Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
/99 '9- c���SB' /G l / $62 7 r /r % ( C DRY SPRINKLERS, STANDARD RESPONSE • HORIZONTAL SIDEWALL MODEL F960/Q -46 DESIGNER, SR, 5 mm BULB TYPE 1/2" (15 mm) ORIFICE construction, or installation economy use in applications where the sprin- GENERAL DESCRIPTION considerations. klers and/or a portion of the connect- ing piping may be exposed to freezing The 1/2 inch orifice Model F960/Q -46 Available in a wide range of operating temperatures (e.g. horizontal piping Standard Response Designer Dry temperatures and in order lengths of extensions from a wet pipe system Horizontal Sidewall Sprinklers (Ref. 1/2 inch increments from 2 -1/2 to 48 through a wall to protect a freezer or Figure A) are automatic sprinklers of inches, the F960/Q -46 is intended for an unheated area of a building). the frangible bulb type. They are "standard response - standard orifice sidewall sprinklers" intended to be TEMPERATURE RATINGS AND BULB used in fire sprinkler systems de- UOUID COLOR CODE: signed in accordance with the stand- 1 3 5 ° F / 57 °C Orange and installation rules recognized by the 155 °F / 68 °C Red applicable Listing or Approval agency 175 °F / 79 °C Yellow _____________ 200 °F / 93 °C Green (e.g., UL Listing is based on NFPA 13 ��� C111111110 �4 286 °F / 141 °C Blue requirements). 1 360 °F / 182 °C Mauve They are designed for installation NOMINAL K- FACTOR: along a wall and just beneath a smooth 360°F ( GPM / psil / ceiling. Installed with their centerline of 79.2 (LPM / barin) waterway horizontal, these sprinklers produce a quarter - spherical water dis- "S" ORDER LENGTHS: charge pattern that is predominately s 2 -1/2 to 48 inches in 1/2 inch increments .. directed downward and outward from the deflector; however, a portion of the FINISH COMBINATIONS: spray is directed towards the backwall. Sprinkler Escutcheon Chrome Plated Chrome Plated Horizontal sidewall sprinklers are gen- Chrome Plated White Painted erally used in lieu of pendent sprin- Natural Brass White Painted klers because of aesthetic, building "S" ORDER LENGTH 4" (101 6mm) 2-1/2 "(63.5mm) MINIMUM — f- _9/16• (14 3mm) NOMINAL 48" (1.22 m) MAXIMUM NOMINAL COMPONENTS: MAKE-IN MOUNTING SURFACE (WALL) 1 - Deflector r " _ - - - - 3 2-FraMe \ r- ' 3 -Guide Tube I 2 3 ; 1 1 Sub - assembly I. NPT —o 3/8" ' VENT 4 S __J (95mm) 4 -Water Tube HOLE , � 3.5" i 5-Spring , ..,0� iiiiiiv1 e.: 6- Compression ____�� ����4W ,V,a— Screw _' I IIMI A. I" OIA. 7•Bulb 7 - - -- I (25.4mm) 8 -Bulb Seat ���" a a 1 5/16" �V. p.D�- r ...•n —H' 9- Casing 8 (7 9mm) • 10-Yoke 6 - i N 11 -Inlet ) 8 9- 10 ' II— J 12 -Plug — CENTERLINE 14 12 _____ - - - -J 13 -0-Ring Seal OF WATERWAY 15 kIN 3° (76. ER ) 13 14- Escutcheon, ** SHOWN 90 OUT OF POSITION Inner Piece 1 -3/4" (44.5mm) * TEMPERATURE RATING IS DIAMETER IS- Escutcheon, INDICATED ON DEFLECTOR (RECOMMENDED) _ Outer Piece FIGURE A MODEL F960/0 -46 DRY HORIZONTAL SIDEWALL SPRINKLER WITH STANDARD ESCUTCHEON PLATE Printed in U.S.A. 6 -98 TD555 50 IIIMMIIII NO . 5 TECHNICAL DATA P ARTIAL CURVE ONLY •. p . PARTIAL CURVE ONLY 0. 45 MAXIMUM PRESSURE .��� MAXIMUM PRESSURE I 175 PSI ...a.�.� 12.07 BAR O . m u The 1/2 inch orifice Model F960/Q -46 ....am 3.0 • � %� . i al- ■■■■■° Standard Response Dry Horizontal , • 40 .... ...................... o.. MMUMMEMEMMEMOUPAmilmnia m00■■■■■■wI■O Sidewall Sprinklers are rated for use at cc oo iia. ■■�■■■■■■I.■■O sc 3 5 . ............................. . a 2 . 5 ■ I �■� °MONA a maximum service pressure of 175 • H MAIM= .....o.. �M.q.°. i m■ ■ ■ ■OI.■OO 11...117 psi. The available temperature ratings, °.° � ._.__ h '�� ? v o o � order lengths, sprinkler finishes, and CL Via.. „ �� it 2.0 , , , • „ escutcheon plate finishes are given in mom 25 u �:'. �� . � �.. N I , I ' i , Z Figure A. ._.. —� mo._..... .. .e v�' .i .a.. W , , i _p A d .. z0 ...... �� �` � : '�.�: d 1 .5 A■MMIOO The F960/Q -46 must be Installed with .... . O : '. m "um.. O �MM: ? •�.MO '' I■ ■ ■ ■O■°■■ a deflector to ceiling distance of 4 to 12 15 : o"'' „=.= .�... ■■OV AI■■ ■■ ■ ■■■■■■■ ........Af........�. .... OOorm■■ ■m ■m■ inches. To meet this requirement, the % ... .....r.w............. .... 1.0 r .O■■■■■00■O centerline of the sprinkler waterway • 10 mu.N s.ai ■■O ■ ■ ■ ■ ■ ■ ■ ■ ■■■ W E..aVW. m...00.OMn ■ O (Ref. Fig, A) must be between 4 -5/16 a . 'W :C ...:: ; - MI N=WM W� and 12-5/16 inches below the ceiling. 5 0.5 10 15 20 25 30 35 40 50 75 100 125 150 The nominal discharge curves plotted DISCHARGE IN U S. GALLONS PER MINUTE DISCHARGE IN LITRES PER MINUTE (GPM) (LPM) in Figure B represents the flow "0" in GPM (LPM) as determined by the for - FIGURE B mula: NOMINAL DISCHARGE CURVES Q =K,IT When the F960/Q -46 is in service, The 135 °F /57 °C through 286 °F /141 °C where the nominal sprinkler discharge water is prevented from entering the Model F960/Q -46 Standard Response coefficient "K" equals 5.5 (79,2); and assembly by the Plug and 0-Ring Seal Dry Horizontal Sidewall Sprinklers are "p" equals the residual pressure In psi in the Inlet of the Sprinkler. Upon expo- approved by Factory Mutual Research (bar). Listing standards permit the ac- sure to a temperature sufficient to op- Corporation for use in Light Hazard tual value of "K" to vary from 5.3 to 5.8 erate the Bulb, the Bulb shatters and Occupancies. (76,4 to 83,6); however, for hydraulic the Bulb Seat is released. The corn- calculations a K- factor of 5.5 (79,2) Is pressed Spring is then able to expand The laboratory listings and approval to be applied. and push the Water Tube as well as the only apply to the order lengths, sprin- Guide Tube outward. This action simul- kler finishes, and escutcheon plate fin- Figure A illustrates the F960/0 -46 as- taneously pulls outward on the Yoke, ishes stated in Figure A. sembly. The Plug and Inlet are brass - withdrawing the Plug and 0-Ring Seal per ASTM B16 (C36000), and the 0- from the Inlet and initiating water flow. The Model F960/0-46 Standard Re- Ring Seal is silicone rubber. The Cas- sponse Dry Horizontal Sidewall Sprin- ing is galvanized carbon steel per The Escutcheon Plate has been de- klers are accepted by the City of New ASTM A135 Grade A. The Frame is signed to provide 1 inch of total hors- York under MEA 214 -94 -E. bronze per ASTM B62 (C83600), the zontal adjustment (plus or minus 1/2 Deflector is brass per ASTM 836 inch), to assure proper field position- WARNING (C22000), the Compression Screw is ing and to reduce the accuracy to The Model F960/Q - Standard Re - bronze per ASTM 8140 (C31400), and which the sprinkler fitting must be in- sponse Dry Horizontal Sidewall the two pieces of the Escutcheon Plate stalled. The 3 inch outside diameter of Sprinklers described herein must be are 0.020 inch thick carbon steel per the outer piece of the Escutcheon installed and maintained in compli SAE 1008/1010. The Water Tube is Plate combined with the 1 -3/4 inch di- ance with this document, as well as brass per ASTM B135 (C33000). The ameter clearance hole size also con- applicable standards of the National Bulb Seat, Spring, and Yoke are all tributes to the ease of installation by Fire Protection Asociation, in addi Type 302 stainless steel. The Guide covering offset clearance holes. tion to the standards of any other Tube sub - assembly is constructed of authorities having jurisdiction. Fail Type 302 stainless steel and brass per The Escutcheon Plate is a separable ure to do so may impair the integrity ASTM B16 (C36000) two -piece design which allows installa- of these devices. tion of the sprinklers and pressure testing of the fire protection system, The owner is responsible for main - prior to wall construction and /or appli taining their fire protection system SYSTEM DESIGN cation of a finish coat to the wall. It also and devices in proper operating con - permits refinishing of a wall surface dition. The installing contractor or The F960/Q -46 Dry Horizontal Side - without having to first shut down the manufacturer should be contacted wall Sprinklers are to be installed in the fire protecton system and remove the relative to any questions. 1 inch NPT outlet of a malleable iron sprinklers. threaded tee fitting per ANSI B16.3 or The Model F960/Q - Standard Re - cast iron threaded tee fitting per ANSI sponse Dry Horizontal Sidewall B16.4 with the end sprinkler fitting on Sprinklers must only be installed in a branch line to be plugged as shown APPROVALS AND STANDARDS fittings that meet the requirement of in Figure A; or, installed in the side the System Design section. outlet of a Gruvlok® Figure 7105 Sock - The 135 °F /57 °C through 360 °F /182 °C ItTM x 1 inch NPT side outlet fitting Model F960/Q -46 Standard Response manufactured by Grinnell Corporation. Dry Horizontal Sidewall Sprinklers are listed by Underwriters Laboratories NOTES Inc. and Underwriters' Laboratories of Do not install the F960 into any other Canada for use in Ordinary Hazard type fitting without first consulting Occupancies. e • SPRINKLER SPIRIT the Technical Data Department. Fail- Failure to prevent the formation of FITTING / LEVEL ure to use the appropriate fitting may condensate could result in the build- result in binding of the inlet Plug or up of ice around the releasing compo- f - CENTERLINE insufficient engagement of the inlet nents and, consequently, either an in- _�i O SPRINKLER 1 pipe threads with consequent leakage. advertant operation of the sprinkler 6 INCH (1 50 mm) OR WATERWAY t or, impaired operation due to reduced LONGER PIPE NIPPLE Branch, cross, and feedmain piping thermal sensitivity. SPRINKLER I SPIRIT � \ that is connected to dry horizontal LEVEL �� sidewall sprinklers and subject to • ��a freezing temperatures must be pitched INSTALLATION (_ SPRINKLER for drainage in accordance with the DEFLECTOR minimum requirements of the National Fire Protection Association for dry pipe NOTES FIGURE C sprinkler systems. The Model F9601Q -46 Dry Horizon- LEVELING OF tal Sidewall Sprinkler must only be SPRINKLER FITTING The outer piece of the Escutcheon installed in fittings that meet the re- AND DEFLECTOR Plate cannot be used to hold the quirements of the System Design sec - F960/0 -46 Sprinkler in position. Pipe tions. support must be provided in accord- ance with the minimum requirements Refer to the System Design section for OUTER PIECE of the National Fire Protection Asso- other important requirements regard - ciation with respect to armovers and ing piping design. 90 wall mounted sidewall sprinklers. Do not install any bulb type sprinkler When dry horizontal sidewall sprin- if the bulb is cracked or there is a loss ESCUTCHEON, klers are to be used in wet pipe sprin- of liquid from the bulb. With the sprin- INNER PIECE ` 7 kler systems protecting areas subject kler held horizontal, a small air bub- 1` 1 to freezing temperatures (e.g., .cool- ble should be present. The diameter of �. ers or freezers), consideration must be the air bubble varies from approxi- r %L y g iven to the appropriate length of the mately 1116 inch for the 135°F157 °C sprinkler that will prevent freezing of rating to 118 inch for the 1 / / the water in the connecting pipes, due 360°F! 182 °C rating. to conduction. When the temperature ,- surrounding the wet pipe sprinkler sys- The sprinkler fitting should be located / tern is maintained at a minimum tern- so that the face -of- fitting to mounting perature of 40 °F /4 °C, the following are surface distance is within plus or mi- • PRONGS the minimum recommended lengths nus 1/4 inch (6,4 mm) of the sprinkler between the face of the F960/0 -46 order length. The remaining escutch- FIGURE D sprinkler fitting and the outside surface eon plate adjustment can then be used ESCUTCHEON OUTER PIECE of the protected area (i.e., length ex- to compensate for the possible manu- INSTALLATION posed to minimum ambient of facturing variations in the take -out of 40 °F /4 °C): the fittings, as well as in the make -in of the sprinklers (as permitted by ANSI 1. With pipe thread sealant applied to • 6 inches when the temperature B1.20.1). the pipe threads, hand tighten the within the protected area is 0 °F; sprinkler into the sprinkler fitting. The F960/0 -46 must be installed with • 12 inches when the temperature a deflector to ceiling distance of 4 to 12 2. Wrench tighten the F960/0 -46 by within the protected area is -20 °F; inches. To meet this requirement, the wrenching on the Casing with a pipe centerline of the sprinkler waterway wrench, whenever the Casing is • 18 inches when the temperature (Ref. Fig, A) must be between 4 -5/16 readilyaccessable .Otherwise,usea within the protected area is -40 °F; and 12 -5/16 inches below the ceiling. 10 inch adjustable wrench applied to and, the wrench flats of the Frame. The Model F960/0 -46 must be in- • 24 inches when the temperature stalled with the centerline of the water- NOTES within the protected area is -60 °F way horizontal and perpendicular to A leak tight 1 inch NPT sprinkler the back wall surface. The word "TOP" joint should be obtained with a For protected area temperatures be- on the deflector must face upwards torque of 20 to 30 ft.lbs. Higher tween those given above, the minimum toward the ceiling. levels of torque may distort the recommended length from the face of Inlet with consequent leakage or the fitting to the outside of the pro It is recommended that a lightweight impairment of the sprinkler tected area may be determined by in- spirit level (less than 1 pound), be used terpolating between the indicated val to level the sprinkler fitting and the Do not attempt to make -up for in- ues. sprinkler Deflector, as shown in Figure sufficient adjustment in an es- C. cutcheon plate by under- or over - NOTE tightening the sprinkler. Readjust When the F960 / Q -46 Sprinklers NOTE the position of the sprinkler fitting penetrate a wall into an area subject The Deflector is angled forward- to suit. to freezing, the clearance space downward at a nominal angle of 3.5 °; around the Sprinkler Casing must be consequently, the spirit level must be 3. After the wall has been installed or completely sealed, in order to prevent carefully positioned left -to- right, the finish coat has been applied, in- the leakage of moist air into the freez- when using it to level the deflector. stall the outer piece of the Escutch- ing area which might result in the eon as follows: formation of condensate around the Proceed with the installation as fol Frame, Deflector, Bulb Seat, or Bulb. lows: a. Refer to Figure D and place the - outer piece of the Escutcheon PSN 60 - XXX - X - XXX I "S" ORDER LENGTH TEMPERATURE INCHES DECIMAL RATING l (FOR EXAMPLE) 940 135 °F / 57 °C - 025 2.5° SPRINKLER ESCUTCHEON PLATE 941 155 °F / 68 °C FINISH FINISH 080 8.0' 942 175 °F / 79 °C 0 CHROME PLATED WHITE PAINTED 180 18.0° 94.3 200 °F / 93 °C 1 NATURAL BRASS WHITE PAINTED 185 18.5° 944 286 °F / 141°C 9 CHROME PLATED CHROME PLATED 475 47.5° 945 360 °F / 182 °C 480 48 0" TABLE A - PRODUCT SYMBOL NUMBER SELECTION FOR MODEL F960/0 -46 SR DRY HORIZONTAL SIDEWALL SPRINKLERS WITH STANDARD ESCUTCHEON PLATES over one side of the Deflector Before closing a fire protection system with one pair of the Prongs at the control valve for maintenance work on ORDERING PROCEDURE bottom as shown in Figure D, the fire protection system which it con - and with the other pair of Prongs troll, permission to shut down the af- Model F960/0 -46 Standard Response directly above the Deflector. fected fire protection system must be Dry Horizontal Sidewall Sprinklers are obtained from the proper authorities furnished based upon "Ordered b. Pass the outer piece of the Es- and all personnel who may be affected Lengths" as measured from the face of cutcheon over the Deflector by by this action must be notified. the wall to the face of the fitting in horizontally swinging the outer which the individual sprinkler is to be piece 90° towards the wall. It is recommended that automatic installed (refer to Figure A). After the sprinkler systems be inspected guar- measured length is taken, round the c. Slide the outer piece of the Es- terly by a qualified Inspection Service. measurement up or down to the near- . cutcheon over the inner piece est 1/2 inch increment of 2 -1/2 to 48 until the outer piece contacts the NOTES inches. Orders must include the de- wall. It is recommended that the piping scription and Product Symbol Num- connected to dry horizontal sidewall bens. sprinklers be periodically checked to assure that proper pitch and drainage Sprinklers: CARE AND MAINTENANCE is in accordance with the minimum Specify: (temperature rating) Model requirements of the National Fire F960/Q -46 SR Dry Horizontal Sidewall Automatic sprinklers must never be Protection Association, if the piping is Sprinkler with (specify type) finish shipped or stored where their tempera- subject to freezing temperatures. Sprinkler and (specify type) finish tures will exceed 100 °F /38 °C and they Standard Escutcheon Plate and "S" must never be painted, plated, coated A Vent Hole is provided in the Bulb Order Length of (specify) inches, PSN or otherwise altered after leaving the Seat (Ref. Figure A) to indicate that (specify from Table A). factory. Modified sprinklers must be re- the Dry Horizontal Sidewall Sprin- placed. Sprinklers that have been ex- kler is remaining dry. Evidence of Contact your local distributor for avail - posed to corrosive products of corn- leakage from this Vent Hole is an in- ability. bustion, but have not operated, should dication that there may be weepage be replaced if they cannot be corn- past the 0 -Ring Seal and, therefore, it Replacement Parts: pletely cleaned by wiping the sprinkler is an indication that the sprinkler Specify: F960/Q -46 Standard Outer with a cloth or by brushing it with a soft must be removed for determining the Escutcheon with (specify finish), PSN bristle brush. cause of leakage (e.g. an improper in- (specify). stallation or an ice plug). The fire pro - Care must be exercised to avoid dam- tection system control value must be Painted White .. . . PSN 56-960-0-007 age to the sprinklers — both before closed and the system drained before Chrome Plated . ... PSN 56.960 -9 -007 and after installation. Sprinklers dam- removing the sprinkler aged by dropping, striking, wrench twist/slippage, or the like, must be re- PATENTS • placed. Also, replace any sprinkler that has a cracked bulb or that has lost WARRANTY U.S.A. Patent No. 5,188,185 applies to liquid from its bulb. (ref. Installation the Model F960/Q -46 Standard Re- Section Note.) Seller warrants fora period of one year sponse Dry Horizontal Sidewall Sprin- from the date of shipment (warranty klers. NOTES period) that the products furnished Absence of the outer piece of an es- hereunder will be free from defects in cutcheon, which is used to cover a material and workmanship. — clearance hole, may delay the time to sprinkler operation in a fire situation. For further details on Warranty, see Price List. ® Reg. trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833 A tI4CO INTERNATIONAL LTD. COMPANY 1 t. PENDENT & RECESSED PENDENT RESIDENTIAL SPRINKLERS MODEL F680 DESIGNER, BULB TYPE, 3.0 K-FACTOR, 155°F & 175 °F Components: I ESCUTCHEON 1/2" NPT PLATE SEATING SURFACE 7 I 1 - Frame — 7/16" (11,1 mm) . Z • Button M AKE -iN� WRENCH 4WI ! 3 - Gasketed i . FLATS t Su Plate - -� i �'■r ,in C 4 - Bulb , i- -- - � �- 3 5 - Compression J i i �`� � -" Screw 2 -3/1 i -- 6 - Deflector (5.6 mm) 2 e 7 - Bushing 8- Ejection Sp r in g 1 - / 2 " � 4 (38.1 mm) ' \ ' E SCUTC HEON ILO ' ESCUTCHEON I 5 MOUNTING 11. 4E5 i i� • Temperature ' ' PLATE j rating is .r�e -- -• ., — I �- � ' 6 indicated on Deflector 1 2 - 7/8" OW. I i (73,0 mm) PENDENT RECESSED PENDENT CROSS SECTION FIGURE A 3.0 K- FACTOR MODEL F680 DESIGNER RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS separable two -piece design which al- . ' GENERAL DESCRIPTION lows installation of the sprinklers and APPROVALS AND STANDARDS pressure testing of the fire protection The 3.0 K- factor, Model F680 Designer system, prior to ceiling construction The 3.0 K- factor, Model F680 Designer Residential Pendent and Recessed and/or application of a finish coat to Residential Pendent and Recessed Pendent Sprinklers (Ref. Figure A) are the ceiling. They also permit refinishing Pendent Sprinklers are listed by Un- automatic sprinklers of the frangible of a ceiling surface without having to derwriters Laboratories Inc. and Un- bulb type. They are to be used in first shut down the fire protection sys- derwriters' Laboratories of Canada. tem and remove the sprinklers. The listings only apply to the service • wet pipe residential sprinkler sys- conditions indicated in the General tems for one- and two - family dwell- The adjustment provided by the Re- Technical Data and Residential Design ings and mobile homes per NFPA cessed Escutcheons substantially re- Criteria sections. 130, duces the accuracy to which the length of fixed pipe drops to the sprinklers Any questions concerning an interpre- • wet pipe residential sprinkler sys- must be cut. Also, the Closure has a tation of NFPA 13, 13D, or 13R sprin- terns for residential occupancies up 1/2 inch (12,7mm) wide flange which kler system design /installation stand- ; to and including four stories in provides ample clearance for covering ards, as well as requests for system . height per NFPA 13R, and the mounting hole. design /installation standards not pres- ently covered by NFPA 13, 130, or • wet pipe sprinkler systems for the The F680 Sprinklers have been de- 13R, should be addressed to the: residential portions of any occu- signed to operate with a particular pancy per NFPA 13. temperature rating and heat respon- Secretary, Standards Council sive thermal characteristic, as well as National Fire Protection Association The recessed version of the Model to discharge water in a specific pattern Batterymarch Park F680 Sprinklers is obtained by utilizing and quantity per square foot relation- Quincy, MA 02269 either the 155 °F /68 °C Model F680 In ship. The combination of the perform - combination with the Model F700 Re ance characteristics which are associ- cessed Escutcheon or the 175 °F /79 °C ated with the F680 Sprinklers have WARNINGS F680 with the Model F705 Recessed been proven to help in the control of The Model F680 Designer Resi- Escutcheon (Ref. Figures C -1 and C- residential type fires and, therefore, to dential Pendent and Recessed 2). The F700 Recessed Escutcheon improve the chance for occupants to Pendent Sprinklers described provides up to 3/4 inch (19,1 mm) of escape or be evacuated. herein must be installed and • total adjustment from the flush pen- maintained in compliance with • dent position, and the F705 provides Fire sprinkler systems are not a substi- this document, as well as with the ` t.. i up to 1/2 inch (12,7 mm) of total adjust- tute for intelligent fire safety aware- applicable standards of the Na- ment. ness or construction materials and tional Fire Protection Associa- practices required by building codes. tion, in addition to the standards : The Recessed Escutcheons have a of any other authorities having f jurisdiction. Failure to do so may Printed in U.S A. 6 -98 TD583 , . impair the integrity of these de- Escutch NOMINAL 1< = 3.0 vices. A separately ordered escutcheon plate -- 40 1 , is required for concealed piping instal- v Because of the above cited stipu- lations of the F680 Sprinklers. Refer to z 35 lotions and the varied nature of Technical Data Sheet TD805 for infor- z I ` % : residential type architecture, mation on available escutcheons. . ■1110 111O1111=1°•O= there will be some compartment a 30 � designs which cannot be fully Figure C -1 illustrates the Model F700 v I I I sprinklered in accordance with Recessed Escutcheon which is the cc 25 , the recommendations of NFPA 13, only recessed escutcheon acceptable a 1 ; ; ; 1 J A _____ 13D, or 13R. In the event of this for use with the 155 °F /68 °C F680 condition, consult the authorities Sprinkler, and Figure C -2 illustrates 2 20 Aa_ having jurisdiction for guidance the Model F705 Recessed Escutcheon o and approval which is the only recessed escutcheon Z is O ��0�. acceptable for use with the �� It is the responsibility of an in- 175 °F /79 °C F680 Sprinkler. Both the it ' stalling contractor to provide a F700 and F705 have a Closure and 10 � ; , ; I 1 ' I ; copy of this document to the Mounting Plate fabricated from low a I I ' owner or his representative and, carbon steel. The Mounting Plate 5 10 15 20 in turn, it is the obligation of the prongs, which are compressed back 5 owner to provide a copy of this into the Mounting Plate as the Closure DISCHARGE IN U.S. GALLONS PER MINUTE document to a succeeding owner. is pushed over it, maintain a tight fric- (GPM) tion fit between the two pieces. The The owner is responsible for Mounting Plate and Closure can also NOMINAL 1< = 43.2 maintaining their fire protection swivel relative to each other and corn- 3.0 • system and devices in proper op- pensate for minor non - perpendicular- _� , 1 1 .. i . 1 , I I I i 1 I erating condition. The installing ity between the Model F680 Sprinkler i I ii 1: . : I • i II contractor or sprinkler manufac- and the ceiling. , 1 ' I 1 1 , + , , turer should be contacted relative 2 I I : . , , ' 1 ' T he F700 and F705 Escutcheons are ' ' ■ ' • 11 ' . . I .. I I to any questions. 1 . 1 1 1 . 1 1 k available with chrome plated finish or g I I • , 1 ; l l + ' I 2.0 a coated finish in any color. , 1 = 1,, 1 I , I, • 1 11 ti I 1 1I 11' II I II•I x' CL GENERAL TECHNICAL DATA NOTES W Absence of an escutcheon may de- 0 , ; , 7, 1 I , Sprinkler Assemblies: lay the time to sprinkler opera- o I,5 i ; i L i ; ; , i • ; The 3.0 K- factor, Model F680 Designer tion in a fire situation. a I , ' f I ,1 1 • I • 11 • ` Residential Pendent Sprinklers are I ' I 1 I f' ' ' I I ' I • ' ' ' I 1 • available in either a 155°F/68°C or Only use escutcheons which con- i . o I ' 1 . , , , I 1 , I 1 1 175 °F /79 °C temperature rating, and sist of metallic materials that 1 i • I ' I ' { ' ' ' ' ' ' they are rated for use at a maximum will not deform or dislod a at a 1 ' ; ; I t. ' ' ' 1 1 7 I 11 f g I i,•1 1171 III I_ service pressure of 175 psi. They are temperature of less than ' ' - ' ' 1 ' ' 1 ' ' ' ' available chrome plated, natural brass, 1200 °F /6.19 °C and /or which have 0 ' S 30 40 50 60 70 80 or polyester coated In any color. been listed by Underwriters Lobo- DISCHARGE IN ratories Inc. for fire protection LITRES ° ER MINUTE The nominal discharge curves for the service. F680 are plotted in Figure B and rep- FIGURE B resent the flow "0" as determined by The Escutcheons shown in TD805, NOMINAL DISCHARGE CURVES the formula Figure C -1, or Figure C -2 cannot be used to hold the F680 in posi- 0 = K psr tion. The F680 must be secured in where the nominal sprinkler discharge position by firmly fastening the tent and completely familiar coefficient is "K", and "p" equals resid- sprinkler system piping to the with automatic sprinkler sys- ual pressure. "K" equals 3.0 for flow in dwelling structure. If the F680 is tern design, installation pro - U.S. gallons per minute (GPM) and not properly secured in position, cedures, and techniques. residual pressure in pounds per reaction forces resulting from square inch. "K" equals 43,2 for flow in sprinkler operation could alter 2. Several criteria may apply to litres per minute and residual pressure its orientation and water distri- the installation and usage of In bar. bution pattern. each sprinkler. Consequently, it is recommended that the The F680 utilizes a bronze Frame per sprinkler system designer re- ASTM B176 (087800). The Button view and develop a working un- (bulb retainer) is phospher bronze per RESIDENTIAL DESIGN CRITERIA derstanding of the complete ASTM 8103 (C51000, 052000, or – of criteria, prior to initiat- he 3.0 K- factor, Model F680 Designer the sprinkler 054400), and the Bushing is brass per Residential Pendent and Recessed ing the design of ASTM B152 (032200). The Gasketed system. Pendent Sprinklers must only be in Spring Plate consists of a berylium stalled and utilized in accordance with nickel disc spring that is sealed on both 3. Questions concerning sprink- its inside and outside edges with a the following described criteria which ler installation and usage cri- are provided by the manufacturer. teria, which are not covered by Teflont gasket. The Ejection Spring is g stainless steel, the Compression the following instructions, . Screw is C51000 , NOTES phosphor bronze ) should be mailed to the atten- P p ( I. Residential Fire Sprinkler and the Deflector is brass per ASTM terns should only be designed tion of the Technical Data De- B36 (022000). and installed by those compe- partment. Include sketches —2— t DuPont Registered Trademark H j . FULLY RECESSED DIMENSIONSt 2 -1/4' (57,2 mm) 0IA. C115 Up to 1/2 inch adjustment from minimum 1/4 inch to maximum FACE OF SPRINKLER 3/4 inch recessed position. FITTING Dim. Inches MM •` � r A- 5 /8t1 /8tt 15,9±3.2 ' �•J B -Min. 3/4 19,1 A B -Nom. 1 25,4 - lii i. B -Max. 1/1/4 31.8 C 6 C Min. 1/4 6,4 III • C -Max. 3/4 19,1 4 / -I MOUN TING 8 1/8' 2b 2a 1 SU RFACE HIGH ADJUSTMENT 1 (3,2 mm) DIMENSIONS r Up to 3/4 inch adjustment from the - 2 -7/8' (73.0 mm) OM. . flush ceiling position to 3/4 inch recessed position- ` Dim. Inches MM t For best overall appearance. A- 1/2_ +1 /4tt 12,7x-6.4 B -Min. 3/4 19,1 ttRemaining 1/4 inch (6,4mm) of adjust- 1- Model F680 Pendent Spnnkler ment can be used to compensate for 2- Model F700 Recessed Escutcheon 8 -Nom. 1 -1/8 28.6 a- Mounting Plate B -Max. 1 -1/2 38.1 variations in sprinkler make -In and fitting b- Closure C -Min. FLUSH — take -out. C -Max. 3/4 19.1 FIGURE C - 155 °F /68 °C MODEL F680 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE MODEL F700 RECESSED ESCUTCHEON 0 , FULLY RECESSED DIMENSIONSt 2-1/4" (57,2 mm) DIA. Up to 1/4 inch adjustment from minimum 1/4 inch to maximum FACE OF 1/2 inch recessed position. SPRINKLER FITTING Dim. Inches MM A- 1 /21t 12.7 ;` r B -Min. 1 25,4 � tor A B -Nom. 1-1/8 28.6 ,�I�r - -- �� B - Max. 1 -1/4 31,8 C C Min. 1/4 6,4 \� ` / } C - Max. 1/2 12.7 I MOUNTING t /8' 2D 2a t SURFACE 8 (3.2 mm) HIGH ADJUSTMENT fir DIMENSIONS f Up to 1/2 inch adjustment from the flush ceiling position to f~ 2 -7/8 (73,0 mm) DIA. 1/2 inch recessed position. Dim. Inches MM y A- 3/8 +1 /8tt 9,5±3.2 t For best overall appearance. B - Min. 1 25,4 1 Model F680 Pendent Spnnkler B -Nom. 1 -1/4 31,8 ttRemaining 1/4 inch (6,4mm) of adjust- 2- Model F705 Recessed Escutcheon I B -Max. 1 -1/2 38,1 ment can be used to compensate for a- Mounting Plate ■ Cs C -Min. FLUSH — variations in sprinkler make -In and fitting b- Closure C - Max. 1/2 12,7 take -out. FIGURE C -2 175 °F /79 °C MODEL F680 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE MODEL F705 RECESSED ESCUTCHEON —3— it MINIMUM FLOW (D) • 155°F AND S2 MAX Sa MAx. , 5r2 MAX RESIDUAL PRESSURE "' ' 01CM�r 4 INCHES MW. MW. I PAIN MAXIMUM — 1"-- "'- COVERAGE ONE MULTIPLE ;° ':NCMES • AREA (a) SPRINKLER SPRINKLERS PAIN PAIN FT. xFT. FLOWING FLOWING • J. y • 12 x 12 9 GPM 8 GPM � (TyP) • (9.0 PSI) (7.1 PSI) 1 14 x 14 10 GPM 8 GPM (11.1 PSI) (7.1 PSI) Figure 0 - 1 (Plan View) Figure E - 2 (Plan View) 16x16 10 GPM 8GPM — (11.1 PSI) (7.1 PSI) Sr2 MAX. 111 MAX. Sa MAX s MAX ` SAX / 2 M 18 x 18 13 GPM 10.5 GPM 4 4 INCHES (4 INCHES i INCH a F EET MIN. 4 INCHES (18.8 PSI) (12.3 PSI) MIN. I MIN MIN (SEE NOTE) MIN. 20x20 14 GPM 13.5 GPM (21.8 PSI) (20.3 PSI) • INCHES 1 4 1N H 5 PAIN MIN • • • MINIMUM FLOW (b) 175 °F AND �Me x e WAIN PRESSURE a BEET MIN (SEE NOTE) (SEE NOTE) MAXIMUM COVERAGE ONE MULTIPLE • _ • • I AREA (a) SPRINKLER SPRINKLERS X i FT. x FT. FLOWING FLOWING 4IN CHES MCNES PAIN 12 x 12 9 GPM 9 GPM —_L._ — (9.0 PSI) (9.0 PSI) Figure 0 (Plan View) Figure D (Plan View) 14 x 14 11 GPM 9 GPM - 1 (13.4 PSI) (9.0 PSI) Sa MA X 15/2 MAX S/2 MAX 1 16 x 16 11 GPM 9GPM 4 INCHES 14 INCHES (13.4 PSI) (9.0 PSI) PAIN I PAIN 18x18 13 GPM 10.5 GPM h r � (18.8 PSI) (12.3 PSI) / \ 4 GH I L S/2 MAX t. MIN 4 20 x 20 14 GPM 13.5 GPM Sr2 MAX 1 0 FEET 4 INCHES MIN. r (21 8 PSI) (20.3 PSI) MIN ( 4INCHES / SI2 MAX MIN 1`( 10 FEET 4INCHES 4 INCHES MIN MIN. PAIN, J (a) For coverage area dimensions less than J S MAX or between those indicated, it is I a FEET MIN, necessary to use the minimum i— st 2 MAX (SEE NOTE) required flow for the next h i g hest -- I 4INCHES Figure D - 6 (Plan View) coverage area for which hydraulic design criteria are stated. S/2 MAX I S MAX. 1 S/2 MAX 14 INCHES 8 FEET MINIMUM 4 INCHES MIN. 4INCHES MIN (b) Requirement is based on minimum flow . (SEE NOTE) MIN in GPM from each sprinkler. The Figure 0 - (Plan View) • --- associated residual pressures are I calculated using the nominal K-factor I ►,� MIN. Refer to Hydraulic Design Criteria , ,--1- Section for details. 4-S/2 MAX ---• TABLE A s/2 MAX - I -- 4 INCHES PAIN HYDRAULIC DESIGN CRITERIA 4INCHES PAIN Sa MAX - , 4 INCHES ' PAIN S/2 = ONE-HALF THE LENGTH OF THE COVERAGE AREA BEING 5/2 MAX Figure D - 7 (Plan View) HYDRAULICALLY CALCULATED (REF. TABLE A). ID FEET MIN. / _ S = THE LENGTH OF THE COVERAGE l Sa MAX r t- GRAPH A GRAPH A AREA BEING HYDRAULICALLY 1111 • INCHES CALCULATED (REF TABLE A). MIN I OBSTRUCTION NOTE: The 8 foot minimum spacing shown Figure D - (Plan View) in Figures D -3 through D -6 applies to Figure D - (Elevation View) - adjacent sprinklers installed with their frame arms either in line or parallel with each other: otherwise, 10 feet is FIGURE D the minimum required spacing. SPACING RULES UNDER LEVEL CEILINGS —4— ( / M� MA .4. /� S ''o0-4-/-4,e, 1 4 , T B F s,� 0 41 A T 4 f 3 FEET MAX. o ffe r t i rJ ` �,, /A 10 FEET MINIMUM FOR GAs31 Figure E -1 (Elevation View) Figure 11 -2 (Elevation View) I j.-- s2 MAX. sM AX I \ SEE GRAPH 8- —# I ,� / 4 SF F C q � 44. yy 1 Io F 10 FEET FOp �1:4:13(44 J FOR A s �Vy 1 � Figure E -3 (Elevation View) ' Figure E-4 (Elevation View) ^ MAXIMUM t 1 b° . 'E `O M'4 `0 JAM, + A*CP I kr 4 F� 1 0 FEET MIM & ` F u".„4..„,‘„,,,,,._ , SEE SEE GRAPH 0 GRAPH 0 Figure E -5 (Elevation View) Figure E-6 (Elevation View) 0 3 FEET MAX 3 FEET / 40PAI I FOOT MIN. MAXIMUM Q�C.\ s o. G ap S • `pF �0 B SR MAX --4. 4:1 SEE ".� 1 FoR 1. A Bouts A GRAPH E Figure E -7 (Elevation View) Figure F-8 (Elevation View) • 3 FEET MAX M/4 I SpM % 1401 \ 0,949E$. OBSTRUCTION _+ Ma SR MAX. ar 4 INCHES MIN Figure E -9 (Elevation View) Figure E -10 (Elevation View) S/2 = ONE-HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A). S = THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A). NOTES: 1. Figures E -1 through E•9 only apply when: (a) the ceiling ridge is honzontal; (b) the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler; (c) any adjacent spnnklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge. and the sprinklers are to be spaced a minimum of 8 feet apart; 0 (d) the sprinklers are installed with their frame arms perpendicular to the ceiling ridge: and. (e) the spnnklers shown in Figures E -1 through E -8 are located in a plane which is perpendicular to the ceiling ridge. and the ceiling angles are within the specified range. 2. Contact the Technical Data Department for questions concerning installations outside the scope of Figures E -1 through E -10. FIGURE E, SPACING RULES UNDER PITCHED CEILINGS AND /OR OVERHANGS —5- ' 1P 0 --i& = 6 - 4� _ - ' . 0 0' 2 . 6. 9, 6 ; 0' 0' ;. c 6 4 . 2' U C 2• \� x . ' iRR:' \ 2' �. 1 • e U e � IlialaUSiiiiiNa 2' ° ■■■■uM■Mu■ 4 ■ M . M t .�'� \tee` U ■ � .M •1l V�IM�� ■■ 4 1 1 1 1 I i ,y. ���\ i�1\ \ � 8 �� 4 . 6' •I /uiUuU . 6' ®' I I I I I I 1 6 . 111111111111.E. 6, 6. 8' 6' 6' IIII441m11111110TOT e' e' 8 ' 12' X 12' Coverage Area 9 GPM 8 GPM • 16' X 16' Coverage Area 10 GPM 20' X 20' Coverage Area 8 GPM 14 GPM 13.5 GPM FIGURE F NOMINAL WETTING PATTERNS AT MINIMUM REQUIRED FLOW CONDITIONS FOR SELECTED COVERAGE AREAS • 27 O ._•_ • • -- •�. -s ••• -sd •-E/ • r•— =�iri• . IBM - •u •u ... LI, .................... c ,§ 5 %IC 6 -,9 It a antA" e : <:,.. A 4 ,-9 • .......— pZ 18 - - - --0 (le_ 4' - Q• • Q — • W o • C7 io Q � . 11 Q. _ -- ' W --- - - -a•— O • d h • w - ry 41 , .. N. 3 i- -- - T. . ■ ............. a - - --- � .• . Cn _ • ._— �••• • •• i ._ -••• -- �N 12 •d • Er ` 20 • s omma••..— w — •_•__.•r _ ••r .— .• G -- •. - - -...•� ._o ■•• AMY .••• -_• - -- .., i w OW ABM OMR Ma •=1/ ADS ".••1•1•111••11•1•■• •111•1=11• IBM MEE - . A 6 •�� -- - .••sr --==== -- ---- r•- U.••••• . _••••- -I _ -1 _I IN •1•11•11•11•••••• 1_s AIM _ a_ 0 - - -- 111•1•1111111 '•• ••• - - -- M F V 0 1 2 3 4 5 6 7 8 9. 10 PLUS (MAX.) DISTANCE TO OBSTRUCTION 'H' OR Z. FEET NOTES: 1. CEILING OBSTRUCTIONS MUST BE SPACED ON THE BASIS OF USING THE MAXIMUM RESIDUAL PRESSURE WHICH WOULD BE PRESENT FOR A SINGLE SPRINKLER OPERATION. 2. BEAMS AND /OR OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH 'V' OF MORE THAN 3 INCHES WITHIN THE SPRINKLER COVERAGE AREA. GRAPH A .. MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER MOUNTING SURFACE AND THE BOTTOM OF CEILING MOUNTED OBSTRUCTIONS SUCH AS BEAMS, OVERHANGS, AND LIGHT FIXTURES WITHOUT UNDULY OBSTRUCTING THE WATER SPRAY DISTRIBUTION —6— ■ W W LL . 3 .MM owe .E.. . •EEM .MM •s sM EM EE el) p= M-E ems E.. MM M. E mums IMM. MIME W EM M. W. ■.ME.MM Y...M. WEE O MIME WEENY .M....... • Erne EEE CL W M • MM ■:E.m M 5. EEC MEW ' 2 E ME \1. .- i M MEMO NEENE= E EWE EV.- .EO ...M .E... Q a MEW • u.E.EEM EEEE. :•M s_. ...M..... . WH ■ EE.O..E.. .EM. EMIRS UMW ■MU EM EO.-E!-EEEM .W. .EEM..EE. Q to ■EEM •• -.M .EE.EEE. ..EEO ■EEM . MEE• • E c �•. arm. ...M . En ip 1 ■W..EE.. E.mE.MM Ems. ammo EEEM ■MM . ' J ■n.. • EM.E • ■EEM ■EEM• 1• ME. .m= MIRES s_ ME• •••••• W M E OE 1EE EMEND . E. GEESE ■EEM EEEE•1.EM■ Emu. MEE. ?0' • •.••• ... i iw ii5.a EE. MM iEs_. REESE EMMii 20 0 0 5 10 15 20 25 30 35 40 45 50 55 60 0 CEIUNG ANGLE 'A'. DEGREES M (MIN.) NOTE: SPRINKLERS MUST BE INSTALLED WITH THEIR FRAME ARMS PERPENDICULAR TO THE CEILING RIDGE. GRAPH B MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LOCATED ON A LEVEL CEILING AND AN INTERSECTING PITCHED CEILING WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION 0 - ` 3 FEET MAXIMUM WHEN THERE ARE NO SPRINKLERS ON COVERAGE AREAS. ■ THE LEVEL CEILING Y (a) 20' x 20' (c) 16' x 16' ... (MIN.) ... (b) 18'x18' (d) 14' x 14' & 12' x 12' T 6 t• E_ _ MEM.t..EE/E wE. ■sME MEW EEEM Ears -- sums Imo emu ram mom um sass mum mom wpm —E MEEE maws emir. IIIIIIII••• MIME INMEEU WWWWW1 MENU EWE= REM . u. . _N EO Mr W AE ME uo a_ 5 . _ _ u MEMO _ 3L '�i•!We rigna w EE_mMO ..EEO EEESE E/.. dM ME" - - - 0l. . ME.E 0 MEMO MIMEO MUM MUM EMCEE l. s_c, rE MEMO MME.EaES =MIRE WLL EM u o mime MEMO EP J EEP- MM•• �.M�M• WINE MOO Q • • 4 EEEM eEEM uEm. MIME Em EEE► } EEEU EPEE EWEEEEm• .EEM c, MEm EME. EEME EME -EOOEE MEd EEC •• E_KEW EEEa • AMEN EEMO MEMO EEW WEE . E .. emu . EMM EENNE MERE BMW • MEE/. . WU WEENIE 11•111711 MIME NEW Al• IEEE .41 EEEE- EWE I-O• MME WEM.MEEMIMES IZQ 3 EEEM �� OW/ AM �� �•..EmU.E E MEOIE .E.. e�I1 .EomE nto ERE MEW EM EMM UU .M .E M .0 MERE . . MEEE WV . MM.NEEE- 2 p uOE WEE MEP Y MM ...EESE EWE OO E U/.OMEMO SEEMS SEMEN SEEE E. /ME M.E E •• EEO MS W M .EE E� NEW EEE V E.EEE. WOW 21- 2 M ES EEE uEUEE••■••EEM. All•EMEE MEW WEEEO EEME•. MEMO EEM.E EMM MEW MEMO MIME MEV ./ e- -EEEEE EUE. WOMB EMI. MEE..EOEE OM• WEEP Q u_ IMF p /EE.. .M-O .mm • EEM. /.AE WEE • ■a._a _� E MEE Cr) 1 Ew /a A i .a_ � is m m eMEME /r SEISM "7...M MEW .c - _ —S. EEW EM.• ••1 -=! UMW ummE WEE EWE EEi =.E-M MM.mMO EWE SEEM EE--MEOu� EUM EWE MEM EEC W E� EEE� uMm dM EWE.EEIE EEEEE ■ EEE . OWE O O •� MEP PM MME MEM.MEE NOW M1• E_O !MEW MEMO 0 5 10 15 20 25 30 35 40 45 50 55 60 f. CEILING ANGLE'A', DEGREES NOTE: SPRINKLERS MUST BE INSTALLED WITH THEIR FRAME ARMS PERPENDICULAR TO THE CEILING RIDGE. 4.1-1) GRAPH C MINIMUM REQUIRED SLANT DISTANCE BETWEEN A LEVEL CEILING AND A SPRINKLER LOCATED ON A PITCHED CEILING WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION —7— 4" TO 6" (SEE NOTE 2) ■■ � ann Si ..411b. ` MOUNTING SURFACE MUM _.No. .m.ao.. - - - - au ►•�...aa - 9 .Ya allo. . 0 H ••• ua■km.aa ... w sun .n man aa■.m■■ nn■ w ....n .a . • Minn .an■ U. m. IMO. y f G- 8 ..Y YY own / 4 4 w? ■.0 u ia� ∎. o .oaum.am. ill IMAM. -T I A -••• ■■■■■a■■avow ■amNomu.o ...aaon . mn..a. non w mom Nom Mann Ili m .mu. 0 .- .nnn noon maim ua. •.as um .am m m N (MAX.) N (MAX.) Q ZZA 7 IN No .a.......IN..'No.a ■■ Mann MOIRE •m ill 1151111111111 Nom ma a� 0 Enna■■■■■linenamaaINo.am.aallomnun■ma (SEE NOTE I) (SEE NOTE 1 ) Z .... um ■a■■inillinn■Me. Inn ■ ■m ■111111•NI 111•11=■m■ ■ Man ■■ - ME nil ® •.am ROOM! Eli m. ��w ..uuan.aaa.a- n..:"Nom NOTES: mJw 6 ..0 mom nnmmow nano .•mallom sawn anon m ■■ ■■■■■ Nom=Id= um .a llom m . u m aa aannm m. a■ . n .. a ... . 1. UP TO A MAXIMUM OF ONE-HALF THE LENGTH > c ••u mw Nom •••■ A. ma MIN=■m■ .m. a 0 ■.0 ■■ EN E N . s•■ ■m Non ��•su u m m THE COVERAGE AREA BEING HYDRAULICALLY HIV 5 . a . um . .mamam ill•1 aa■allo CACULATED. ma..a■ in Noa Q a..Y woo avan Nom ill Nairn _ = ®■a�■� ■m■■■ ■■■■ 2. THE MOUNTING SURFACE MUST BE LOCATED m s • .�.No.r. .. •.s.. 4 ..No Mann m No■m m nn::: in WITHIN 4 TO 6 INCHES OF THE PEAK, IF IT IS NOT ■ .u . aaYmao■sn.mNom- �Noamu ..•••••••••••• •• E .■.u.um.aaa..m.� �`'-■l ■uY::: CONTINUOUS OVER THE FULL LENGTH OF THE ■■ in! Min= Winn MONO ninlin■inall . CEILING RIDGE. 3 Ulm .mm Swan. .aY 10 15 20 25 30 35 40 45 50 55 60 3. SPRINKLERS MUST BE INSTALLED WITH THEIR FRAME ARMS PERPENDICULAR TO THE CEILING CEILING ANGLE 'A'. DEGREES RIDGE. GRAPH D MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED AT A PEAK I- t0 ; . ISFf4t w T F2/ w ' w . .. , . . • a- 9 ' _ � UNACCEPTABLE _ , _. - - - - _ _ U= , alp 8 ' ' - T , Mp J (MAX.) � 7 I (SEE NOTE I) ) a z `" ACCEPTABLE 3TE t.,..., 2 � 6 ' L UP TO A MAXIMUM OF ONE -HALF THE LENGTH OF THE I., . 0 r COVERAGE AREA BEING HYDRAULLICALLY = 5 CALCULATED. - - 0 5 10 15 20 25 30 35 40 45 3 FEET IS THE MAXIMUM PERMITTED AND 1 FOOT IS THE CEILING ANGLE. DEGREES MINIMUM REQUIRED. (USE THE GREATER OF ANGLE 'A' OR ANGLE B') SPRINKLERS MUST BE INSTALLED WITH THEIR FRAME ARMS PERPENDICULAR TO THE CEILING RIDGE. GRAPH E MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED ON A PITCHED CEILING OPPOSITE FROM AN INTERSECTING PITCHED CEILING 5 ammo mum Nom■amam-........ JVERAGE AREAS: .p w uNo.u a u °a i�u�m� a.i�.mOm...ai° 20' x 20' rM /� / cU ■.au i u i u m u m v a m � ia y..�� ) W 4 .m. um um war .�..aa.•raw.m ) 18' x 18' cc Nom Nom Noes _...n Noas• ..� - u... ..a. UMW MAIM ...r. m/ u• I • . a ■ ■ Manna Mir .a Mann ear ..Noua■■rAO ) 16' x 16' • u.. Nom ua.•.nos•NoMI �a Q Z 3 Snails u, • nil Ua° . .....Amor ' o � ) 1 a' x t a' ■ Q m ■ ■■v.■...a .w.m �I- Noum ) 12' x 12' )'A I •' A =ln u■■.• w AIM &WO WWisu.•.oa MP T I 1 mp ..m�.aa.u.ar S/2 MAXIMUM _ Z)- 2 MIA. •um.s■V•No.v Anna • /NM WAN ur.■ .■a■OW .■■a"•OW/ (SEE NOTE I ) < orA OTES: J y• u■ • 1 °■■ °' °° ' ■sow aw` UP TO A MAXIMUM OF ONE -HALF THE LENGTH OF THE COVERAGE 10 15 20 25 30 35 40 45 AREA BEING HYDRAULICALLY CACULATED. CEILING ANGLE 'A', DEGREES SPRINKLERS MUST BE INSTALLED WITH THEIR FRAME ARMS PERPENDICULAR TO THE CEILING RIDGE. i GRAPH F MINIMUM REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION —8— and technical details, as ap- kept as few as possible. Do NOT F680 heat responsive element (Bulb), propriate. use more sprinklers than neces- due to exposure to heat sources other sary to cover a particular space. than abnormal fire. 4. In some instances, the require - ments of this document may Spray Coverage Criteria. Figures 0 concern specifications which and E provide spacing rules that must are more stringent and which be followed to assure that the F680 take precedence over those Sprinklers will provide their design dis- INSTALLATION specified in NFPA 13, NFPA tribution of water spray. Nominal wet- NOTES 13D, NFPA 13R, or by the ling patterns for the F680 Sprinklers at authority having jurisdiction. minimum required flow conditions Residential Fire Sprinkler Sys - (Ref. Table A), are illustrated in Figure terns should only be designed and 5. The spray from the F680 is dis - F, for selected coverage areas. installed by those competent and tributed radially outward and completely familiar with auto- downward from the sprinkler Operational Sensitivity Criteria. For matic sprinkler system design, in- • deflector. Consequently, the proper operational sensitivity, the stallation procedures, and tech - F680 Sprinklers must be installed be- niques.' sprinklers must be located spaces Heath solid r ace The e de a smooth or such that there will not be any shielded from textured surface. The deflector -to -cell- The Technical Data Department blind P f' ing distance is to be 1 -1/2 to 4 inches, should be contacted relative to spray by partitions, room di- unless the F700 or F705 Recessed any questions. viders, overhangs or other Escutcheon is being utilized per Figure parts of the dwelling structure. C -1 or C -2, as applicable. Do not install any bulb type sprin- kler if the bulb is cracked or there General Service Conditions. The The F680 Sprinklers must NOT be is a loss of liquid from the bulb. F680 Sprinklers must only be utilized used above or below open - gridded With the sprinkler held horizon - in wet pipe sprinkler systems with all type suspended ceilings; beneath sof- tal, a small air bubble with an interconnecting system piping as well fits or beams resulting in a deflector- approximate diameter of 1/16 as the sprinklers maintained at a mini- to- ceiling distance (i.e., deflector -to- inch should be be present. mum temperature of 40 °F /4 °C, and mounting surface plus depth of soffit or with water supplies which are substan- beam) exceeding 4 inches; or, with The Model F680 Designer Residential tially free of contaminants and parti- beams, joists, or ducts having a height Sprinklers must be installed in accord - cles of a size greater than 1/8 inch (3,2 of more than 3 inches located within ance with the following instructions: mm). the sprinkler coverage areas. 1. The Sprinkler must only be installed Thermal Responsive Criteria. All NOTE in the pendent position and with the residential sprinklers installed within a Beams having a height of more Deflector parallel to the mounting 0 compartment (as defined by the NFPA) than 3 inches may be located with surface. must have the same heat response their centerlines along the bound - thermal characteristic, and their tern- cries separating adjacent sprin- 2. Pnor to installing each Sprinker, ver- perature ratings are to be within 10 °F kler coverage areas. ify that the outer face of the mating of each other. fitting is within the proper range of It is recommended that as part of the distance of the mounting surface, NOTES sprinkler system design, the designer which can be accommodated by the In accordance with the require- review the dwelling plans and, where particular type of escutcheon plate ments of NFPA 13, 13D, and I3R, appropriate. advise the owner or his being used. all sprinklers within a compart- representative as to the following. mented area must be of the lowest When installing a Model F680 Pen - required temperature classifica- I. Lintels of at least 3 inches in height dent Sprinkler with either the F700 tion as a function of the maximum and preferably 8 inches should be or F705 Recessed Escutcheon, for expected (non -fire) sprinkler tem- used over all passageways from one best overall appearance. use Di- perature. space to another, in order to reduce mension "A" indicated under the • the possibility of sprinkler operations "Fully Recessed Dimensions" head - Do Not use sprinklers with a tem- outside of the fire area. ing of Figure C -1 or C -2, as applica- perature rating higher than nec- ble. Otherwise, use Dimension "A" essary to cover a particular area. II. Beams of at least 3 inches in height under the "High Adjustment Dimen- Hydraulic Design Criteria. The mini- should be used to border each of 5 sions" heading. In either case, the H Y 9 or more adjoining areas of F680 remaining adjustment can be used mum required single and multiple Spnnkler coverage (within the same to compensate for the possible sprinkler flow rates are given in Table compartment), in order to decrease manufacturing variations in take -out A as a function of temperature rating the time to first sprinkler operation as of the fittting, as well as in the make- • and the maximum allowable coverage well as to reduce the possibility of in of the sprinklers (as permitted by areas. The single sprinkler flow rate is multiple sprinkler operations. ANSI B1.20.1). the minimum required discharge from i the most hydraulically demanding sin- Cold Soldering Criteria. Figures 0 3. Install the F700 or F705 Mounting gle sprinkler and, the multiple sprinkler and E provide the minimum spacing Plate (or other escutcheon, as appli- flow rate is the minimum required dis- requirements necessary for preventing cable) over the sprinkler threads. . charge from each of the total number the wetting (i.e., cold soldering) of the of "design sprinklers" (as specified in heat responsive element (Bulb) of a 4. With pipe thread sealant applied to , , . 1 NFPA 13, 13D, or 13R). non - operated F680 Sprinkler, which is the pipe threads. hand tighten the I NOTE adjacent to one which has operated. sprinkler into the sprinkler fitting. The number of sprinklers within Heat Source Criteria. Refer to NFPA 5. Refer to Figure G and select the each compartment (as defined by 13D for the requirements relating to appropriate Sprinkler Wrench for NFPA 13, 13D, or 13R), must be preventing the possible release of an —9— I SELECTION: . Escutcheon Plate by under- or Select the appropriate wrench over - tightening the Sprinkler. based on the following require- Readjust the position of the ments: sprinkler fitting to suit A. Model F680 Sprinklers with a l -- pr 1 40•1111C) 6. I n recessed pendent sprinkler instal- "..\ natural brass or chrome plated i I �I� I i lations, after the ceiling has been finish and where the Wrench L. installed s talled or the finish coat has been Flats shown in Figure A are ac- pplied, slide on the F700 or F705 cessible, may be be installed 1 �� Closure, as applicable, over the using an 8 or 10 inch adjustable _ Model F680 Spnnkler and push the Crescent type wrench or the © i Closure over the Mounting Plate un- Model F850 Sprinkler Wrench. ri til its flange comes in contact with the ceiling. B. Model F680 Sprinklers with a � - - - 1 - -- i 1 polyester coated finish must �____: only be installed with the Model , e• F850 Sprinkler Wrench. CARE AND MAINTENANCE WRENCH LUGS C. Model F680 Recessed Pen- The F680 Sprinklers must never be dent Spnnklers which are to be Model F850 Nylon Coated shipped or stored where their tempera - installed after completion of a S rinkler Wrench lure will exceed 100 °F /38 °C and they fixed ceiling must only be in- p must never be painted, plated, coated, stalled with the Model F850 or otherwise altered after leaving the Sprinkler Wrench. factory. Modified sprinklers must be re- placed. Sprinklers that have been ex- posed to corrosive products of corn - USE: bustion, but have not operated, should When using an 8 or 10 inch adjustable Crescent type wrench, the wrench is to be be completely cleaned by wiping the applied to the sprinkler wrench flats only (Ref. Figure A). sprinkler with a cloth or by brushing it with a soft bristle brush. To use the F850 Sprinkler Wrench, slip the Wrench opening over the Model F680 Sprinkler Deflector by passing the Sprinkler Wrench around the side of the NOTE Sprinkler as shown in the above illustration. particular care to prevent over- heating must be exercised when Using a 1/2 inch ratchet drive or by applying an 8 or 10 inch adjustable wrench to storing sprinklers in cars, trucks, the hex end of the Sprinkler Wrench, tighten the sprinkler into the fitting. The two trains, or other vehicles on warm, lugs located on opposite sides of the Wrench indicate the orientation of the blight sunny days. sprinkler frame arms. i Care must be exercised to avoid dam - NOTE age to the F680 Sprinklers - both be- Push up on the Sprinkler Wrench, while it is being turned, to ensure fore and after installation. Sprinklers that the Wrench recess stays fully engaged with the sprinkler wrench damaged by dropping, striking, flats. wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- Carefully remove the Sprinkler Wrench by disengaging it from the sprinkler wrench kler that has a cracked bulb or that has flats, and then passing it sideways over the sprinkler deflector. lost liquid from its bulb (Ref. Installa- tion Section). FIGURE G SPRINKLER WRENCH SELECTION AND USE NOTES Absence of an Escutcheon Plate may delay the time to sprinkler operation in a fire situation. tightening the Sprinkler into the compartments in which the sprinkler fitting. sprinklers are only located on a Before closing a fire protection level ceiling must be installed system main control valve for The F850 Sprinkler Wrench must be with their frame arms parallel maintenance work on the fire pro- used for installling polyester coated to a straight compartment wall. tection system which it controls, spnnklers, in order to prevent dam- permission to shut down the af- age to the sprinkler finish. All sprinklers installed within fected fire protection systems compartments having a pitched must be obtained from the proper ceiling with one or two parallel authorities and all personnel who NOTES horizontal ceiling ridges must may be affected by this action A leak tight 112 inch NPT sprin- be installed with their frame must be notified. kler joint should be obtained arms perpendicular to the ceil- with a torque of 7 to 14f.lbs. (9,5 ing ridges. It is recommended that automatic to 19,0 Nm). A maximum of 21 sprinkler systems be inspected Jt.lbs.(28,5 Nm) of torque istobe Failure to properly orientate the and maintained in accordance used to install sprinklers. sprinkler frame arms may re- with the advice and suggestions Higher levels of torque may dis- suit in impaired fire protection given in NFPA 13, 13A, 13D, and tort the sprinkler inlet with con- due to cold soldering and/or in- 13R, as applicable. Sequent leakage or impairment adequate spray coverage. of the sprinkler. It is recommended that automatic Do not attempt to make -up for sprinkler systems be inspected guar- All sprinklers installed within insufficient adjustment in an terly by a qualified Inspection Service. —10— t DuPont Registered Trademark • LIMITED WARRANTY REMODELING The manufacturer warrants for a period of one year from the date of sale • (warranty period) that the product(s) sold hereunder are free from defects When remodeling, such as by adding in material and workmanship. Our obligation under this warranty is limited false beams or light fixtures or chang- to repair or replacement, or, at our option, we will repay the price paid for ing the location of compartment walls, the product(s), plus any transportation charge paid by the purchaser. In first verify that the new construction • the case of replacement, we will pay the transportation charges to the will not violate the installation require - location of the defective product. We must be given the opportunity to ments stated under WARNINGS. Alter inspect any product you believe to be defective. To make a claim under the new construction and/or the sprin- this limited warranty, you should contact our Sales Services Manager at kler system to suit the requirements of (401) 781 -9032. this document. THERE ARE NO OTHER WRITTEN OR ORAL WARRANTIES. ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR 1 A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO THE DU- ORDERING PROCEDURE RATION OF THE LIMITED WARRANTY SET FORTH ABOVE. • i A Product Symbol Number (PSN) is • The manufacturer does not assume any other obligation in connection not specified when ordering polyester with the sale of the product(s) by purchaser. coated Model F680 Sprinklers with other than a white color or when order - This warranty shall not apply to any product(s) which have been installed ing color coated Recessed Escutch- in violation of written instructions furnished by the manufacturer, repaired eons with other than a white color. It is or altered, misused or damaged, or not properly maintained. suggested that a color chip be pro- vided when ordering special color fin - 1 The manufacturer is not liable for indirect, incidental or consequential ishes. Otherwise, responsibility for du- i damages in connection with the use of the product(s). plication cannot be accepted. Some states do not allow limitations on how long an implied warranty Contact your local distributor for avail - lasts, or exclusion or limitation of incidental or consequential damages, ability. so the above limitations or exclusion may not apply to you. Sprinkler Assembly: THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU Specify: (specify 155 °F or 175 °F) MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO Model F680 Designer Residential Pen . STATE. dent Sprinkler with (specify type) fin- ish, PSN (specify). Chrome Plated Finish • s 1 155F/68C. . . .. PSN 51-680-9-155 � -.. The F680 Sprinklers must only be re- ammonia, cleaning fluids, or Natural Brass Finish placed with pendent sprinklers which other chemicals. Remove dust, 155F/68C... .. . ... PSN 51- 680.1 -155 are listed for residential fire protection lint, cobwebs, cocoons, insects, White Polyester Finish service and which have the same and larvae by gently brushing 155F/68C .. ... . .. PSN 51- 680 -4 -155 nominal K- factor, the same coverage with a feather duster or gently Chrome Plated Finish area, and the same or lower flow rat- vacuuming with a soft bristle (i.e., 175F/79C. . . ... .. PSN 51. 680 -9 -175 ings (as indicated under "Hydraulic dusting) brush attachment. Natural Brass Finish Design Criteria "). 175Fr79C.. .. ... .. PSN 51. 680.1.175 The minimum vertical clearance White Polyester Finish All residential sprinklers installed between the tops of free standing 175F/79C . . . . .. . PSN 51-680-4-175 within a compartment (as defined by partitions, room dividers, cab - the NFPA) must have the same heat inets, storage racks, stock piles, Recessed Escutcheon: response thermal characteristic, and etc., and the sprinkler deflector is Specify: 1/2" (15mm) Model (specify - their temperature ratings are to be NOT to be less than the clearance F700 or F705) Recessed Escutcheon { within 10 °F of each other. given below. with (specify finish), PSN (specify). i NOTES Horizontal Distance Vertical 1/2' (15mm) F700 Wet pipe sprinkler systems must from Sprinkler Clearance Chrome Plated . .. . PSN 56- 701 -9 -010 be maintained at a minimum tem- to Item, ft. In. 1/2' (15mm) F700 perature of 40F /4C. Exposure to White Color freezing temperatures can result More than 6 24 Coated . .. ... PSN 56- 701.4.010 g P 1/2' (15mm) F705 in bursting of the pipe and /or From 3 to 6 19 Chrome Plated . . . PSN 56.705 -9.010 . sprinkler. Between 2 and 3 16 1/2' (15mm) F705 From I to 2 13 White Color Do NOT enclose sprinklers within Less than I 10 Coated . .. . .... . . PSN 56.705 -4.010 . drapes, curtains, or valances. Sprinkler Wrench: Do NOT hang anything from the Exercise suitable safety precau- Specify: Model F850 Sprinkler sprinklers. Lions in the use and storage of Wrench, PSN 56 850 - - 001. highly flammable and potentially • Order for NFPA publications should be • Automatic sprinklers are NOT to exp materials. The rapid i. 1 be tested with a heat source. Op- rate of fire development and addressed to the: V . eration of the heat responsive spread which can be caused by Publication Sales Department 1 element (Bulb) can result. such materials can reduce the NFPA ability of the sprinkler system to Batterymarch Park Do NOT cleanse the sprinklers aid in the control of a fire in Quincy, MA 02269 with soap and water, detergents, which they are involved. 4 . — 11— ; WEIGHT The nominal weight of the Model F680 Designer Residential Pendent Sprin- kler is 2.7 ounces. ® Reg. trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833 A 174C0 INTERNATIONAL LTD. COMPANY GRINNELL FIRE PROTECTION SYSTEMS CO., INC. 2870 N.W. 29TH AVENUE PORTLAND, OR 97210 HYDRAULIC CALCULATIONS FOR RESIDENCE #1 11867 S.W. TREEHILL CT. TIGARD, OREGON FILE NAME:REZ1.SDF DATE: 6 -29 -99 - DESIGN DATA - OCCUPANCY CLASSIFICATION: NFPA 13D RESIDENTIAL MAXIMUM HEAD SPACING: 18 ft. X 18 ft. AREA OF APPLICATION: 223 sq. ft. COVERAGE PER SPRINKLER: 324 sq. ft. (maximum) NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 20.8 gpm TOTAL WATER REQUIRED (including hose): 120.8 gpm FLOW AND PRESSURE (@ BOR): 20.8 gpm @ 27.4 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: GRINNELL FIRE PROTECTION DESIGN /LAYOUT BY: JOE FREY AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR LICENSE NUMBER: 63205 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4 C1324J) HRS SYSTEMS, INC. ATLANTA, GA SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 ` Date: 06/29/1998 REZ1.SDF JOB TITLE: RESIDENCE #1 11867 S.W.TREEHILL CT. WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SRC 69.0 64.0 750.0 68.8 120.8 52.9 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 120.8 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 20.8 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) SRC 0.0 SOURCE 52.9 20.8 301 25.0 K= 3.00 12.3 10.5 302 28.0 K= 3.00 11.8 10.3 B1 25.0 - - - - 12.6 - - - B2 29.0 - - - - 11.5 - - - B2A 29.0 - - - - 11.7 - - - B3 29.0 - - - - 14.0 - - - B4 10.0 - - - - 22.9 - - - TOR 10.0 - - - - 23.3 - - - BOR 2.0 - - - - 27.4 - - - BF 2.0 - - - - 32.4 - - - X 9.5 - - - - 23.9 - - - Y -4.0 - - - - 35.5 - - - Z -4.0 - - - - 41.7 - - - WM1 -4.0 - - - - 43.5 - - - WM2 -4.0 - - - - 53.5 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 ` Date: 06/29/1998 REZ1.SDF JOB TITLE: RESIDENCE #1 11867 S.W.TREEHILL CT. PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 1 -10.5 1.101 PL 1.97 PF 0.3 301 25.0 3.0 12.3 10.5 3.5 150 FTG 2E PE 0.0 B1 25.0 0.0 12.6 0.0 0.021 TL 15.97 PV 0.1 Pipe: 2 -10.3 1.101 PL 1.00 PF 0.1 302 28.0 3.0 11.8 10.3 3.5 150 FTG T PE -0.4 B2 29.0 0.0 11.5 0.0 0.020 TL 6.00 PV 0.1 Pipe: 3 -10.5 1.101 PL 15.47 PF 0.6 B1 25.0 0.0 12.6 0.0 3.5 150 FTG 2E PE -1.7 B2 29.0 0.0 11.5 0.0 0.021 TL 29.47 PV 0.1 Pipe: 4 -20.8 1.394 PL 1.39 PF 0.2 B2 29.0 0.0 11.5 0.0 4.4 150 FTG T PE 0.0 B2A 29.0 0.0 11.7 0.0 0.023 TL 7.39 PV 0.1 Pipe: 4A -20.8 1.394 PL 31.36 PF 2.4 B2A 29.0 0.0 11.7 0.0 4.4 150 FTG 8ET PE 0.0 B3 29.0 0.0 14.0 0.0 0.023 TL 101.36 PV 0.1 Pipe: 5 -20.8 1.394 PL 20.00 PF 0.7 B3 29.0 0.0 14.0 0.0 4.4 150 FTG E PE 8.2 B4 10.0 0.0 22.9 0.0 0.023 TL 28.00 PV 0.1 Pipe: 6 -20.8 1.394 PL 3.00 PF 0.4 B4 10.0 0.0 22.9 0.0 4.4 150 FTG ET PE 0.0 TOR 10.0 0.0 23.3 0.0 0.023 TL 17.00 PV 0.1 Pipe: 7 -20.8 1.394 PL 6.00 PF 0.4 TOR 10.0 0.0 23.3 0.0 4.4 120 FTG E PE 0.2 X 9.5 0.0 23.9 0.0 0.035 TL 11.29 PV 0.1 Pipe: 8 -20.8 1.380 PL 4.00 PF 0.3 X 9.5 0.0 23.9 0.0 4.5 120 FTG E PE 3.2 BOR 2.0 0.0 27.4 0.0 0.037 TL 7.00 PV 0.1 Pipe: R1 FIXED PRESSURE LOSS DEVICE BF 2.0 0.0 32.4 0.0 5.0 psi, 20.8 gpm BOR 2.0 0.0 27.4 0.0 Pipe: 9 -20.8 1.049 PL 1.00 PF 0.4 BF 2.0 0.0 32.4 0.0 7.7 120 FTG E PE 2.6 Y -4.0 0.0 35.5 0.0 0.140 TL 3.00 PV 0.4 Pipe: 10 -20.8 0.995 PL 35.00 PF 6.2 Y -4.0 0.0 35.5 0.0 8.6 150 FTG 6ET PE 0.0 Z -4.0 0.0 41.7 0.0 0.120 TL 52.00 PV 0.5 Pipe: 11 -20.8 1.245 PL 40.00 PF 1.8 Z -4.0 0.0 41.7 0.0 5.5 150 FTG 2E PE 0.0 WM1 -4.0 0.0 43.5 0.0 0.040 TL 44.00 PV 0.2 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 06/29/1998 REZ1.SDF JOB TITLE: RESIDENCE #1 11867 S.W.TREEHILL CT. PIPE DATA (cont.) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 12 FIXED PRESSURE LOSS DEVICE WM2 -4.0 0.0 53.5 0.0 10.0 psi, 20.8 gpm WM1 -4.0 0.0 43.5 0.0 Pipe: 13 -20.8 1.245 PL 20.00 PF 1.1 WM2 -4.0 0.0 53.5 0.0 5.5 150 FTG ETG PE -1.7 SRC 0.0 SRCE 52.9 (N /A) 0.040 TL 28.00 PV 0.2 NOTES: (1) Calculations were performed by the HASS 6.2.0 computer program under license no. 4 C1324J granted by HRS Systems, Inc. 2193 Ranchwood Dr., N.E. Atlanta, GA 30345 (2) The system has been balanced to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.104 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 8.6 ft /sec at pipe 10. (4) PIPE FITTINGS TABLE Pipe Table Name: GRINNELL.PIP PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v Y Z GrvCpl GrvFit 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 1.00 4.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 1.00 4.00 PAGE: G MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 1.101 7.00 5.00 0.00 0.00 0.00 0.00 0.00 0.00 1.394 8.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 06/29/1998 REZ1.SDF JOB TITLE: RESIDENCE #1 11867 S..W.TREEHILL CT. PAGE: K MATERIAL: COPK HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 0.995 2.00 5.00 0.00 0.00 0.00 0.00 0.00 0.00 1.245 2.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 06/29/1998 REZ1.SDF JOB TITLE: RESIDENCE #1 11867 S.W.TREEHILL CT. WATER SUPPLY CURVE 72+ *0 \ \ \ \ \ \ \ \ \ \\ 66+ \\\\\\\\\\\\ * < -64.0 psi @ 750 gpm Flow Test Point 60+ 54 + X P 48+ R E S S 42 U R E 36+ ( P S I 30+ 24 + 18+ 12+ LEGEND " X = Required Water Supply 52.88 psi @ 120.8 gpm " 6+ " 0 = Available Water Supply " 68.83 psi @ 120.8 gpm " 11 0 + +- +--- + - - - -+ + + + + + + 200 300 400 500 600 700 800 900 1000 FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Date: 06/29/1998 REZ1 JOB TITLE: RESIDENCE #1 11867 S.W.TREEHILL CT. WATER SUPPLY CURVE WATER SUPPLY ANALYSI Static: 69.00 psi Resid: 64.00 psi Flou: 750.0 gpm 120.0 LEGEND Available pressure 1WA 68.83 psi 2 120.8 gpm 7A Required pressure 2% /A 52.88 psi 2 120.8 gpm 100.0 - 80.0 - in a ., w a m ( 60.0 - W a a w %b CD CD 40.0 20.0 0.0 -14.7 ii I I I I I I 200300 400 500 600 700 800 900 1000 FLOW (GPM>