Loading...
Specifications . e —4 0/,( — COO / 0 /1999 �ev(- / C,J` CONCEALED PENDENT SPRINKLERS RESIDENTIAL MODEL F978 DESIGNER, BULB TYPE 4 K- FACTOR, 155 °F GENERAL D ESCRIPTION Dim. Inches MM The 4.2 K- factor, Model F978 Design- B . 3- 3/16 4 .8 er Residential Concealed Pendent c . 2 -5/8 66,8 \4 I x I /2" Sprinklers (Ref. Figure A) are auto- D - Min. 1 -15/16 49,2 V REDUCER matic sprinklers of the frangible bulb D - Nom. 2 -3/16 55.6 (TYPICAL INSTALLATION) type. They are to be used in; D - Max. 2 -7/16 61,9 • wet pipe residential sprinkler sys- e C (DIA) 11.-J terns for one- and two - family dwell- ADJUSTMENT ings and mobile homes per NFPA 130, , 1/2" NPT • wet pipe residential sprinkler sys- tems for residential occupancies up to four stories in height per NFPA , — - 13R, and D _ -- SPRINKLER/ • wet pipe sprinkler systems for the ik . ASSEMBLY residential CUP residential portions of any occu- ; pancy per NFPA 13. ' .. The small Cover Plate is flat, to blend r /� „1 in with the ceiling for an aesthetically -■�� 7 — 4 pleasing and relatively unnoticeable COVER PLATE ASSEMBLY appearance. Standard finishes for the B i A (DIA) 1 3/ 32" GAP - Cover Plate are painted white and (2,4 mm) satin chrome plated. Other factory ap- plied painted finishes for the Cover FIGURE A Plate are available on special order. 4.2 K- FACTOR MODEL F978 DESIGNER RESIDENTIAL CONCEALED PENDENT SPRINKLERS The separable two -piece design of the Cover Plate and Mounting Cup As- semblies allows installation of the sprinklers and pressure testing of the moved and the Cover Plate Assembly fire protection system prior to installa- installed. APPROVALS AND STANDARDS tion of a suspended ceiling or applica- tion of the finish coating to a fixed The F978 Sprinklers have been de- The 4.2 K- factor, Model F978 Design - ceiling. They also permit removal of signed to operate with a particular tem- er Residential Concealed Pendent suspended ceiling panels for access to perature rating and heat responsive Sprinklers are listed by Underwriters building service equipment, without thermal characteristic, as well as to Laboratories Inc. and Underwriters' having to first shut down the fire pro- discharge water in a specific pattern Laboratories of Canada. The listing tection system and remove sprinklers. and quantity per square foot relation- only applies to the service conditions ship. The combination of the perfor- indicated in the General Technical Also, the separable two -piece design mance characteristics which are asso- Data and Residential Design Criteria of the the F978 Sprinkler provides for ciated with the F978 Sprinklers have sections. 1/2 inch (12,7 mm) of vertical adjust- been proven to help in the control of ment, to reduce the accuracy to which residential type fires and, therefore, to Any questions concerning an interpre- the length of fixed pipe drops to the improve the chance for occupants to tation of NFPA 13, 130, or 13R sprink- Sprinklers must be cut. escape or be evacuated. ler system design /installation stan- dards, as well as requests for system The F978 Sprinkler is shipped with a Fire sprinkler systems are not a substi- design /installation standards not ores- Disposable Protective Cap as shown tute for intelligent fire safety aware- ently covered by NFPA 13, 13D, or in Figure B. The Protective Cap is tem- ness or construction materials and 13R, should be addressed to the' porarily removed to install the F978, practices required by building codes and then replaced to protect the F978 Secretary, Standards Council while the ceiling is being installed and National Fire Protection Association Li finished. The tip of the Cap can also be Batterymarch Park used to mark the center of the ceiling Quincy, MA 02269 hole into plaster board, ceiling tiles, etc by pushing the ceiling product WARNINGS against the Cap When the ceiling in- The Model F978 Designer Resi- stallation is complete, the Cap is re- dential Concealed Pendent Printed in U S A 1 -96 TD584M 4 N DISCHARGE IN U S GALLONS PER MINUTE (GPM) 5 10 15 20 25 50 I • i t SI �- -� - - - - _ = t • v1 �5 ` PARTIAL CURVE ONLY a. —MAX PRESSURE 175 PSI 0 0 4 I 1 :: SPRINKLER /,V OUNT.NG 0 JD - I to CUP ASSE MBLY z taa 75 2 s Z ' -- ,` G O Al Al N n _ ' Cr 00 20 „ W - H W o. N ? p _ no 1R I • i 25 m .l • • k • N ' ' , DISPOSABLE PROTECTIVE ? a 20 =- A O I ® Ls a CAP w = _ - - - - ] ' j 15 11111 AlliMilli= VI CI A. 10 or. — PARTIAL CURVE ONLY = /•.. MAX. PRESSURE 12 07 BARS 0.5 i TIP 5 50 75 100 DISCHARGE IN LITERS PER MINUTE FIGURE B FIGURE C DISPOSABLE PROTECTIVE CAP FOR F978 SPRINKLER NOMINAL DISCHARGE CURVE Sprinklers described herein must phosphor bronze per CDA Alloy 510, be installed and maintained in GENERAL TECHNICAL DATA and theYoke is high strength brass. compliance with this document, as well as with the applicable The 4.2 K- factor, Model F978 Design- The Frame is secured to the Mounting standards of the National Fire er Residential Concealed Pendent Cup and Mounting Plate with a plated Protection Association, in addi- Sprinklers are available in a steel Retaining Ring. The Mounting tion to the standards of any other 155 F /68'C temperature rating, and Cup, which is chrome plated 0.021 authorities having jurisdiction. they are rated for use at a maximum inch (0.53 mm) thick, low carbon sheet Failure to do so may impair the service pressure of 175 psi (12,1 bar). steel, is staked to a stainless steel integrity of these devices. The nominal installation dimensions Mounting Plate, and the Mounting are given in Figure A. Standard fin- Plate provides for rigid engagement of — Because of the above cited ishes for the Cover Plate are painted the Sprinkler Wrench (Ref. Figure J) stipulations and the varied na- white and satin chrome; however, with the Frame. ture of residential type architec- other painted finishes for the Cover ture, there will be some compart- Plate are available on special order. A polyethelene Disposable Protective ment designs which cannot be Cap (Ref. Figure B) is provided as part fully sprinklered in accordance The nominal discharge curve for the of the Sprinkler /Mounting Cup Assem- with the recommendations of F978 is plotted in Figure C and it rep- bly. . NFPA 13, I3D, or 13R. In the event resents the flow "0" in GPM (LPM) as of this condition, consult the au- determined by the formula: The Cover Plate Assembly, which thorities having jurisdiction for Q= K screws onto the Sprinkler /Mounting guidance and approval. P Cup Assembly, consists of a Cover where the nominal discharge coeffi- Plate which is soldered to an Enclo- It is the responsibility of an in- cient "K" = 4.2 (60,5); and "p" equals sure at three equidistant locations stalling contractor to provide a the residual flowing pressure in psi around its periphery. Solder having a copy of this document to the owner (bar). temperature rating of 135'F/57 - C is or his representative and, in turn, used with Cover Plate Assembly. The it is the obligation of the owner to The F978 Sprinkler consists of two as- Cover Plate and Enclosure are brass provide a copy of this document to semblies, as shown in Figure D: the per ASTM B36 (C26000 or C26800). A a succeeding owner. Sprinkler /Mounting Cup Assembly and Type 302 stainless steel compression the Cover Plate Assembly. Spring is located between the flange of The owner is responsible for the Enclosure and the Cover Plate, to maintaining their fire protection The Sprinkler /Mounting Cup Assembly ensure separation of the two pieces system and devices in proper op- utilizes a 155 *F /68'C, 3mm Bulb and when the solder melts. erating condition. The installing has a bronze Frame per ASTM B176 contractor or sprinkler manu fac- (C87800) and a brass Orifice Insert per When the Cover Plate Assembly is ex- turer should be contacted relative ASTM B140 (C32000). The Button posed to a temperature sufficient to to any questions. (bulb retainer) is phosphor bronze per fuse the solder, the Cover Plate will fall ASTM B103 (C51000, C52000, or away from the Enclosure which allows C54400), the Ejection Spring is stain- the Deflector to drop and to expose the less steel, and the Compression Sprinkler for operation. Screw is a plated bronze per ASTM B140 (C31400). The Gasketed Spring NOTES Plate consists of an Inconel (per ASTM Absence of the Cover Plate Assem- B168) disc spring that is sealed on bly may delay the time to sprink- both its inside and outside edges with ler operation in a fire situation. ' a Teflont gasket. The Deflector is brass per ASTM B36 (C22000), and The F978 Mounting Cup and the Deflector Cone is brass per ASTM Cover Plate Assembly shown in B16 (C36000) The Deflector Arms are Figure D cannot be used to hold —2— t DuPont Registered Trademark (w V SPRINKLER /MOUNTING CUP ASSEMBLY Thermal Responsive Criteria. All residential sprinklers within a compart- '' MOUNTING PLATE ORIFICE INSERT ment (as defined by the NFPA) must '' R RING have the same heat responsive ther- r: --7.--li : MOUNTING CUP ° ! mal characteristic, and their tempera - • a GA SPRING ture ratings must be within 10'F of EJECTION _ EVM,FI "' b� � PLATE each other. SPRING BUTTON ilir--- I �.it � NOTE DEFLECTOR ARM 1 =1 D Not use sprinklers with a tem- ■ �%. FRA p Q1a t uTe rating higher than nec- YOKE } =� � `` + BULB essary to cover a particular area. DEFLECTOR CONE ��■� Hydraulic Design Criteria. The mini - . , COMPRESSION SCREW mum required single and multiple DEFLECTOR sprinkler flow rates are given in Table 1a,_1 -. .-_,: R.. A for the maximum allowable coverage areas. The single sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sin- gle sprinkler and, the multiple sprinkler ENCLOSURE i o O ) flow rate is the minimum required dis- SPRING charge from each of the total number COVER PLAT of "design sprinklers" (as specified in NFPA 13, 130, or 13R). COVER PLATE ASSEMBLY NOTE ' The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R), must be FIGURE D kept as few as possible. Do NOT MODEL F978 CONCEALED PENDENT SPRINKLER ASSEMBLY use more sprinklers than neces- sary to cover a particular space. the F978 in position. The F978 3. Questions concerning sprink- l '\ must be secured in position by ler installation and usage cri- Spray Coverage Criteria. Figures E -� firmly fastening the sprinkler sys- teria, which are not covered by and F provide spacing rules that must tem piping to the dwelling struc- the following instructions, be followed to assure that the F978 ture. If the F978 is not properly should be mailed to the atten- Sprinklers will provide their design dis- secured in position, reaction tion of the Technical Data De- tribution of water spray. Nominal wet- (_ forces resulting from sprinkler partment. Include sketches ting patterns for the F978 Sprinklers at operation could alter its orienta- and technical details, as ap- minimum required flow conditions tion and water distribution. propriate. (Ref. Table A), are illustrated in Figure G, for selected coverage areas. 4. In some instances, the require- ments of this document may ' RESIDENTIAL DESIGN CRITERIA concern specifications which Operational Sensitivity Criteria. For are more stringent and which proper operational sensitivity, the The 4.2 K- factor, Model F978 Design- take precedence over those F978 Sprinklers must be installed be- er Residential Concealed Pendent specified in NFPA 13, NFPA neath solid ceilings having a smooth Sprinklers must only be installed and 13D, NFPA 13R, or by the -au- flat or textured surface and in accor- utilized in accordance with the follow- thority having jurisdiction. dance with Figure A. ing described criteria which are pro- vided by the manufacturer. 5. The spray from the F978 is dis- The F978 Sprinklers must NOT be tributed radially outward and used above or below open - gridded NOTES downward from the sprinkler type suspended ceilings; beneath sof- 1. Residential Fire Sprinkler Sys- deflector. Consequently, the fits or beams having a depth of more tems should only be designed sprinklers must be located than 4 inches (101,6 mm); and, with and installed by those compe- such that there will not be any beams, joists, or ducts having a height tent and completely familiar blind spaces shielded from of more than 3 inches (76,2 mm) lo- with automatic sprinkler sys- spray by partitions, room di- cated within the sprinkler coverage tern design, installation pro- eiders, overhangs or other areas. • cedures, and techniques. parts of the dwelling structure. NOTE 2. Several criteria may apply to General Service Conditions. The Beams having a height of more the installation and usage of F978 Sprinklers must only be utilized than 3 inches (76,2 mm) may be each sprinkler. Consequently, in wet pipe sprinkler systems with all located with their centerlines it is recommended that the interconnecting system piping as well along the boundaries separating { \ sprinkler system designer re- as the sprinklers maintained at a mini- adjacent sprinkler coverage �� view and develop a working un- mum temperature of 40•F /4•C, and areas. derstanding of the complete with water supplies which are substan- list of criteria, prior to initiat- tially free of contaminants and It is recommended that as part of the ing the design of the sprinkler particles of a size greater than 1/8 inch sprinkler system design, the designer system. (3,2 mm). review the dwelling plans and, where —3— MINIMUM FLOW (b) „11_22.42.5.....4 MAX $12 MAX 5,2 MAX t4 INCHES MAXIMUM AND l NCHES 4INCHESI MIN MIN I MIN. COVERAGE RESIDUAL PRESSURE cn MA 4 INCHES , AREA (a) S/2 MAX 4 INCHES MIN MIN FT. x FT. ONE MULTIPLE 1 (m x m) SPRINKLER SPRINKLERS s r7 MAX FLOWING FLOWING SINCHES 90 T MIN I 12x12 16 GPM 12 GPM (3,7 x 3.7) (14.5 PSI) (8.2 PSI) Figure E -1 (Plan View) Figure E -2 (Plan View) 14 x 14 16 GPM 12 GPM S/2 MAX 1 S/2 MAX 1 5/2 MAX ,l S MAX ■ S/2 MAX i. a INCHES 8 FEET MIN i4 INCHES 4INCHES 4INCHES MIN MIN. (4,3 x 4,3) (14.5 PSI) (8.2 PSI) MIN i MIN I I �- �— S/2 MAX S/2 MAX. 4 INCHES 16 x 16 16 GPM 12 GPM S / 2 M Es MIN (4,9 x 4,9) (14.5 PSI) (8.2 PSI) • I, 18 x 18 24 GPM 17 GPM I I S MAX (5,5 x 5,5) (32.7 PSI) (16.4 PSI) 8 FEET MIN 1 20x20 25 GPM 18 GPM 1 �_ 1 (6,1 x 6,1) (35.4 PSI) (18.4 PSI) s/ MAX. 5/2 INCHES MAX. 4 INCHES 4 INCHES MIN MIN For coverage area dimensions less �— than or between those Indicated, it is Figure E - 3 (Plan View) Figure E (Plan View) necessary to use the minimum required flow for the next highest coverage area for which hydraulic 1 S/2 MAX. 1, S/2 MAX t. Ir-S/2 MAX — • design cntena are stated 4 INCHES 4 INCHES! I MIN MIN. (b) Requirement Is based on minimum flow let? - s/2 MAX X in GPM from each sprinkler. The 41N E5 I—_ associated residual pressures are s/2 MAX MIN , calculated using the nominal K- factor. 4 INCHES e � I 4 INCHES MAX. Refer to Hydraulic Design Cnteria MIN. 0 Q� Oro 8 FEET 4 INCHES MIN ^ '4-4 INCHES MIN. Section for details. MIN. M�IN --• -� SMAX TABLE A B S HYDRAULIC DESIGN CRITERIA ---`— S /2 MAX J 1 41MIN.ES Figure E-6 (Plan View) S/2 MAX S MAX. i I, S/2 MAX 4 INCHES 8 FEET MINIMUM I 14 INCHES MIN MIN. i 4 INCHES MIN Figure E -5 (Plan View) — S/2 MAX MIN S/2 = ONE -HALF THE LENGTH OF THE 4 INCHES .41, MIN COVERAGE AREA BEING HYDRAULICALLY CALCULATED \-S/2 MAX -. (REF. TABLE A). -4 INCHES MIN S = THE LENGTH OF THE COVERAGE S1 AX , s,z MAX. AREA BEING HYDRAULICALLY 4 INCHES I d IN C HE S MIN MIN CALCULATED (REF. TABLE A) -- 41 s\\\\ ,,, < 1 Figure E -7 (Plan View) S r2 MAX. 8 FEET MIN 1 y� �— SEE SEE f GRAPH A GRAPH A S/2 MAX I 4 1N� INCHES MIN l::1 OBSTRUCTION I- Figure E -8 (Plan View) Figure E -9 (Elevation View) FIGURE E SPACING RULES UNDER LEVEL CEILINGS —4— (. • '.•• s.2 3 FEET MAXIMUM p'1'`�JN s � 2 4., M O l x 41447 O ., s o . 0 , 3 F ,NUM 3 FEET MAX ` / 8P$ '(1 ` I <. 4 N / MCi 7.141&,. /S2 �4k se i 4 9i ( 43 °). �A I 8 1 I 1 I 1� FOR FEET L AI MIN 5 60' MUM Figure F -1 (Elevation View) Figure F -2 (Elevation View) MAX 1 _5/2 S/2 MAX. {. \ SEE GRAPH 5/2 B— I II�s 2 y 44- GA 4 o I L-----______ C I FO R G A s M AK---..„ FOR 4 A/ s•60.47 l A� I I Figure F -3 (Elevation View) Figure F-4 (Elevation View) — 3 FEET `30 e,, MAXIMUM ,��``N ,` 6'6. / �� �OO,ygx F Y 1 t y /N\�J�' sp. I / +/ � y g 1----------- 8 FEET MINIMUM A � �A 1 SEE SEE .„/).'A F OR [ A a ^ d 4 B 5 60' 6 GRAPH 0 GRAPH 0 Figure F -5 (Elevation View) Figure F -6 (Elevation View) l 416 3 FEET MAX MAXIMUM UM Q �F� 1 FOOT MIN P M 4 x r �� 0�� i I S/2 MAX. —mil. /y P L. L.P. SEE .,.....)-A 6FOR FEET MINIMUM A� / A, FO G RAPH E� C A 5 60' Figure F -7 (Elevation View) Figure F -8 (Elevation View) • s 1 ,F � pF 3 FEET MAX. r : / N sp i� 4, 4 > k F�T4% Gq /is, '' F I h q e / FFT4 I OBSTRUCTION __ 5/2 MAX. 4 INCHES MIN Figure F -9 (Elevation View) Figure F -10 (Elevation View) S/2 = ONE -HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A). S = THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A). NOTES: 1. Figures F -1 through F -9 only apply when: (a) the ceiling ridge is horizontal; (b) the compartment openings to adjoining spaces have minimum lintel depths of 8 inches (203,2 mm) below the lowest sprinkler; (c) any adjacent sprinklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge, and the sprinklers are to be spaced a minimum of 8 feet apart; . (d) the sprinklers are Installed with Deflector Arms perpendicular to the ceiling ndge; and, - (e) the sprinklers shown in Figures F -1 through F -8 are located in a plane which is perpendicular to the ceiling ridge, . and the ceiling angles are within the specified range. 2. Contact the Technical Data Department for questions concerning installations outside the scope of Figures F -1 through F -10. FIGURE F, SPACING RULES UNDER PITCHED CEILINGS AND /OR OVERHANGS —5— 4 Cfr �� 0. 2. ; 6 6 4 O • f 1 2' \e\ ' 2' I I i ■ I UR .�� -- 1 6' = = =A. 6 , 4 • �' 6 _ 6 8 8' 6 ® 6 8 . 8 . 8' B' 12' X 12' Coverage Area 16 GPM 12 GPM 16' X 16' Coverage Area 20' X 20' Coverage Area 16 GPM 25 GPM - 12GPM 18 GPM FIGURE G NOMINAL WETTING PATTERNS AT MINIMUM REQUIRED FLOW CONDITIONS FOR SELECTED COVERAGE AREAS 27 - -- _ -- 24 —m ...... _ r -_. W II MEW AI ,INIMP MINIM MN NM ∎� v i_� ,r �v 21 J i J -• • J . J. . w • 0 row 0 u— .O • Y- - o z 18 , Cr om ' o Q ., • • -- w m-- ∎ �vi i= Q� • Q ' a -- 0 > _—NOME Q. i s Q r� `� r 1 � � o = - '.2 �L � MIME Ac ■ ■ ■ a a .1,- - P o - - -- ■ 2I - m=- - - -_— r.� .. Amor 1 .... .1 - - -- 12 M p m = = =NOME-- . -11I -11. 'A- --• ,�- .�- .ar. - = - - -- .� - - -- 2 9 -• — N I- I - ter. -'a r -I -W MO.- °C _= =_= =v = - - .A�P _— w _ - NOME -- •J:9rig= T.d n 6 V(MAX.) -- ME — ine ► -- = —ME-- — -- __ --_ 4 —_ 4_... NOME--- - - NOME NOME--- ______ __ __f - _�1.,�____________ it H 1 v 0 1 2 3 4 5 6 7 8 9 10 PLUS (MAX.) DISTANCE TO OBSTRUCTION 'H' OR 2', FEET NOTES: 1. CEILING OBSTRUCTIONS MUST BE SPACED ON THE BASIS OF USING THE MAXIMUM RESIDUAL PRESSURE WHICH WOULD BE PRESENT FOR A SINGLE SPRINKLER OPERATION. 2. BEAMS AND /OR OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH 'V' OF MORE THAN 3 INCHES (76,2 mm) WITHIN THE SPRINKLER COVERAGE AREA. GRAPH A MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER MOUNTING SURFACE AND THE BOTTOM OF CEILING MOUNTED OBSTRUCTIONS SUCH AS BEAMS, OVERHANGS, AND LIGHT FIXTURES WITHOUT UNDULY OBSTRUCTING THE WATER SPRAY DISTRIBUTION -6- • L''' • F- W W W = 3 uO WIRE �m Y KEWMEW � _ EWE ■ o_ v 0 - ■■ ■ M ■■.. KEW .RE.. WIRE ow um amain 1 Q • ■ ■III mY WM ma WEE WIRE ..... mum 0Q ..WI ..mYY... !AVE EWE un.WEE W1 mu. mu W.. mu. m.. um mu. w WEE EWE m.. ..0 • MEW MU EN EWE WEE WEE WEE EVII!.. WEE gr =J MY i• u... W.. .u.. u... RE... Wu um 2a VY....Y ..... WEE m.. u... u... u/.. WIRE m....... RE... F— .... ..... m.. WEE NEW .YY m■. ? Z Y EWE •• i u.. m u m.. um ..OE ud mu ■ MEM u . s.. MMO 2O 0 N cc 0 5 10 15 20 25 30 35 40 45 50 55 60 = CEILING ANGLE 'A', DEGREES H A (MIN.) h NOTE: SPRINKLERS MUST BE INSTALLED WITH DEFLECTOR ARMS PERPENDICULAR TO THE CEILING RIDGE. GRAPH B MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LOCATED ON A LEVEL CEILING AND AN INTERSECTING PITCHED CEILING WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION ` ` 3 FEET � AXIMUM WHEN THERE ARE . ` NO SPRINKLERS ON COVERAGE AREAS: THE LEVEL CEILING Y (a) 20' x 20' (c) 16' x 16' (MIN.) �. (b) 18'x18' (d) 14'x14'&12'x12' 6 YY■ mY KEW WEE ® me WIREWEN mu KE W . WM KEW u . WIRE WEE WEE Will um �. Am KEW �i WEE 5 -- ..AMEN m.. NO...... H mu.. 'VI ®mO . ..a. W mu u.0 .W■ mu. =DK= .e. uulr _ WEE m.. EWE KEW um mu. u.0 .rs u.Y u/: M/.■ EWE m.. m.. 0 W WIRE WEE WWII EWE u_u. .mid= RM. m..■.w.us.■ ill LL KEW WEE KEW KEW MEW" SIEVE 1111■...A WEE EWE MEW EWE EWE Q - 4 uu .m..u....aMI. m ul.WM EWE MEW EWE EREU. - } RE. ■...Y. WIRE KEW ',WE u NEW m.. m...uu■WI■ RE... W wail um. urn Y.YV r.. m.. ■O. EWE EWE m.. uu. W 0 mmu. uxu.s u.Y m I. u/J um um WEE EWE WINE .u.. WEE cr Z 3 uu. .E.umur .us.uQm umu .uu...u..W.u..m Q W■. .E. Y... Y Y■..m YY. . Y... WEE .EWE II .m'.u■. KEW EWE WEE NEW NEW ■ ....1 ..... 21-- ...Y WEE WEN/ mr W EE WY muu...uu.■ ..u.m.. D mu. EWE umr.O / MY. um u ..0 u m./' m.. mu. m a mY mY WIRE ... mY mY Earn WEE .■I.A m.. um WINE m..uo m.l m /umum mu u . .- um umu... _ Z 2 u _u ® m.. Yu' w m o . a uu. ■m. uu■ u.■. m ■■ • ax ® w.Y WIRE. RE.. OEM WY WEE mP Q uRE. YI J ►v.u.Y UU.um.�A.mY WIRE mr �� J EWE WIRE u>'. V /0.. mt. WEE WEE /.!. EWE u.o 1/...01, KEW cri WEN mu O. um WEE mu ...V .u.. u.M ■��j!{��� d... MY. 1 um. mu 9 v.. um EWE EWE Man./ um u .. g i m.. m.. WYE O.iY■■..m Y... f_.. KEW ...�� WEE KEW ....■ ma um m.. maws MEW WIRE WIRE ® O. WIRE Yom■.■■.. uu. WIu uYl. WI■. Y... =UM EWE U■.■ mu U... WEE MEW m.. NEW WEE 0 m.. ..nu m.. 0 5 10 15 20 25 30 35 40 45 50 55 60 CEILING ANGLE 'A', DEGREES NOTE: SPRINKLERS MUST BE INSTALLED WITH DEFLECTOR ARMS PERPENDICULAR TO THE CEILING RIDGE. 0 GRAPH C MINIMUM REQUIRED SLANT DISTANCE BETWEEN A LEVEL CEILING AND A SPRINKLER LOCATED ON A PITCHED CEILING WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION —7— 4" TO 6" 10 r(SEE NOTE 2 ) AMOUNTING SURFACE 9 UNACCEPTABLE - - - - - - w w I.L. w 8 W Z ∎, 211 A r-__. • „ t CJ ,. II I w 7 ' , N (MAX.) N (MAX.) CI-0 1 ' . ' ' (SEE NOTE I) (SEE NOTE) ) Ma 6 NOTES: Q 1. UP TO A MAXIMUM OF ONE -HALF THE LENGTH OF M 5 _ ; i , ; , ; THE COVERAGE AREA BEING HYDRAULICALLY cr 0 ACCEPTABLE CACULATED. = 4 ■ II 1 T. ' I ® ® 2. THE MOUNTING SURFACE MUST BE LOCATED ' I ' ' ' ' WITHIN 4 TO 6 INCHES (101,6 to 152,4 mm)OF THE i i i ` ; , ' ; ; ; ' ; . ; , , ; : . . PEAK, IF IT IS NOT CONTINUOUS OVER THE FULL 3 10 15 20 25 30 35 40 45 50 55 60 LENGTH OF THE CEILING RIDGE. CEILING ANGLE 'A', DEGREES 3. SPRINKLERS MUST BE INSTALLED WITH DEFLECTOR ARMS PERPENDICULAR TO THE CEILING RIDGE. GRAPH D MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED AT A PEAK 10 ( SFc 0 U. T F 2) p -- 9 - w? UNACCEPTABLE w wa0 8 — L — - Ye - - \ A � CL — Z _ / I D -J w ) D - 7 J (MAX.) M�UA (SEE NOTE I ) aQ _ ACCEPTABLE NOTES: ) M NJ 6 cc 1. UP TO A MAXIMUM OF ONE -HALF THE LENGTH OF THE O COVERAGE AREA BEING HYDRAULLICALLY 5 CALCULATED. 0 5 10 15 20 25 30 35 40 45 2. 3 FEET (914 mm) IS THE MAXIMUM PERMITTED AND CEILING ANGLE, DEGREES 1 FOOT (305 mm) IS THE MINIMUM REQUIRED. (USE THE GREATER OF ANGLE 'A' OR ANGLE 'B') 3. SPRINKLERS MUST BE INSTALLED WITH DEFLECTOR ARMS PERPENDICULAR TO THE CEILING RIDGE. GRAPH E MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED ON A PITCHED CEILING OPPOSITE FROM AN INTERSECTING PITCHED CEILING 5 Emilia szlii min. nOisa isir 11111.= Illnill. COVERAGE AREAS: y U.1 MOM =MN aaaaasasa► ��s as CI L T_ ®iaamsaau°sasv.wsv . asm (a) 20' x 20' w 4 mom ® aia s — •'' � ®® a smdwzri �., (b) 18' x 18' 0 L s�iaamu (c) 16' x 16' _ _ - _ _ Luc) msm ssr .amr.sW.- - cc Z 3 maa aas. aamss .�aaa .asa• �a�• d 14' x 14' MI- mms.sssa II c U) aam . s (e) 12' x 12' lA i 4� maa•.aaasm'.aas — a mar ®aasr aam►�aaa 2 ��� Jm S/2 MAXIMUM ? Z saa ®a�am�m (SEE N I) M¢ araaam i U) 1 rwo®r,s An Ts� Ams NOTES: 10 15 20 25 30 35 40 45 1. UP TO A MAXIMUM OF ONE -HALF THE LENGTH OF THE COVERAGE CEILING ANGLE 'A', DEGREES AREA BEING HYDRAULICALLY CACULATED 2 SPRINKLERS MUST BE INSTALLED WITH DEFLECTOR ARMS PERPENDICULAR TO THE CEILING RIDGE GRAPH F MINIMUM REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION -8- • To prevent the possible release of an F978 Sprinkle r's heat responsive " " /,' ;z . %i/ " ' element (Bulb), due to exposure to heat sources other than abnormal fire, the 155'F/68'C F978 Sprinklers are only to be installed where the 11 i i 1 maximum (non -fire) temperature of all the sprinklers within a compart- ment will not exceed 100•F/38'C. H : 1: • / The sprinkler system piping must NOT be run through heating ducts, or 2' R. (TYP 1 / '" , MP) connected to the domestic hot water system. . i r` Ir 1 The following areas are examples of locations where the ambient FRONT EDGES temperatures may exceed 100•F/38'C. The F978 Sprinklers must NOT OF PREPUCE SOX � - be located in these areas unless the system designer can documenty�I■I, K' that the ambient temperature of the sprinklers will not exceed 100•F/38 with the heat source in use at maximum output. , 1. Where they will be exposed to the rays of the sun passing through glass Recessed Hearth Fireplace or plastic skylights. 2. In unventilated compartments containing a furnace or water heater. 3. In unventilated attics or in an unventilated - concealed compartment under an uninsulated roof. - :�' 4. Within 2 feet (610 mm) of an outside edge of a ceiling mounted, downward discharging diffuser. :�,t 5. Within 2 feet (610 mm) of the left or right edges of a horizontal .. '`_ ,.• 3 -6 discharging heat diffuser or within 3 feet (914 mm) of the front of a 3.-6" ('YP' ... +^ - _ � :' horizontal discharging heat diffuser. 2' R (TYPI `' 6. Within the following distances of exposed light fixtures: .j ■ SIDES 4 I Wattage Minimum OF STOVE • l b Range Distance '•* % Less than 250 6 inches (152 mm) � � • 250 -499 1 toot (305 mm) L t ■ 500 -999 2 feet (610 mm) 1000 and more 3 feet (914 mm) Coal or Wood Burning Stove 7. Within 18 inches (457 mm) of the side of an uninsulated heating duct. - 8. Within 1 foot (305 mm) of an uninsulated hot water pipe. a _ _•. .. -_ i 9. Within the shaded areas shown in in the adjacent illustrations , -� =� ,- -: l ' - - ; - 3 (TYP.) x \ \ '"� i s n t . , i. . - ' :_,.. : 1 ;3 :_ ";:. :j , 0y , ,,, .� , (TYP) 1 I Va�i.a'..o-j E: „ �: - ?; I 2' R.(TYPI (TTP) (TYPI 1111 , . 1 • • 6 • R. MP) \ N a N .. <<“ s< ;: _ t : z :' Open Hearth Fireplace { '''' - � 4 ' I — '..�• 1 9• ITYP TO FLUES/ i."f V ) : - . ;3 - - r - T B' ❑ r _ N.-y- • -- +..-t - t ,;,,�v1- ITYP) . ❑ --. I (TYE) -,1,. 4. 6' (TYP ) am 1 -I- I --- - - -- M- fi'(TYP) II II II -� = �'= = = �� —'� 6 (ALL AROUND) ii fl 1LL!J - -= .- ' Range or Wall Oven Furnace or Water Heater FIGURE H HEAT SOURCE CRITERIA —9-- r �- appropriate, advise the owner or his WRENCH TAB ' representative as to the following. _ _ MOUNTING CUP SLOT I. Lintels of at least 3 inches (76,2 mm) r `-, in height and preferably 8 inches 0 (203,2 mm) should be used over all passageways from one space to an- other, in order to reduce the possibil- ity of sprinkler operations outside of the fire area. II. Beams of at least 3 inches (76,2 OtL 1111111111111 � mm) in height should be used to WRENCH border each of 5 or more adjoining / areas of F978 Sprinkler coverage ■ � 0 (within the same compartment), in �� order to decrease the time to first ,., 1 -1/16" (27 mm) HEX sprinkler operation as well as to re- i/2" RACHET DRIVE i duce the possibility of multiple sprinkler operations. INDICATING BOSSES ARE IN LINE WITH DEFLECTOR ARMS Cold Soldering Criteria. Figures E FIGURE J and F provide the minimum spacing MODELS F874 SPRINKLER WRENCH requirements necessary for prevent ing the wetting (i.e., cold soldering) of the heat responsive element (Bulb) of sufficient adjustment in the is non cen to one e wh78 ich Sprinkler, • which I NSTALLATION , Sprinkler Assembly by under- or is adjacent to o which has operated. over- tightening the Sprink- Heat Source Criteria. Figure H out- NOTES ter /Mounting Cup Assembly. Re- lines the requirements relating to pre- Residential Fire Sprinkler Sys- adjust the position of the sprink- venting the possible release of an terns should only be designed and ler fitting to suit. F978 heat responsive element (Bulb), installed by those competent and due to exposure to heat sources other completely familiar with au- A leak tight 112 inch NPT sprink- than abnormal fire. tomatic sprinkler system design, ler joint should be obtained with installation procedures, and a torque of 7 to 14 ft. lbs. (9,5 to ,� techniques. 19,0 Nm). More than 21 ft. lbs. (28,5 Nm) of torque may distort The Technical Data Department the sprinkler orifice seat with should be contacted relative to consequent leakage. any questions. Proceed with the installation as fol- The F978 Sprinkler is inoperative lows: with the Disposable Protective Cap in place. 1. The pipe connected to the sprinkler fitting should be cut so that the bot- Do not install any bulb type torn face of the fitting is between sprinkler if the bulb is cracked or 2 - 1/16 and 2 -5/16 inch (52,4 and there is a loss of liquid from the 59,0 mm) above the ceiling line. By bulb. With the sprinkler held hor- using a 1/4 inch (6,4 mm) range for izontal, a small air bubble with the "D" dimension shown in Figure an approximate diameter of 1/16 A, the remaining 1/4 inch (6,4 mm) inch (1,6 mm) should be be pres- of adjustment can be used to com- ent. pensate for the possible manufac- turing variations in the make -in of the All sprinklers installed within sprinklers and the take -out of fittings compartments having a pitched (as permitted by ANSI B1.20.1). ceiling with one or two parallel horizontal ceiling ridges must be 2. Apply pipe thread sealant sparingly installed with the Deflector Arms to the sprinkler threads only. Use of perpendicular to the ceiling a Teflonr based pipe joint sealant is ridges. Failure to properly orien- recommended. tate the Deflector Arms may result in impaired fire protection due to 3. Remove the Protective Cap and cold soldering and /or inadequate then using the Model F874 Wrench, spray coverage. positioned as shown in Figure J, in- stall and tighten the F978 Sprink- Only use the Model F874 Sprink- ler /Mounting Cup Assembly into the ler Wrench for installation of the fitting. The F874 will except a 1 -1/16 F978 Sprinkler. Do not wrench on inch (27 mm) hex socket or a 1/2 the SprinklerlMounting Cup As- inch rachet drive. sembly other than as shown in Figure J. After Installing the Sprinkler /Mount Ing Cup Assembly, the Protective Do not attempt to make - for in - Cap is to be reinstalled until the ceil- -10— - DuPont Registered Trademark ing installation and finishing is corn- fore and after installation. Sprinklers and larvae by gently brushing plete. The Cap is intended to help damaged by dropping, striking, with a feather duster or gently prevent damage to the F978 Sprink- wrench twist/slippage, or the like, must vacuuming with a soft bristle (i.e., ./'N , ler during ceiling installation and/or be replaced. Also, replace any spank- dusting) brush attachment. during application of the finish coat- ler that has a cracked bulb or that has ing of the ceiling. Also, the tip of the lost liquid from its bulb (Ref. Instal- The minimum vertical clearance Cap can be used to mark the center lation Section). between the tops of free standing of the ceiling hole into plaster board, partitions, room dividers, cab- • ceiling tiles, etc. by pushing the ceil- NOTES inets, storage racks, stock piles, ing product against the Cap. Absence of an Escutcheon Plate etc., and the sprinkler deflector is may delay the time to sprinkler NOT to be less than the clearance 5. After the ceiling has been completed operation in a fire situation. given below. with the 2 -5/8 inch (66,8 mm) diam- eter clearance hole and in prepara- Before closing a fire protection Horizontal Distance Vertical tion for installing the Cover Plate system main control valve for from Sprinkler Clearance Assembly, remove and discard the maintenance work on the fire pro- to Item, ft. (m) In. (mm) , Protective Cap, and verify that the tection system which it controls, ( Deflector falls freely. permission to shut down the af- More than 6 fected fire protection systems (1,8) 24 (610) If the F978 Sprinkler has been dam- must be obtained from the proper From 3 to 6 aged and the Deflector does not fall authorities and all personnel who (0,9 to 1,8) 19 (483) freely, replace the entire F978 may be affected by this action Between 2 and 3 Sprinkler assembly. must be notified. (0,6 to 0,9) 16 (406) From 1 to 2 6. Screw -on the Cover Plate Assembly It is recommended that automatic (0,3 to 0,6) 13 (330) until its flange comes in contact with sprinkler systems be inspected Less than 1 10 (254) the ceiling. and maintained in accordance • (0,3) with the advice and suggestions Do not screw -on the Cover Plate given in NFPA 13, 13A, 13D, and ( Assembly such that it will lift a ceiling 13R, as applicable. Exercise suitable safety precau- panel out of its normal position. tions in the use and storage of It is recommended that automatic highly flammable and potentially If the Cover Plate Assembly can- sprinkler systems be inspected guar- explosive materials. The rapid not be engaged with the Mount- terly by a qualified Inspection Service. rate of fire development and ing Cup or the Cover Plate As- spread which can be caused by sembly cannot be engaged The F978 Sprinklers must only be re- such materials can reduce the sufficiently to contact the ceil- placed with pendent sprinklers which ability of the sprinkler system to ing, the Sprinker has been posi- are listed for residential fire protection aid in the control of a fire in tioned incorrectly and must be service and which have the same nom- which they are involved. repositioned according to Step inal K- factor, the same coverage area, No.1. the same or lower flow ratings (as indi- cated under "Hydraulic Design Cri- teria"). • All residential sprinklers installed within a compartment (as defined by the NFPA) must have the same heat responsive thermal characteristic, and their temperature ratings are to be within 10'F of each other. CARE AND MAINTENANCE REMODELING NOTES The F978 Sprinklers must never be Wet pipe sprinkler systems must When remodeling, such as by adding shipped, stored, or used where their be maintained at a minimum tem- false beams or light fixtures or chang- temperature will exceed 100'F/38'C perature of 40'F 14'C. Exposure to ing the location of compartment walls, and they must never be painted, freezing temperatures can result first verify that the new construction plated, coated, or otherwise altered in bursting of the pipe and /or will not violate the installation require - after leaving the factory. Modified sprinkler. ments stated under WARNINGS. Alter sprinklers must be replaced. Sprink- the new construction and/or the sprink- lers that have been exposed to corro- Do NOT enclose sprinklers within ler system to suit the requirements of sive products of combustion, but have drapes, curtains, or valances. this document. not operated, should be completely cleaned by wiping the sprinkler with a Do NOT hang anything from the cloth or by brushing it with a soft bristle sprinklers. brush. Automatic sprinklers are NOT to NOTE be tested with a heat source. Op- Particular care to prevent over- eration of the heat responsive ele- heating must be exercised when ment (Bulb) can result. a storing sprinklers in cars, trucks, N. trains, or other vehicles on warm, Do NOT cleanse the sprinklers bright sunny days. with soap and water, detergents, ammonia, cleaning fluids, or Care must be exercised to avoid dam- other chemicals. Remove dust, age to the F978 Sprinklers - both be- lint, cobwebs, cocoons, insects, —11— ORDERING PROCEDURE • LIMITED WARRANTY Orders for the Model F978 Designer The manufacturer warrants for a period of one year from the date of sale Residential Concealed Pendent (warranty period) that the product(s) sold hereunder are free from defects • Sprinklers must include the descnp- in material and workmanship. Our obligation under this warranty is limited tion and Product Symbol Number to repair or replacement, or, at our option, we will repay the price paid for (PSN) where applicable. the product(s), plus any transportation charge paid by the purchaser. In the case of replacement, we will pay the transportation charges to the Contact your local distributor for avail- location of the defective product. We must be given the opportunity to ability. inspect any product you believe to be defective. To make a claim under this limited warranty, you should contact our Sales Services Manager at Sprinkler Assemblies: (401) 886 -3105. Specify: 4.2 K- factor, 155'F/68 Model F978 Residential Concealed THERE ARE NO OTHER WRITTEN OR ORAL WARRANTIES. ALL Pendent Sprinkler with (specify type IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR finish) Cover Plate, PSN (specify). A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO THE DURATION OF THE LIMITED WARRANTY SET FORTH ABOVE. Painted White Cover Plate . .... ... PSN 51- 978 -0.155 The manufacturer does not assume any other obligation in connection Chrome Plated with the sale of the product(s) by purchaser. Cover Plate .. . PSN 51- 978 -9.155 Contact your local distributor for This warranty shall not apply to any product(s) which have been installed availabilty. in violation of written instructions furnished by the manufacturer, repaired or altered, misused or damaged, or not properly maintained. Product Symbol Numbers are not specified when ordering F978 Sprink- The manufacturer is not liable for indirect, incidental or consequential lers with a special painted finish for the damages in connection with the use of the product(s). Cover Plate. It is suggested that a color chip be provided when ordering Some states do not allow limitations on how long an implied warranty special painted finishes. Otherwise, lasts, or exclusion or limitation of incidental or consequential damages, responsibility for duplication of the de- so the above limitations or exclusion may not apply to you. sired finish cannot be accepted. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU Separately Ordered Parts: MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO Specify: Model F874 Sprinkler STATE. .. Wrench, PSN 56- 976 -1 -001. Order for NFPA publications should be addressed to the: Publication Sales Department NFPA PATENTS ' Batterymarch Park Quincy, MA 02269 The following patent is applicable to Replacement Parts: the Model F978 Residential Con - Specify: (description) for use with cealed Pendent Sprinkler: F978 Sprinklers, PSN (specify). U.S.A. 5,152,344 Sprinkler /Mounting Cup Assemblies are not available as replacement parts. • WEIGHT Painted White I35'F/57•C Cover Plate The nominal weight of the Model F978 Assembly PSN 56- 978 -0 -155 Residential Concealed Pendent Chrome Plated Sprinkler is 7.2 oz. (204 g). 135•F/57•C Cover Plate Assembly PSN 56- 978 -9 -155 Product Symbol Numbers are not specified for replacement Cover Plate Assemblies with special painted fin- ishes. Records are not maintained of previously ordered special painted fin- ishes. Therefore, it is suggested that a color chip be provided when ordering replacement parts with special painted finishes. Otherwise, responsibility for duplication of the desired finish cannot be accepted. ® Reg trademark of GRINNELL CORPORATION, 3 TYCO PARK EXETER NH 03833 A "NCO INTERNATIONAL LTD COMPANY Sheet % of q Grinnell Fire Protection, Portland, OR 2870 N.W. 29TH AVE. PORTLAND, OREGON Date 01/06/00 ift Job: RESLOT7S PROJECT INFORMATION Job_ REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR • Occupancy RESIDENTIAL 13D Area of Operation 115 square feet Area per Sprinkler 256 SQ FT MAX Number of Sprinklers Calculated: 1 heads Authority having Jurisdiction_ _ NFPA -13 Hose 10.0 gpm Outside Hose System type_ _ Wet Water Supply _ 69.00 psi Static, 65.00 psi Residual @ 750.0 gpm Sprinklers _ _ 1/2 inch orifice CALCULATION SUMMARY Demand 41.71 psi @ 16.0 gpm @ B.O.R. 53.49 psi @ 26.0 gpm @ Supply 68.99 psi available @ 26.0 gpm Demand is below curve by 15.50 psi Notes: • Sheet 1 REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR *: Static = 69.00 psi Residual = 65.00 psi at a flow of 750.0 gpm F: Demand at BOR = 41.71 psi with 16.0 gpm flowing. D: System demand = 53.49 psi with 26.0 gpm flowing. *: Pressure available = 68.99 psi when 26.0 gpm is flowing. Demand is below curve by 15.50 psi. (22.5 %) for Remote Area 1 PSI Multiply pressure scale by 10 N1.85 Graph 10 + +- - + - - -+ + + + + + + + 9+ + 8+ + 7* + * 6+ + D 5+ + F. 4+ + 3+ + 2+ + 1+ + 0 + +- - + - - -+ + + + + + + + 1 2 3 4 5 6 7 8 9 10 GPM Multiply flow scale by 100 • Sheet 3 Grinnell Fire Protection, Portland, OR Description of Fitting abbreviations Code Description T Tee E Ninety degree elbow PT Plastic Tee PE Plastic 90 degree Elbow BKF Backflow preventor MTR Meter Loss GV Gate valve Description of Other abbreviations Code Description BL Branch Line CM Cross Main PT Total pressure PE Pressure loss due to elevation changes PF Pressure loss due to friction A.5 Raised to the power of .5 (Square Root) A Actual pipe length F Fitting equivalent pipe length T Total pipe length RESLOT7S '01/06/00 3:37pm Sheet i i Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Raw data previous to any calculations No. Code Diam Length Kfacl Kfac2 Press Elev Hose HW Vel Fittings 1 BL1 1.109 7.2 4.2 14.50 0.00 0.0 150 32 3PE 2 CM1 1.109 8.0 BL1 0.00 0.00 0.0 150 32 1PT 3 CM1 1.109 8.0 0.00 0.00 0.0 150 32 2PT,2PE 4 RI 1.109 68.0 CM1 -6 0.00 30.00 0.0 150 32 4PT,4PE,1BKF 5 BU 1.109 35.0 RI 0.00 0.00 0.0 150 32 4PE,1PT 6 UG 1.109 45.0 BU -6 0.00 0.00 0.0 150 32 1T,2E,1MTR,1GV 7 UG 1.109 0.0 0.00 0.00 10.0 150 32 RESLOT7S '01/06/00 3:37pm Sheet Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi /ft) (psi) Ref (fps) Notes Branchline No. 1 C = 150 A 7.2 PT 14.50 1 End head 16.0= 4.20(14.50) ^.5 F 21.0 PE 0.00 1 16.0 1.11 3PE T 28.2 0.04343 PF 1.22 5.31 PT 15.72 2 Cross main Jct K- factor for branchline no. 1 = 16.0/(15.72) ^.5 = 4.03 RESLOT7S •01/06/00 3:37pm Sheet4 Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi /ft) (psi) Ref (fps) Notes Cross main 1 C = 150 A 8.0 PT 15.73 2 BL1 16.0= 4.03(15.73) ^.5 F 5.0 PE 0.00 2 16.0 1.11 1PT T 13.0 0.04347 PF 0.57 5.31 A 8.0 PT 16.29 3 F 24.0 PE 0.00 3 16.0 1.11 2PT 2PE T 32.0 0.04347 PF 1.39 5.31 PT 17.68 4 Top of Riser K- factor for Cross main 1 = 16.0/(17.68)".5 = 3.81 • RESLOT7S •01/06/00 3:37pm Sheet 7 • Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi /ft) (psi) Ref (fps) Notes Riser C = 150 A 68.0 PT 17.68 4 CM 1 F 48.0 PE 12.99 (EL= 30.00 ft) 4 16.0 1.11 4PT 4PE T 116.0 0.04347 PF 5.04 5.31 1BKF PT 35.71 5 B.O.R. Bulk C = 150 ___= A 35.0 PT 41.71 5 17.3 = 2.68(41.71) ^.5 F 33.0 PE 0.00 5 17.3 1.11 4PE 1PT T 68.0 0.05018 PF 3.41 5.74 PT 45.13 6 K- factor for Bulk = 17.3/(45.13) ".5 = 2.58 Under ground C = 150 A 45.0 PT 45.13 6 B.O.R. F 19.8 PE 0.00 6 17.3 1.11 1T 2E T 64.8 0.05023 PF 3.26 5.75 1MTR 1GV A 0.0 PT 48.38 7 10.0 gpm = Hose F 0.0 PE 0.00 7 27.3 1.11 T 0.0 0.00000 PF 0.00 9.07 PT 48.38 8 Supply Jct Available flow at 48.38 psi is 1819.9 gpm which is 1792.6 gpm from curve. Supply pressure available with 27.3 gpm flowing is 68.99 psi, thus system requirement is 20.61 psi below supply curve. (29.9 %) • RESLOT7S - 01/06/00 3:37pm Sheet 15 Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Node Detail Discharge Pressure Outlet Elevation Node (gpm) (psi) K -Value Source (ft) Comments 1 16.0 14.50 Orif= 4.20 30.00 2 - 15.73 30.00 3 - 16.29 30.00 4 - 17.68 30.00 5 - 41.71 0.00 6 - 45.13 0.00 7 10.0 48.38 Hose 0.00 8 - 48.38 Supply 0.00 RESLOT7S -01/06/00 3:37pm Sheetilt + Grinnell Fire Protection, Portland, OR Sprinkler Systems Hydraulic Flow Calculations REDWOOD VISTA LOT #7 - SINGLE HEAD 11999 SW TREEVIEW CT TIGARD, OR Pipe Detail Actual Total Elev Fric Fric Press Press Pipe Diem Len Len Head Flow Loss Loss Vel Nodes @ Beg @ End No. (inch) (Ft) (Ft) (Ft) (Gpm)(Psi /Ft)(Psi)(Fps) Beg End (Psi) (Psi) 1 1.11 7.2 28.2 0.00 16.0 0.0434 1.22 5.3 1 2 14.50 15.73 Fit= 21.0 3PE 2 1.11 8.0 13.0 0.00 16.0 0.0435 0.57 5.3 2 3 15.73 16.29 Fit= 5.0 1PT 3 1.11 8.0 32.0 0.00 16.0 0.0435 1.39 5.3 3 4 16.29 17.68 Fit= 24.0 2PT 2PE '4 1.11 68.0 116.0 30.00 16.0 0.0435 5.04 5.3 4 5 17.68 41.71 Fit= 48.0 4PT 4PE 1BKF 5 1.11 35.0 68.0 0.00 17.3 0.0502 3.41 5.7 5 6 41.71 45.13 Fit= 33.0 4PE 1PT 6 1.11 45.0 64.8 0.00 17.3 0.0502 3.26 5.7 6 7 45.13 48.38 Fit= 19.8 1T 2E 1MTR 1GV 7 1.11 0.0 0.0 0.00 27.3 0.1168 0.00 9.1 7 8 48.38 48.38