T UALATIN VALLEY FIRE & RESCUE
FIRE PREVENTION
/ 4755 S.W. Griffith Drive . P.O. Box 4755 . Beaverton, OR 97076 . (503) 526 -2469 . FAX 526 -2538
s -- & RE
October 13, 1998
Bob Poskin, Plans Examiner
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223
re: Gensco Fire Access
Bob,
This correspondence is to document our conversation of October 9, 1998
regarding the Gensco building located at 7650 SW Tech Center Dr., Tigard.
Due to the building's location on the property and the proximity of the railroad
right -of -way, it is impractical to provide fire department access to within 150 feet
of the rear of the building.
Because the building is completely protected with an approved automatic fire
sprinkler system and is separated into areas of less than 12,000 square feet by
approved area separation walls, the Fire District will waive the requirement for
fire department access as allowed in Uniform Fire Code, Section 902.2.1,
Exception (1).
Please contact me at (503) 526 -2661 with any additional questions.
Sincerely,
e✓. 77 777, YYl--
Eric T. McMullen
Deputy Fire Marshal
cc: Cleve Joiner, Assistant Fire Marshal
File
"Working" Smoke Detectors Save Lives
r
, 1 ,
t .
,_411
August 7, 1998
CITY OF TIGAR
• OREGON
Gensco
Attn: Robert Schram
7550 SW Tech Center #230 j Tigard, OR 97223 G
RE: Gensco Building Plan Review ( �"
7550 SW Tech Center Dr. #230 6'
PC #: 8 -04c BUP #: 98 -0305
Your plans have been reviewed for compliance with applicable codes. The following items require
your attention.
STORAGE RACK l
1) 1. Access roadways are required within 150 feet of all portions . exterior walls. UFC 8102.5.1,
provide details.
r"► )12. Provide details showing compliance with OF :102.5.2 (access doors).
, \ 3. Provide details showing complian - with UFC 8102.6 (smoke and heat control)and TVFR
Table 81 -B.
4. Provide details showi = compliance with UFC 8102.7 and TVFD Table 81 -B (curtain boards).
5. Provide detail howing compliance with UFC 8102.8 (hose stations and hose connections).
6. Provi• - 1 -hour fire proofing on all columns located in flue spaces, NFPA 3- 2.3(a).
ACCESSIBILITY -
&1 . ) Provide a barrier improvement plan on the enclosed form, showing how you will expend
l �®� $3250, the 25% prescribed by OSSC 447.221.
ileA I FIRE AND LIFE SAFETY n' I ,
1. Your required exits (2), are not placed a distance apart to not less than one -half of the
maximum overall diagonal dimension of the building area to be served in a straight line
between exits. OSSC, 1003.3.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Gensco Building Plan Review
PC #: 8 -04c BUP #: 98 -0305
Page #2
I ENVIRONMENTAL AIR
Provide details on how you will comply with OSSC, Chapter 12.
I MECHANICAUSPRINKLER SYSTEM
A separate mechanical and sprinkler permit and plans shall be required.
Please submit two copies of revised submittal documents and a letter indicating your response to the
above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
R ert Poskin, CBO
SENIOR PLANS EXAMINER
•
tP gib - 6 50S
SUBJECT: ACCESSIBILITY
BARRIER REMOVAL IMPROVEMENT PLAN
REQUIREMENT: OREGON REVISED STATUTE (ORS) 447.241.
(1) Every project for renovation, alteration or modification to affected buildings and related
facilities shall be made to insure that the path of travel to the altered area and the
restroom, telephones and drinking fountains are readily accessible to individuals with
disabilities, unless such alterations are disproportionate to the overall alterations in
terms of cost and scope.
(2) Alterations made to the path of travel to an altered area may be deemed
disproportionate to the overall alteration when the cost exceeds twenty-five percent
• (25 %).
VALUATION of all renovation, alteration or modification being done
excluding painting, wallpapering. [1] $ 1
multiply: 25% Barrier removal requirement. .25
BUDGET FOR BARRIER REMOVAL [2] $ 3
In choosing which accessible elements to provide under this section, priority shall be given to
those elements that will provide the greatest access. Elements shall be provided in the following
order:
(a) Parking $ •
(b) An accessible entrance: $
(c) An accessible route to the altered area: $
(d) At least one accessible restroom for
each sex or a single unisex restroom: $
(e) Accessible telephones: $
(f) Accessible drinking fountains: and $
(g) When possible, additional accessible
elements such as storage and alarms: $
TOTAL: Shall equal line 2 of value computation $
Mertetpaccomelea