RE: DAKOTA MEADOWS
DEAR JAMES:
WE HAVE PROVIDED ANALYSIS FOR THE KEYSTONE WALLS YOU WISH TO BUILD.
YOUR WALLS MAY GO UP TO 5 FEET WITHOUT REINFORCING, IF THE KEYSTONE
STANDARD UNITS ARE USED. PER YOUR REQUEST, WE HAVE ALSO LOOKED AT
USING REINFORCING FOR HIGHER WALLS UP TO 6 FEET, USING A KEYSTONE
COMPACT UNIT IN CONJUNCTION WITH FORTRAC 35 -20/20 REINFORCING
MATERIAL. A 6' WALL IN THIS CASE WILL REQUIRE ONE LAYER OF
REINFORCING, 4' LONG, PLACED PER THE MANUFACTURER'S
RECOMMENDATIONS ON TOP OF THE FOURTH BLOCK.
FOR THESE DESIGNS, WE HAVE ASSUMED A LEVEL BACKFILL CONSISTING OF
CLEAN 1 1/4" MINUS WITH NO FINES AND A NATIVE SOIL WITH AN ANGLE OF
INTERNAL FRICTION OF 26 DEGREES. STANDARD DRAIN PIPE NEEDS TO BE
INSTALLED FOR DRAINAGE, AND SUITABLE BASE EXCAVATION NEEDS TO BE
CONFIRMED BY THE SOIL ENGINEER. 1u,4.g /246:.4.26-10 1 iLL -4-i- t
IF YOU HAVE ANY QUESTIONS, PLEASE CALL US AT 503 -598 -1866.
SINCERELY,
c _
EDWARD K. CHRISTENSEN, P.E.
PRINCIPAL
7150 SW Hampton Street, Suite 226 • Portland, Oregon 97223 • Phone: (503) 598 -1866 • Fax: (503) 598 -1868
E -Mail: cei @cybernw.com
page / of 1
KEYSTONE RETAINING WALL DESIGN
Based on Coulomb -NCMA (modified soil interface) Methodology
KeyWall Ver lb, Oct 1, 1997
CHRISTENSEN ENGINEERING, INC.
Project: D + J CONSTRUCTION 9/29 Date: 9/29/1998
Proj. No.: - By: RN
Design Parameters
Soil Parameters c psf ,x pd
Reinforced Fill: 34 0 120 ` } "_`
Retained Fill: 26 0 120
Foundation Fill: i v 26 `` fn„ 0 120 1S
Reinforce Fill Type: S- minus v crushed stone or gravel I ,,ti :
Unit Fill: Crushed Stone, 1 inch minus t` .'
Factors of Safety
Sliding: 1.50 Overturning: 2.00
Pullout: 1.50 Uncertainties: 1.50 Bearing: 2.00
Connection Peak: 1.50 Serviceability: N/A
Reinforcing Parameters: Generic Geogrids
Tult RFcr RFd RFid LTDS FS Tal Ci Cds
Gen -15+ 2503 1.67 1.20 1.20 1041 1.50 694 1.00 1.00
Analysis: Section
Unit Type: COMPAC Wall Batter: 7.10 deg.
Leveling Pad: Crushed Stone
Wall Ht: 6.00 ft embedment: 0.50 ft
Level Backfill
Surcharge: LL -- 0 psf uniform surcharge DL -- 0 psf uniform surcharge
Results: Sliding Overturning Bearing Shear Bending
Factors of Safety: 2.14 4.79 3.15 4.52 2.43
Calculated Bearing Pressure: 754 psf
Eccentricity at base: 0.27 ft
Reinforcing: (ft & Ibs /ft)
Layer Height Length Reinf. Tal Tension Tconn FSpo
1 ^ 2.67 4.00 Gen -15+ 466 431 466 * 1.89
Reinforcing Quantities (no waste included): ( Efficiency= 62% )
Gen -15 +: 0.44 sy /ft
y � ,) PROFF
� E& V O A
16,166 r v �
nor OREGON
O � �p p 15 V -Ce
CHR+ '
i r Z13 9
NOTE: THESE CALCULATIONS ARE FOR PRELIMINARY DESIGN ONLY AND SHOULD
NOT BE USED FOR CONSTRUCTION WITHOUTREVIEW BY QUALIFIED ENGINEER
Minneapolis, MN 55435
page I of
• KEYSTONE RETAINING WALL DESIGN
Based on Coulomb -NCMA (modified soil interface) Methodology
KeyWall Ver lb, Oct 1, 1997
CHRISTENSEN ENGINEERING, INC.
Project: D + J CONSTRUCTION 9/29 Date: 9/29/1998
Proj. No.: By: lc
Design Parameters
Soil Parameters c psf
Reinforced Fill: 34 0 120
Retained Fill: 26 0 120
Foundation Fill: 26 0 120
Reinforce Fill Type: 0.75" minus crushed stone or gravel t
Unit Fill: Crushed Stone, 1 inch minus
Factors of Safety
Sliding: 1.50 Overturning: 1.50
Pullout: 1.50 Uncertainties: 1.50 Bearing: 2.00
Connection Peak: 1.50 Serviceability: N/A
Analysis: Section
Unit Type: STANDARD (21.5 in) Wall Batter: 7.10 deg.
Leveling Pad: Crushed Stone
Wall Ht: 5.00 ft embedment: 0.50 ft
Level Backfill
Surcharge: LL -- 0 psf uniform surcharge DL -- 0 psf uniform surcharge
Results: Sliding Overturning Bearing Shear Bending
Factors of Safety: 1.71 1.81 2.89 N/A N/A
Calculated Bearing Pressure: 748 psf
Eccentricity at base: 0.36 ft
„OD PROp s
<V 5 1GINf4 4%
16,166
F s OREGON
O j 5 1,15v Z
'QOk CHRISr(
NOTE: THESE CALCULATIONS ARE FOR PRELIMINARY DESIGN ONLY AND SHOULD
NOT BE USED FOR CONSTRUCTION WITHOUT REVIEW BY QUALIFIED ENGINEER
Minneapolis, MN 55435
Main Office Branch Office
PO Box 23814 4060 Hudson Ave.
Tigard, OR 97281 Salem, OR 97301
Carlson Testing, Inc. Phone (503)684 -3460 Phone (503)589 -1252
Fax # (503)684 -0954 Fax # (503)589 -1309
August 19, 1998 b7 ---q5- 02- 6 3
#97-G1353 - 604
Beacon Homes
9500 SW 125th Ave.
9,, 11
Beaverton, OR 97005
— 4 1 / 0
FINAL SOILS LETTER
DAKOTA MEADOWS - BUILDING PADS 1 -4 and 18 -25
CITY OF TIGARD, OREGON
This letter confirms that as of August 11th, 1998, density testing on the granular engineered fill was
adequately completed. Based on our observations and testing, the fill location was properly prepared
and the fill achieved at least 90 percent of the modified Proctor maximum dry density. The above
listed pads are suitable for foundation and slab support.
Information contained herein is not to be reproduced, except in full, without prior authorization from
this office. If there are any further questions regarding this matter, please do not hesitate to contact
this office.
Respectfully submitted, l f /A 3/ ,e/ix) t6u
CARLSON TESTING, INC. 446(A#4-40
t o P - / ja // GINf£ si 4743 4 — / /� r , C j�iit�c. --
N &L � 23 v4 19 2_" /l 30 / j "
• Mes D. 00 e L,./0 re. 7 fq If aM )4(1 11,1 /i & , e ___
ao /f301-f N
James D. Imbrie, P.E. d �kji,(._
Geotechnical Engineer a (- 1/ 3' /
cc: City of Tigard a s- 039
---, a3- LL376 = -.0
a5- toP 0) -litii, / �e'
Ma! ,rfi. Branch Office
�
PO B23814 4060 Hudson Ave.
` Tigard, OR 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503)684 -3460 Phone (503)589 -1252
Fax # (503)684 -0954 Fax # (503)589 -1309
August 19, 1998
-
#97-G1353 ) ---rjeAA-
Beacon Homes
9500 SW 125th Ave. C�J
Beaverton, OR 97005
FINAL SOILS LETTER
DAKOTA MEADOWS - BUILDING PADS 1-4 and 18 -25
CITY OF TIGARD, OREGON
This letter confirms that as of August 11 th, 1998, density testing on the granular engineered fill was
adequately completed. Based on our observations and testing, the fill location was properly prepared
and the fill achieved at least 90 percent of the modified Proctor maximum dry density. The above
listed pads are suitable for foundation and slab support.
Information contained herein is not to be reproduced, except in full, without prior authorization from
this office. If there are any further questions regarding this matter, please do not hesitate to contact
this office.
Respectfully submitted,
CARLSON TESTING, INC. 101- ° a,k1
� c 50 PRcipi- t 12 6(�t ■ Fa
i�
e co E 14743 f £R /qk �� I ( Z 6 - -- _ na(ed ✓
/ 7) 4 ‘
�_ 2 6,v_ ' %�� 1 �1G1'(.t? 0V AN
►cam
/
OREGON �r01 P� R' aLG�
N, 23. N
4 �'ES b7,0 E
7 • (..- it7 1°I 11 3(t (u Ib EilMl L'
..• I132( Bi,c-Fck Co fnct ,
James D. Imbrie, P.E. Z 1
Geotechnical Engineer 1 • • "'A_
� 2 I (3) 6 ik-=� v e ,
cc: City of Tigard 2� Rai() () gD ro-
o z`A I l 3 gel 6t,�. to _
•).5 ( 13_• _r -
f
•
V /ZVIUV TILL V / :4J real aVJ o X7141 \.111t1...JV1y 1LJt11vb WJuu.3 •
Main ' vice Branch Office
`/ s PO Bc,_,3814 4060 Hudson Ave.
Tigard, OR 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503)684-3460 Phone (503)589 -1252
Fax # (503)684 -0954 Fax* (503)589 -1309
July 28, 1998
CTI #97 -G1353
Beacon Homes
9500 SW 125th Avenue
Beaverton, Oregon 97005
FINAL REPORT OF EARTHWORK OBSERVATION AND TESTING
DAKOTA MEADOWS SUBDIVISION
TIGARD, OREGON
Carlson Testing Inc. (CTI), has conducted on -call inspection services for the earthwork at the
above residential development located off SW North Dakota & SW 105th PI in Tigard, Oregon.
This final letter briefly summarizes our observations and testing during construction, and the
as -built soil conditions to the best of our knowledge. Foundation design input has already
been addressed in previous reports provided by CTI. In addition, CTI has reviewed and
stamped the approved plans to verify that the previous recommendations were incorporated
into the design of the foundations.
SITE PREPARATION AND FILL PLACEMENT
Based on our visual observations and our density test results, after stripping vegetation and
topsoil, engineered fill using on -site soil was moisture- conditioned and placed on the following
areas to a maximum depth of approximately 3 feet.
LOTS: 5 - 17 and 23 - 25
Based on the in -place soil density results and our visual observations, it is our opinion that the
engineered fill on the above lots was generally placed in conformance with the City of Tigard
standards. On the attached test summary, lot tests LF -1 through LF -20 were density tests
taken during both a morning and afternoon visit by CTI on 1 -9 -98. These test were slightly
lower than the minimum compaction requirement. CTI conducted a follow up visit on 2 -3 -98
and retested the failing areas. All retests exceed the minimum compaction requirement. The
retests are listed as structural fill tests SF -1 through SF -6. The engineered fill is considered
suitable for support of spread footings. The remaining lots within the subdivision were either
cut lots or lots left near original grade.
11200 lei t (d ✓ 0 &AAR-t J b
■ -
5 (l3�
1(2.10 6vk• 4.1D ,./ -�
I (3 SO 6U (�Y� it 2-35 takf-retlo ,.., t
3_ 1( 2 6i,(4-(-4.10 ../ 4 .).. t122-0 X1.1 10 "\
i l - l l 21Q0 hi,uCo ,/
1 it 280 6
&- . to
'(H ((210
5 I 0 614_ o --
09/Z9/99 WKll U7:44 FAA 503 Ei70 9147 CAKLSUN 11:5111\(; 41004
CTI #98-G1353 ,...-- , ,.......,
98 -G 1353 `�
Dakota Meadows
•
Page 2
CLOSING AND LIMITATIONS
Our reports pertain to the materials tested /inspected only. This letter should not be construed
to relieve or lessen the responsibility of the contractor or owner's site representative for this
site work, but is provided for the minimum required governmental assurance. Our support was
given on an as- needed basis as requested. If conditions are encountered during foundation
excavation which differ from this report, then the developer (Beacon Homes), the contractor
(GVS), and CTI should be allowed to review the condition before corrective actions are taken.
Corrective work performed by the builder without notifying the above parties will be
interpreted as an acceptance of the conditions encountered.
Respectfully submitted,
itli PR
CARLSON TESTING, INC. t*GINEER Jo y
4.
14743 /
1, J p° may
/ � OREGON
v4, 4�r 23.1990
,ES D . 111: C-- 66-77
. C '
Brian D. Leach, E.I. James D. Imbrie, P.E.
Engineering Associate Principal Engineer
Attachments: Summary report of in -place soil density tests
U9/Z9/99 WF.l) U7:44 FAA DU:$ ($70 9147 CAKLSON TESTING 10005
CTI #98-G1353
Dakota Meadows
Page 3
APPENDIX A
IN -PLACE DENSITY TESTING
A minimum of 90 percent of the maximum dry density obtained from the Modified Proctor
(AASHTO T -180) was required for engineered fill placed in the lots of this development. The
field density testing was performed in general conformance with ASTM D2922 and D3017,
utilizing a nuclear density gauge.
A complete density test result summary is attached. Prefix designations on the test nos.
indicate the type of fill being tested as follows:
NC- No Code (general fill areas and backfill}
LF- residential Lot engineered Fill
RF- Roadway engineered Fill
PS- Pavement Subgrade
BC- Base Course
RW- Retaining all backfill
WT- Water line Trench
ST- sanitary Sewer Trench
DT- Storm Drain Trench
Any suffix designation's (A, B, C, etc.) indicate results of retests which immediately follow
the original failed test.
09/29/2111 WED 07.44 FAA 50:$ tt7U x147 CAKLSUN 1t,S1 4.1UUt)
Construction Inspection & Related Test~
Carlson Testiirg, Inc.
SUMMARY REPORT OF
P.O. Box 23814
IN-PLACE DENSITY TESTS Tigard, Oregon 97281
Phone (503) 684-3460
JOB NO. 97 - G1�5� FAX (503) 684-0954
Jul 16, 1998
Client
BEACON HOMES
Project DAKOTA MEADOWS _ _ -
- 8' i - 3 ^ .- 1
DATE OF TEST Eavrtium 'PAP= % ALL. RELD D CRY RELamIE
DN
TEST LOCATION ' oasmr COARSE MAX wOTTURt Dear' co)dractioN
TEST NO P6I n 3 ) PARTICLES DENS. (%) aD1(0) t%)
BC STATION 3+50 SW N DAKOTA TOP
1 18' RIGHT OF CENTERLINE
3- 6 144.6 7.7 137.5 9E
DC 'STATION 4 +25 SW N DAKOTA TOP
12' RIGHT C CENTERLINE
3- 6 144.6 8.2 137.8 9t
BC STATION 4+75 SW N DAKOTA TOP
3 16' RIGHT OF CENTERLINE
3- 6 144.6 6.8 137.5 9E
LF LOT 51 CENTER +2.0
1
1- 9 144.6 5.5124.3 (3c
LF LOT 61 CENTER +2.0'
2 . (7
1- 9 144.6 5.5 125.4 U,
LF LOT 7: CENTER +2.0
1- 9 _ 144.6 6.1 126.4 2'
LF LOT 8, CENTER +2.0
4
1- 9 144.6 5.6 123.5 g'
LF LOT 91 CENTER +2.0
5
1- 9 144.6 6.4 121.4 E.•
LF LOT 10+ CENTER +E.0
6
1- 9 144.6 6.1 121.9 8-
LF LOT 11, CENTER +2.0
7
1- 9 144.6 6.6 1256 8
LF LOT 12, CENTER +2.0
s
1- 9 144.6 6.4 126.3 8
LF LOT 139 CENTER +2.0
1- 9 9 1 , 144.6 6 ..9 127.1 8
cc: CITY OF TIGARD
ALPHA ENGINEERING INC
CARLSON TESTING IN(
Information contained herein is not to be reproduced, except in full, without prior authorization from this office.
09/Z9/99 WED 07:45 FAX 503 670 9147 CARLSON TESTING l¢J007
C arlson T Inc. • Construction Inspection &Related Te:
SUMMARY REPORT OF
IN -PLACE DENSITY TESTS P.O. Box 23814
Tigard, Oregon 97281
JOB NO. ?7 -C'1 353 Phone (503) 684 -3460
FAX (503) 684 -0954
Jul 16: 1998
Client BEACON HOMES
Project DAKOTA MEADOWS
SW NUR i H DAKOTA SW 105TH PL - I IGARU --
DATE OF TEST ELEV EVrH FIELD HELD DRY FE VINE
TEST NO TEST LOCATION DAY D€N r cam MAX , o mom
0/0) PARTICLES DENS. (96) (m f R (Y.)
LF LOT 55 FRONT CENTER -2.0
10
_
1- 9
LF LOT 6, FRONT CENTER 144 6.1 127.0 g
11 -2.0
1- 9
LF LOT 71 FRONT CENTER -2.0 144^ E•2 124'
12
1- 9
LF LOT 0, FRONT CENTER 144.6 ° 122.7
13
-2.0
1- '
LF LOT 9, FRONT CENTER 1`14 ° .4 125.0 S
14
-2.0
1- 9
LF LOT 10 FRONT CENTER 144 ^ E 9 1``x'0 c.
15
-2.0
1- 9
LF LOT 11s FRONT CENTER 144 6 . 3 124.E 8( 16 -2.Q
1- 9
LF LOT 12, FRONT CENTER -2.0 144E • 0 125.3
17
1- 9
LF LOT 151 BACK CENTER 144. ��' • 124.7 8c
18
-2.0
1 - 9
LF LOT 16s 144 .6 7.0 126.1 87
BACK CENTER -2.0
19
1- 9,
LF LOT 17/ SACK CENTER 144 6 °8 125.7 g7
ZO -2.0
1
LF CENTER OF LOT 17 144 t "° 125'3 Si
21
-
144.6 8 . 0 1 142.0 991
cc: CITY OF TIGARD
ALPHA ENGINEERING INC
CARLSON TESTING INC.
Information contained herein is not to be reproduced, excevt in full, withou t n alohnri,arin.,
U,y /Z /bb 1thD U7 :45 FAX 5U:3 157U U147 CAKLSUN TESTING 410013
Construction Inspection & Related Test
Carlson Testing, Inc.
SUMMARY REPORT OF
P.O. Box 23814
IN -PLACE DENSITY TESTS Tigard, Oregon 97281
Phone (503) 684 -3460
JOB NO. 97-G1:35"3 FAX (503) 6840954
Jul 163 1998
Client -
HOME - N
Project DAKOTA MEADOWS
SW NUI 1 H DAKW H S 5W 1Ob 1 H 3-'L - 1 1UHHt)
DATE OF TEST aEvroerro ae wa % Ai- RED FED DRY RELATIVE
TEST NO
TEST LOCATION Ana oaro Ary COARSE MRX MOISTURE oENSrrr cam�cTON
r 1 ewner Es �r+s (x) W r rr'1 (�)
LF CENTER OF LOT 23
144.6 7.5 137.8 9E
LF CENTER OF LOT 24
23
2- 144.6 7.9 140.4 97
LF CENTER OF LOT 25
24
2- 3 144.6 8.8 143.3 9S
SF FILL BETWEEN LOTS 5/6
1
3 144.6 8.1 142.5 95
SF FILL ' BETWEEN LOTS 7/8
2- 3 144.6 7.7 1==5.5 ' ?E
SF FILL BETWEEN LOTS 9/10
•
3
2 3 144.6 7.9,141.1 9E
SF FILL BETWEEN LOTS 11/12
4
2- 3 144.4 6.9 137.7
SF FILL BETWEEN LOTS 13/14
5
2 3 144.6 7.3 137.4 9E
SF FILL BETWEEN LOTS 15/16
6
2- 3 144.6 8.2 1:39.8 97
ST STATION 2 +00 LINE "B" -1.0
1 SANITARY SEWER TRENCH
12- S 144.6 12.4122.0 84
ST STATION 1 +00 LINE "B" -1.4
2 SANITARY SEWER TRENCH
12- S 144.6 9.2 119.6 ?S�
ST STATION 3 +00 LINE "A" -1.0
3 SANITARY SEWER TRENCH
12 S 144.6 9.6 123.0 SE
cc: CITY OF TIGARD
ALPHA ENGINEERING INC
•
CARLSON TESTING INC.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office.
Ua /La /aa Y/t.11 UI:4O rAA DU." is /U a14r I.AKLJU1N Ito ll lvl, wJUua
Construction Inspection & Related Tests
Carlson Test , Inc.
SUMMARY REPORT OF
P.O. Box 23814
IN -PLACE DENSITY TESTS Tigard, Oregon 97281
Phone (503) 684-3460
JOB NO. 97 -G135 ' FAX (503) 684 -0954
Jul 16, 1998
Client BEACON HOMES
Project DAKOTA MEADOWS
SW NORTH DAKOTA & SW 105TH PL - TIGARD
DATE OF TEST wax x ADJ. Rao Rao DRY - RtLATrvE
TEST LOCATION � ( Frj DRYDEN51Y COARSE ?AV MO TURF DEN ou TEST NO pe/n PARr�clES { %? q/ 1 (x)
ST LOT 19 LATERAL LINE "A" -1.0
4 SANITARY SEWER TRENCH
12- 8 144.6 118.5 S2
ST LOT 13 LATERAL LINE "A" -1.0
5 SANITARY SEWER TRENCH
12- 8 • 144.6 13.9119.5 5
ST STATION 2 +00 LINE "A" -3.0
6 SANITARY SEWER TRENCH
12- E4 144.6 15.2120.3 83
ST STATION 1 +75 LINE "A" -1.0
7 SANITARY SEWER TRENCH
12- E\ 144.6 12.9117.4 81
ST LOT 9 LATERAL LINE "A" -1.0
8 SANITARY SEWER TRENCH
12- 8 144.6 11.5121.5 84
ST STATION 1 +25 LINE "A" -4.0
9 SANITARY SEWER TRENCH
12- `3 _ 144.4 14.6123.6 86
ST LATERAL LOT 3 LINE "A" -1.0
10 SANITARY SEWER TRENCH
12- 8, 144.6 12.4120.3 8.2 ,
ST STATION 0 +10 ON NORTH DAKOTA -1.0
11 SANITARY SEWER TRENCH
12- 8 144.6 14.0125.4 871
ST LOT 6 LATERAL ON NORTH DAKOTA -1.0
12 SANITARY SEWER TRENCH
12- 8 144.6 12.7119.1 82
cc: CITY OF TIGARD
ALPHA ENGINEERING INC
CARLSON TESTING INC.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office.