Loading...
Specifications Feb :9 01. 07:43p t climate control 503 968 ?224 p.2 /DE Vr0ol cro 4 /5 • 58MVP Carrier 4 - Way Multipoise Direct -Vent HEATING ACOOUNG Variable- Capacity Condensing Gas Furnace Visit www.carner.cont Installation, Start-Up, Operating , and O eratin Instructions For S 040 -120, Series 130 and 140 Ili NOTE: Read rile entire instruction pt51G4, manual before starting the installation. l af;Hlc 4 r" R ATIN FNGr / ® CECIT1 /`� CEn T1F Ito /� \_ ',n ,rro, ama itip CCIA�� _ePreoreo °E,„,,,\,. e Ale CJ 4.00 Cor. A93040 This symbol --) indicates a change since the last issue. '�",� As an ENERGY STARW 50 9 001 MN Index Page Partner. Carney Corpora- ;ion lug, tktcnnincd that DIMENSIONAL DRAWING 1 ERG Y rmaSTARyt ^r® x yuidelutetarhoRN• c REGISTERED QUALITY SYSTEM SAFETY CONSIDERATIONS • 3 rot energy efficiency. Clearances to Combustibles 3 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ...,3 -4 AIRFLOW 4 INTRODUCTION 4 APPLICATIONS 4- l l General 4 Ar uPFLOW Uptlow Applications 4-7 Downtlow Applications 7 -8 l k er a Horizontal Left (Supply -Air Discharge) Applications 8 -9 \_ ,, Horizontal Right (Supply -Air Discharge) Applications 9 -I I 0 HORIZONTAL HORIZONTAL C > LOCATION y 11 -I3 \ LEFT 5, RIGHT DOWNFLOW General 1 1- 12 AIRFLOW AIRFLOW Low -Fire Only Installation 12-13 Furnace Location Relative to Cooling Equipment 13 '0 Hazardous Locations 13 AIRFLOW INSTALLATION 13 - 17 Fig. 1--- Multipoise Orientations A93041 Leveling Legs (If Desired) 13 Installation In Uptlow or Downflow Applications 13 -15 Heating Mode 32 -33 Installation In Horizontal Applications 15 Heating Mode —Two Stage 33 Air Ducts 15 Emergency Heat Mode 33 Filter Arrangement 16 Cooling Mode 33 -34 Bottom Closure Panel l6 Heat Pump Mode 34 Gas Piping 17 Continuous Fan Mode 34 -35 ELECTRICAL CONNECTIONS 17 -21 Component Test 35 115 -v Wiring 17 -18 Bypass Humidifier Mode 35 24 -v Wiring 18 -20 Dehumidification Mode 35 -36 Accessories 20 -21 Zone Mode 36 DIRECT VENTING /1 -29 START -UP PROCEDURES 36 -44 Removal of Existing Furnaces from General 36 Common Vent Systems 21 Select Setup Switch Positions 36 -37 Combustion - Air and Vent Piping 21 - 26 Prime Condensate Trap With Water 37 Concentric Vent and Combustion -Air Termination Purge Gas Lines 37 Kit Installation 26 -29 Adjustments 37 -43 Multiventing and Vent Terminations "9 Set Gas Input Rate 37 -43 CONDENSATE DRAIN 30 -31 Set Temperature Rise 43 General 30 Set Thermostat Heat Anticipator 44 Application 30 CHECK SAFETY CONTROLS.. 44 Condensate Drain Protection 30 -32 Check Primary Limit Control 44 SEQUENCE OF OPERATION 32 -36 Check Pressure Switch 44 Sell -Test Mode 32 CHECKLIST 44-45 Manufacturer reserves the right to discontinue, or change at any time, speciticatlons or designs without notice and without Incurring obligations. Book) I I 4 PC 101 Catalog No. 535 -747 Printed in U.S.A. Form 58MVP.9S1 Po 1 5 -99 Renlarns SAMVP -ACI Feb 19 01..07:43p climate control 503 968 7224 p.3 . i !I, Step 2— Combustion -Air and Vent Piping @ I GENERAL i --) Combustion -air and vent pipe fittings must conform to American 0 National Standards Institute (ANSI) standards and American , FURNACE � Society for Testing and Materials (ASTM) standards D 1785 _ • (schedule -40 PVC), D2665 (PVC -DWV), D2241 (SDR -21 and ( s chedule -40 ABS), `�� ___; - - SDR -26 PVC), D2661 (ABS-DWV), P628 ` - - -- �� F891 (PVC -DWV cellular core), or F441 (schedule -40 CPVC pipe) and F438 (schedule -40 CPVC fittings). Pipe cement and NOT IN pnmer must conform to ASTM standards D2564 or F493 (PVC or HORIZONTAL SECTION CPVC) or D2235 (ABS). See Table 6 for maximum pipe lengths and Fig 34, 35, 36, 37, and 38 for exterior piping arrangements. PIPE DIAMETER In Canada, construct all combustion -air and vent pipes for this unit TRANSITION IN VERTICAL SECTION of CSA or ULC certified schedule -40 PVC, PVC -DWV or ABS -DWV pipe and pipe, cement. SDR pipe is NOT approved in Canada. Fig. 29— Combustion -Air and Vent Pipe A93034 NOTE: Furnace combustion -air and vent pipe connections are Transition Location l a and Configuration sized for 2 -in. pipe. Any pipe size change should be made outside Furnace casing in vertical pipe. (See Fig. 29.) This allows proper NOTE: Select t vent pipe connection and NOTE Select i vent pipe connection and • '' drainage of vent condensate. I combustion-air pipe connection 1 combustion-air pupa connection Il Combustion -air and vent pipes must terminate together FLOW COMBUSTION- COMBUSTION- atmosphere pressure zone, either through roof or sidewall (roof AIR 4 AIR VENT i il termination preferred), using accessory termination kit. See Table ______ , P g ether in same 5 for required clearances. VENT ��� 1 T �ii , VENT Table 5— Combustion -Air and Vent Pipe I'' `� Nr :'' i Sig _Li Termination Clearances 1 \ - f i CLE ARANCE (FT) - -� LOCATION 1 U.S.A. Canada COMBUSTION- COMBUSTION - Above grade level or above anticl- FLOW A IR AIR AIR peted snow depth 1 1 t Dryer vent 3 3 UPFLOW DOWNFLOW From plumbing vent stack 3 3 From any mechanical fresh air Intake 1 6 : For furnaces with an input capacity of COMBUSTION - COMBUSTION- AIR I 100,000 Btuh or less —from any non- AIR mechanical air supply VENT VENT 1 doors mechanical can be opened) or 1, pp y (windows or 1 combustion -air opening AIR — -- __ FLOW 1 AiR For furnaces with an input capacity r FLOW i ' l • greater than 100,000 Btuh —from any Q III p ' ■ non - mechanical air supply (windows 1 3 — J or doors which can be opened) or • combustion -air opening — — From service regulator vent, electric ,■ and gas meters, and relief equipment 4* 6$ Above grade when adjacent to public HORIZONTAL -LEFT DISCHARGE HORIZONTAL•RIGHTDISCHARGE t walkway Note 3 Note 3 • ' Horizontal distance. t 18 In above roof surface in Canada. Fig. 3 0— Combustion -Air and Vent Pipe A 96187 t 36 In. to electric meter in Canada only. Connections • 1 NOTES: 1 If Installing 2 adjacent 58MVP Furnaces, rater to Mull:venting and Vent Terminations section for proper vent configurations. 2 When locating combustion -alr and vent terminations, consideration must be i given to prevailing winds, location, and otter conditions which may cause A CAUTION recirculation of the appliance's own flue products or the flue products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of heat exchangers. When combustion -air pipe is installed above a suspended 3 Vent termination can not terminate less than 2 ft horizontal and 7 ft above ceiling, pipe must he insulated with 3 /8 -in, thick Armaflex- public walkway or where condensate vapor or droplets may bee hazard. type insulation. Combustion -air pipe should also be insulated ii Furnace combustion -air and vent pipe connections must be at- when it passes through a warm, humid space. Cached as shown in Fig. 31. Combustion -air intake plug fitting and Inducer housing alternate vent cap may need to be relocated in I A CAUTION some applications. When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 7 with Armatlex -type insulation. , I Feb 19 01. 07:43p • climate control 503.968 7224 p.4 A CAUTION A WARNING Combustion air must not be taken from inside structure All combustion -air and vent pipes must be airtight and because that air is frequently contaminated by halogens, watertight. Pipes must also terminate exactly as shown in Fig. 1 which include fluorides, chlorides, bromides, and iodides. 33, 34, 35, 36. or 37. Failure to follow this warning could These elements are found in aerosols, detergents, bleaches, result in property damage, personal injury, or death. 4 . cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion -air inlet as far NOTE: The minimum combustion -air and vent pipe length (each) as possible from swimming pool and swimming pool pump for these furnaces is 5 ft. Short pipe lengths (5 -8 ft) may discharge house. water droplets. These droplets may be undesirable, and a 12 -in. Excessive exposure to contaminated combustion air will minimum offset pipe section is recommended. as shown in Fig. 31, result in safety and performance related problems. to reduce excessive droplets from exiting vent pipe outlet. 1 COMBUSTION -AIR AND VENT PIPE DIAMETER j A WARNING t Determine combustion -air and vent pipe diameter. -- Solvent cements are combustible. Keep away from heat, 'I sparks, and open flame. Use only in well ventilated areas. I. Using Table 6, individually determine the combustion -air and 4 Avoid breathing; in vapor or allowing contact with skin or v ehtftiptikilmotithte Ptah , ,: ters 4. ,�alhd use this diameter for both combusti , . eyes. Failure to follow this warning could result in (ire, a property damage, personal injury, or death. 2. When installing vent Systems of short pipe length, use t e smallest allowable pipe diameter. Do not use pipe size greater • : than required or incomplete combustion, flame disturbance, or flame sense lockout may occur. : so not count e . ws or pipe sections in terminations • w , .i•.ed areas in Fig. 34.35, • 4 1 : 12" MIN 12" MIN jo' I a' -- .: LFI I1 0I Ir ' 4 ,. VENT PIPE d pi 0 VENT PIPE - ♦ .......■■,/ I /-- COMBUSTION AIR PIPE I COMBUSTION -AIR PIPE u HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL COMBUSTION -AIR PIPE VENT PIPE ♦I�m` f COMBUSTION-AIR PIPE I goIor_ — Or - + I 12" MIN �J� will, will, go I .. • -i 12" MIN VENT PIPE • VERTICAL TO ROOF VERTICAL TO SIDEWALL , NOTE: A 12 In. minimum offset pipe section is recommended with • short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. . A98230 Fig. 31 —Short Vent (5 to 8 Ft) System Feb 19 01- 07:44p • climate control 503 '968 7224 P- Table 6— Maximum Allowable Pipe Length (Ft) ALTITUD (FT) UNIT TERMINATION PIPE DIAMETER NUMBER OF 90° ELBOWS SIZE TYPE (IN.)' 1 2 3 4 5 6 040 -14 2 Pipe or 2 -In. 1 -1/2 50 45 40 35 30 25 t ve Adi Concentric 2 7 70 70 70 70 70 70 080-14 2 Pipe or 2-in. 1-1/2 30 25 20 15 10 5 ' " ? ' 0 to 2000 080-20 Concentric _ 2 70 70 70 70 70 70 100-20 2 Pipe or 2 -In. 2 45 40 35 30 25 _ 20 Concentric 2 -1/2 70 70 70 70 70 70 2 -1/2 10 NA NA NA NA NA 120 -20 2 Pipe or 3 -In. 3 35 30 15 NA NA NA Concentric 3t 70 70 70 70 70 70 ALTITUDE (FT) UNIT TERMINATION PIPE DIAMETER NUMBER OF 90° ELBOWS SIZE TYPE (IN.)" 1 2 3 4 5 6 040-14 2 Pipe or 2 -In. 1-1/2 45 40 35 30 25 20 Concentric 2 _ 70 70 70 70 70 70 060 -14 2 Pipe or 2 -In. 1 -1/2 45 40 35 30 25 20 Concentric 2 70 70 70 70 70 70 2001 to 3000 080 -14 2 Pipe or 2 -In. 1-1/2 26 21 16 11 6 NA 080 -20 Concentric 2 70 70 70 70 70 70 100 -20 2 Pipe or 2 -In. 2 40 35 30 25 20 15 Concentric 2-1/2 70 70 70 70 70 70 120-20 2 Pipe or 3 -In. 3 31 26 12 NA NA NA Concentric 3t 63 62 62 61 61 61 ALTITUDE (FT) UNIT TERMINATION PIPE DIAMETER NUMBER OF 90° ELBOWS SIZE TYPE (IN.)° 1 2 3 4 5 6 - 040-14 2 Pipe or 2 -In. 1 -1/2 42 37 32 27 22 17 Concentric 2 70 70 70 70 70 70 060-14 2 Pipe or 2 -In. 1 -1/2 42 37 32 27 22 17 Concentric 2 70 70 70 70 70 70 3001 to 4000 080-14 2 Pipe or 2 -In. 1 -1/2 25 20 15 10 5 NA 080 -20 Concentric 2 70 70 70 70 70 70 100 -20 2 Pipe or 2 -In. 2 38 33 28 23 18 13 Concentric 2 -1/2 70 70 70 70 70 70 120-20 2 Pipe or 3 -In. 3 29 24 — 10 NA NA NA Concentric 3t 59 59 58 57 57 56 ALTITUDE (FT) UNIT TERMINATION PIPE DIAMETER NUMBER OF 90° ELBOWS SIZE TYPE (IN.)" 1 2 3 4 5 6 040-14 2 Pipe or 2 -in. 1-1/2 40 36 30 25 20 15 Concentric 2 70 70 70 70 70 70 060-14 2 Pipe or 2 -In. 1 -1/2 40 35 30 25 20 15 Concentric 2 70 70 70 70 70 70 4001 to 5000* 080 -14 2 Pipe or 2 -In. 1 -1/2 23 18 13 8 NA NA 080 -20 Concentric 2 70 70 70 70 70 68 100 -20 2 Pipe or 2 -In. 2 36 31 26 21 16 11 Concentric 2 -1/2 70 70 70 70 70 70 120 -20 2 Pipe or 3 In. 3t 56 55 54 53 52 52 Concentric ALTITUDE (FT) UNIT TERMINATION PIPE DIAMETER NUMBER OF 90° ELBOWS SIZE TYPE (IN.)" 1 2 3 4 5 6 040 -14 2 Pipe or 2 -In. 1 -1/2 37 32 27 22 17 12 Concentric 2 70 70 70 70 70 70 060 14 2 Pipe or 2 -In. - 1 -1/2 37 32 27 22 17 12 Concentric 2 70 70 70 70 70 70 5001 to 6000$ 080 -14 2 Pipe or 2 -In. 1 -1/2 22 17 12 7 NA NA 080 -20 Concentric 2 70 70 70 70 68 63 • 100 -20 2 Pipe or 2 -In. 2 33 28 23 18 13 8 Concentric 2 -1/2 70 70 70 70 70 70 120 20 2 Pipe or 3 -In. 3t 53 52 50 49 48 47 Concentric See notes on next page. 25 Feb 19 01. 07:44•p • climate control 503 '968 '7224 p.6 LI' use of this drain connection is desired, drill out fitting's tap EXAMPLE: plug with a 3 /16 -in. drill and connect a field- supplied 3 /8 -in. An 080 -14 size furnace located in Indianapolis, elevation tube. This tube should be routed to open condensate drain for 650 ft above sea level, could be installed in an application furnace and A/C (if used), and should be trapped. (See Fig. requiring 3 elbows and 17 ft of vent pipe, along with 5 32.) ''`'' elbows and 16 ft of combustion -air pipe. Table 6 indicates this application would allow a 1- 12 -in. diameter vent i P Pe• COMBUSTION - AIR but require a 2-in. diameter combustion air pipe (1-1/2-in. INTAKE HOUSING 3/6' ID TUBE BURNER pipe is good for 20 ft with 3 elbows, but only 10 ft with 5 BOX elbows). Tlieretore, 2 -in. diameter pipe must be used for both ve nt and combustion -air pipes since larger required - L_ O � 4_ diameter must always be used for both pipes. If same installation were in Albuquerque. elevation 5250 ft above Le• O la sea level, installation would require 2 -in. vent pipe and 3116" DRILL combustion -air pipe. At 5001- to 6000 -ft elevation, I -12 l • COMBUSTION - - AIR PIPE in. pipe is not allowed with 5 elbows, but 2 -in. pipe is good 4 ° for 68 ft with 5 elbows. MIN TRAP • COMBUSTION - AIR AND VENT PIPE ATTACHMENT ° Al l TO OPEN IMO NOTE: All pipe joints must be watertight except attachment of DRAIN combustion -air pipe to inlet housing connection since it may be necessary to remove pipe for servicing. Fig. 32— Intake Housing Plug Fitting Dra in 3035 1. Attach combustion -air pipe as follows: 2. Attach vent pipe as follows: a. Determine location of combustion -air intake pipe connec- non to combustion -air intake housing as shown in Fig. 30 a. Determine location of vent pipe connection to inducer For application. housing as shown in Fig. 30 for application. b. Reposition combustion -air intake housing plug fitting in b. Reposition elastomeric (rubber) inducer housing outlet cap appropriate unused intake housing connection. and clamp to appropriate unused inducer housing connec- tion. Tighten clamp. c. Insert perforated disk assembly (factory supplied) in intake housing where combustion -air intake pipe will be con- A WARNING neeted. : :s 0 ._ d. Install pipe support (factory- supplied in loose parts bag) Inducer housing outlet cap must be installed and fully seated into selected furnace casing combustion -air pipe hole. Pipe against inducer housing. Clamp must be tightened to prevent support should be positioned to bottom of casing hole. any condensate leakage. Failure to follow this warning could e. Insert 2 -in. diameter pipe into intake housing. result in electrical shock, fire, personal injury, or death. NOTE: 'A 2 -in. diameter pipe must be used within the furnace c. Install pipe support (factory- supplied in loose parts bag) casing. Make all pipe diameter transitions outside furnace casing. into selected furnace casing vent pipe hole. Pipe support f. Drill a 1 /8 -in. hole in 2 -in. combustion -air pipe using hole should be positioned to bottom of casing hole. in intake housing as a guide. --) d. Be certain that mating surfaces of inducer housing connec- g. Install a field- supplied No. 6 or No. 8 sheet metal screw tion, elastomeric coupling, and 2 -in. diameter vent pipe are into combustion -air pipe. clean and dry. Assemble the elastomeric (rubber) vent NOTE: DO NOT OVERTIGHTEN SCREW. Breakage to intake coupling (with 2 loose clamps) onto inducer housing housing or fitting may cause air leakage to occur. connection. Insert the 2 -in. diameter vent pipe through the NOTE: Do not attach combustion -air intake pipe permanently to elastomeric (rubber) coupling and fully into inducer boas combustion -air intake housing since it may be necessary to remove ing connection until it bottoms on the internal stop. Tighten both clamps to secure the pipe to inducer housing. Tighten pipe for service of ignitor or flame sensor. the clamp screws to 15 in. -Ib, of torque. COMBUSTION -AIR INTAKE HOUSING PLUG FITTING The combustion-air intake plug fitting must be installed in A WARNING unused combustion -air intake housing. This lilting must be attached by using RTV sealant, or by drilling a I /8 -in. hole in Vent pipe must be installed and fully seated against inducer fitting, using hole in intake housing as a guide. Install a housing internal stop. Clamp must be tightened to prevent any field - supplied No. 6 or No. 8 sheet metal screw, condensate leakage. Failure to follow this warning could NOTE: DO NOT OVERTIGHTEN SCREW. Breakage to intake result in electrical shock, fire, personal injury, or death. housing or fitting may cause air leakage to occur. NOTE: A 2 -in. diameter pipe must be used within the furnace A plugged drain connection has been provided on this fitting casing. Make all pipe diameter transitions outside furnace casing. for use when moisture is found in combustion - air intake pipe 3. Working from furnace to outside, cut pipe to required • .,,l' and combustion box. length(s). Moisture in combustion -air intake may be result of 4. Deburr inside and outside of pipe. improper termination. Ensure combustion -air intake pipe is similar to that shown in Fig. 33, 34, 35, 36, or 37 so it will not be 5. Chamfer outside edge of pipe for better distribution of primer susceptible to areas where light snow or other sources of moisture and cement. could be pulled iii. 6. Clean and dry all surfaces to be joined. Feb 19 O 1 07:45(0 , climate control 503 -968 7224 P - 7 Table 7— Maximum Allowable Exposed Vent Pipe Length (Ft) With Insulation in Winter Design Temperature Ambient* NIT WINTER DESIGN MAXIMUM PIPE INSULATION THICKNESS (IN.)t U SIZE TEMPERATURE DIAMETER ( °F) (IN.) 0 3/8 1/2 3/4 1 20 2 21 37 42 50 57 t • 040 - 0 2 10 22 25 30 35 4.k 1.:' -20 2 • 5 14 17 21 25 • — 2 `30) 65 81 70 70 • 2 16 33 38 46 53 ' , - - -20 2 9 23 26 33 38 • 20 2 37 65 70 70 70 y 080 -14 0 2 20 39 45 55 63 080 -20 ... -20 2 11 27 31 39 45 - 20 2 -1/2 41 70 70 70 70 $. 100 - 0 2 -1/2 21 42 48 59 68 -20 2 -1/2 11 28 33 41 49 20 3 49 70 70 70 70 120 - 20 0 3 26 51 58 70 70 j -20 3 15 35 40 50 59 I I ' Pipe length (f1) specified for maximum pipe lengths located in unconditioned spaces. Pipes located In unconditioned space cannot exceed total allowable pipe length 1 as specified in Table 6. t Insulation thickness based on R value of 3.5 (ft 2 ' °F•hr.) /(Btu•in.) I NOTE' Do not allow insulation or other materials to accumulate When a condensate pump is required. select a pump which is inside of pipe assembly when installing it through hole, approved for condensing furnace applications. To avoid conden- sate spillage, select a pump with an overflow switch. Roof terminations— Locate assembly through roof to appro- Furnace condensate is mildly acidic, typically in the pH range of priate height as shown in Fig. 34. 3.2 to 4.5. Due to corrosive nature of this condensate, a condensate Sidewall terminations — Locate assembly through sidewall pH neutralizing filter may be desired. Check with local authorities with rain shield positioned no more than 1 -in. from wall as to determine if a pH neutralizer is required. shown in Fig. 34 , 4 I 5. Disassemble loose pipe fittings. Clean and cement using same Step 2— Application procedures as used for system piping. The furnace, A /C, and humidifier drains may be combined and 6. Check required dimensions as shown in Fig. 34 or 35. drained together. The A/C drain must have an external, field- Step 4—Multiventing and Vent Terminations supplied trap prior to the furnace drain connection. All drain connections (furnace, A /C, or humidifier) must be terminated into When 2 or more 58MVP Furnaces are vented near each other, each an open or vented drain as close to the respective equipment as furnace must be individually vented. NEVER common vent or possible to prevent siphoning of the equipment's drain. 3 breach vent 58MVP furnaces. When 2 or more 58MVP furnaces , are vented near each other, 2 vent terminations may be installed ac See Fig 43 for example of possible field drain attachment using i shown in Fig. 38, 39, 40, 41, or 42, but next vent termination must I /2 - m. CPVC or PVC tee for vent and A/C or humidifier drain be at least 36 in. away from first 2 terminations. It is important that connection. vent terminations be made as shown to avoid recirculation of flue Outdoor draining of the furnace is permissible if allowed by local gases. Dimension "A" in Fig. 38, 39, 40, 41, and 42 represents codes. Caution should be taken when freezing ambient may freeze distance between pipes or rain shields, as touching or 2 -in, drain pipe and prohibit draining. maximum separation. CONDENSATE DRAIN p WARNING Step 1— General Condensate trap is shipped installed in the blower shelf and factory Caution should be taken to prevent draining where slippery connected for UPFLOW applications. Condensate trap must be conditions may cause personal injuries. Excessive condensate RELOCATED for use in DOWNFLOW and HORIZONTAL draining may cause saturated soil conditions which may result applications. in damage to plants. Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain to this condensate trap. Step 3— Condensate Drain Protection The field drain connection (condensate trap or drain tube coupling) Freezing condensate left in condensate trap and drain line may is sized foe 1 /2 - in. CPVC, 1 /2 - in. PVC. of 5 /8 - in. ID tube cause cracks, and possible water damage may occur. If freeze connection, protection is required, use condensate freeze protection accessory Drain pipe and fittings must conform to ANSI standards and or equivalent 3 to 6 watt per ft at 120v and 40 °F self - regulating, 0 ASTM D1785 or D2846. CPVC or PVC cement and primer must conform to ASTM D2564 or F493. In Canada, use CSA or ULC certified schedule 40 CPVC or PVC drain pipe, fittings, and cement. Feb ;9 01. 07:43)o c l i mate control 503 '968 `7224 p. 1 ,446 0 2� 1- v-o-o'f 9 16500 SW 72"' Ave Portland, OR 97224 (503) 453 -HVAC fax(503) 968-7224 Climate Control Fax To: Rick, Tigard Mechanical Inspector From: Jason Young Fax: 503 - 598 -1960 Pages: 2 Phone: 503 - 639 -41 Date: February 19, 2001 Re: 11530 SW Tigard Dr inspection CC: Cl Urgent ❑ For Review ❑ Please Comment ❑ Please Reply 0 Please Recycle • Comments: Rick, About 2 weeks ago, you did the final mechanical inspection at 11530 SW Tigard Dr. The two corrections you came up with were. A) Vent pipe should be 2" PVC instead of 1W B) Vent pipe should be insulated, per manufacturers' instructions. Hopefully, both of these were simply an oversight on your part, or a misunderstanding of the manufacturers' instructions. I have enclosed the pertinent pages from the installation manual for your reference. By way of reminder, this was a downflow 90% Carrier gas furnace in the garage, with the exhaust & intake pipes running to the roof Each pipe is 9 feet long with 3 90° elbows. As far as i can see, this is a legal installation. Am I wrong? Please get back to me ASAP, as my customer is eager to be done with the project. Thanks, Jason Young 503.740.0624 cell 503 968 7224 fax