPE GENERAL MINIMUM AMPS 0 % FACTOR 20 MAIN BKR Y /N? Y MAIN BKR AMPS 200 # BKR CIRCUIT DESCRIPTION VA VA I CIRCUIT DESCRIPTIOBKR # 1 20A -1P IG DUPLEX RECEPTSD 1,080 L1 1,080 D IG DUPLEX RECEPTS20A -1P 2 3 20A -1P IG DUPLEX RECEPTSD 1,080 L2 1,080 D IG DUPLEX RECEPTS20A -1P 4 5 30A -2P WATER HEATER G 2,000 L1 500 G BATH HEAT 20A -2P 6 7 G 2,000 L2 500 G 8 9 20A -1P EQIP. GFI G 1,080 L1 500 G OFFICE HEAT 20A -2P10 11 G L2 500 G 12 13 20A -1P SPARE G L1 G SPARE 20A -1P14 15 20A -1P SPARE G L2 G SPARE 20A -1P16 17 20A -1P SPARE G L1 G SPARE 20A -1P18 19 G L2 G 20 21 20A -1P BATH OFFICE LTG G 500 L1 500 G ELEC. RM. MECH. RMOAbTB22 23 G L2 G 24 25 G L1 G 26 27 G L2 G 28 29 G L1 G 30 31 G L2 G 32 33 G L1 G 34 35 G L2 G 36 37 G L1 G 38 39 G L2 G 40 41 G L1 G 42 PREPARED BY ... RURAL ELECTRIC • r - , ` _ '� � ♦-fit 1 . �..� - I , • ■ DOOR TO LOCK FROM INSIDE . -l� EXIT . • . n - • O I 3 �-- _ _ _ _ - — PROVIDE BLOCK -OUT ABOVE DOOR FOR 0 9 - ELECTRICAL CONDUIT. ; • •• VERIFY LOCATION W/ in • EQUIPIEtZ SUPPLIER. 1 1 1 1 1 1 I I [ ]__I ) < Z Z_ LL ., T X I 6 a C .. ELECTRICAL L I ": ROOM PN� i_ 1}I 0 .. • N \ _ 1 1 1 1 1 1 1 1 1 1 1 1 - 4 1/2" i 2' -O" IS' -1 1/2" / ` CI C 1 Q. - Cqr W o IN — • • O Y a. L ,v• e. \ a CO a►vv% •■ C. I Q• C.. C Or AJ CIVAN a77/ 48uv 34' 4 w 4'c PN L H l 2'740v PAL L I t .2 X4vv % 56 (a ) S s 04(3 }4 /0(u) ow. ak „ , _i , 4000 I A c..(3) 3 w. 20 O 5o : CO Ap.P T Cw P CT CA CwP _ `c2 � - t \ \ , 7 — ___ , a' C3> 4/°"- '� u F Et1� Z.- - — � crv. r 5 "G / . AVQA.N\o`t_ Fa�Ak C_of ": 1 6,789 A'^^Ps. Per P G E To PGE 4. Ma,,, 2,16..1<Hr PNI_ t4\ R0, 2,21( A Ic T sars QGOI ws e r Plan Review submitted by: Rural Electric, Inc. . IPa t. 4 4 Paul A. Ellis, #4062 -S FEB -27 98 11:24 FROM:MAIN OFFICE 5035704420 T0:96406004 PAGE:01 THREE PHASE SEC. FAULT CURRENT CUSTOMER NAME: PACIFIC CAR WASH CUSTOMER ADDRESS: SW SCHOLLS FERRY RD, TIGARD TRANSFORMER KVA: 300 KVA IMPEDANCE: 1.3 % • SECONDARY L -L VOLTAGE: 480 VOLTS WIRE LENGTH: 190 FEET WIRE SIZE: 350 AL NUMBER OF RUNS: 2 RUNS TOTAL WIRE IMPEDANCE R: 0.049 OHMS /1000' WIRE IMPEDANCE X: 0.037 OHMS /1000' FAULT CURRENT: 16789. AMPS TES 9/8/93 * - c .. ' � - 1 RECEIVED MAR 0 2 1998 COMMUNITY DEVELOPMENT h