Permit liPlt ; : CITY OF TIGARD ELECTRICAL PERMIT
1_,.. q PERMIT #: ELC2007-00733
COMMUNITY DEVELOPMENT DATE ISSUED: 10/29/2007
TIGARD 13125 SW Hall Blvd., Tigard, OR 97223 503.639.4171 PARCEL: 1S135C6 00800
SITE ADDRESS: 07787 SW TECH CENTER DR ZONING: UNK
SUBDIVISION: BURLINGTON NORTHERN RR LOT : JURISDICTION: TIG
PROJECT: PORTLAND & WESTERN RAILROAD
Project Description: 400 amp, 3 phase, 120/208 outdoor service at railroad tracks.
RESIDENTIAL UNIT TEMP SRVC /FEEDERS MISCELLANEOUS
1000 SF OR LESS: 0 - 200 amp: PUMP /IRRIGATION:
EACH ADD'L 500SF: 201 - 400 amp: SIGN /OUT LINE LTG:
LIMITED ENERGY: 401 - 600 amp: SIGNAL/PANEL:
MANF HM/ SVC/ FDR: 601 +amps - 1000 volts: MINOR LABEL (10):
SERVICE /FEEDER BRANCH CIRCUITS ADD'L INSPECTIONS
0 - 200 amp: 1 W /SERVICE OR FEEDER: 3 PER INSPECTION:
201 - 400 amp: 1 1st W/O SRVC OR FDR: PER HOUR:
401 - 600 amp: EA ADD'L BRNCH CIRC: • IN PLANT:
601 - 1000 amp: PLAN REVIEW SECTION
1000+ amp /volt: > =4 RES UNITS: > 600 VOLT NOMINAL:
Reconnect only: SVC /FDR >= 225 AMPS: CLASS AREA /SPEC OCC:
Owner: Contractor:
PORTLAND & WESTERN RAILROAD ENERTECH ELECTRIC INC
650 HAWTHORNE SE 7925 NE ST JOHNS RD
SALEM, OR 97301 -5893 • VANCOUVER, WA 98665
Phone: 503 - 365 -7717 Contact #: PRI 360 - 574 -6202
FAX 360- 574 -6185
FEES
Description Date Amount Reg #: ELE 37 -552C
[ELPRMT] ELC Permit 10/29/200' $207.10 LIC 82092
[TAX] 8% State Surcharge 10/29/200' $16.57 SUP 3763S
Total $223.67 REQUIRED ITEMS AND REPORTS
This Permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other applicable laws. -
All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is
suspend. : or .. han 18' •ays. ATTENTION: Oregon law requires you to follow rules adopted • - = .Oregon Utility Notification Center.
Thos= ules are set fo . OA 9 .- 001 -0010 through OAR 952 -001 -0100. You may obtai these rules or direct questions to OUNC at
503. 46.6699 or 1.800 • . 23 '
Issu:d By: , . 4� i A t Permittee Signatu _ �ti' / D (L5L-_____,
OWNER INSTALLATION ONLY
The installation is being made on property I own which is not intended for sale, lease, or rent.
OWNER'S SIGNATURE: DATE:
C ONTRACTOR INSTALLATION ONLY
SIGNATURE OF SUPR. ELEC'N: C _— ,;piJ / � i�_� DATE:
/ .
LICENSE NO:
•
Call 503.639.4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
•
Oct 29 07 09:59a Ericksonlenertech 3605746185 p.1
so
' 11ectrical Permit Application FOR OFFICE USE ONLY
IN City of Tigard Received /v 29 07 )e P . 'I No.: �,c.� ?— Od 733
13125 SW W Hall Blvd., Tigard, OR 97223 Plan Review
C Phone: 503.639.4171 Fax: 503.598.1960 Date/By Ot er Permit:
TIGARD Inspection Line: 503.639.4175 Date Ready/By: 1 • H See Page 2 for
Internet: www.tigard- or.gov Notilled 1( Supplemental Information
TYPE OF WORK P i AN REVIEW
® New construction ❑ Addition/alteration/replacement Please check a0 that apply (su emit sets of plans wlitcros checked below):
❑ Service or feeder 400 am or more ❑ Building over three stones.
❑ Demolition ❑ Other: where the available fault rrent 0 Marinas and boatyards.
CATEGORY OF CONSTRUCTION exceeds 10,000 amps at 15 A volts or ❑ Floating buildings.
I� to ground, or exceeds 4,000 ❑ Commercial -use agricultural
❑ 1 - and 2- family dwelling ® CotnmerciaUindtstrial ❑Accessory building amps for all other installeti ^. buildings.
1 ❑ Multi- family ❑ Master builder ❑ Other. ❑ Fire pump. ❑ Installation of 75 KVA or
vi ❑ Emergency system. larger separately derived system.
JOB SITE INFORMATION AND LOCATION ❑ Addition of new motor loa•' of ❑ "A ", "E ", "1 - 2", "1 - ",
'1 elf- or more. occupancy.
Job no.: 7010 Job site address:77g o� ¢C({- '(�/Ji � .
' ❑ Six or more residential uni ❑ Recreational vehicle parka.
City /State /ZIP: TIGARD, OREGON ❑ Health -care facilities. ❑ Supply voltage for morn than
❑ Hazardous locations. 600 volts nominal.
4 Suite/bldg. /apt. no.: Project name: P &W RAILROAD ❑ Service or feeder 600 am.: or more.
F :E SCHEDULE
Cross street/directions to job site: 72 AVE OFF OF IIW 217 Description 1 city. I Fee I Total I '
"N, DEAd END AT TECH CENTER DRIVE AND 72 AVE, BETWEEN RAILROAD New residential single o multi - family dwelling unit.
C � _ rn a r-ve Includes attached garag
` l Subdivision: Lot no.: 1,000 sq. fl or less 145.15 4
•
Ea. add
500 sq. R. or po . on 33.40 1
Tax map/parcel no.: Limited energy, residentia
(
DESCRIPTION OF WORK sq. ) 75.00 2
2
(with above ft.
400 AMP,3 PHASE, 120/208 OUTDOOR SERVICE AT RAILROAD TRACKS Limited energy, muRi - fa ily 75 00
residential (with above .. ft)
Services or feeders • . I ation, alteration, and/or relocation
200 amps or less 1 80.30 80.30 2
, S ®PROPERTY OWNER I ❑ TENANT 201 amps to 400 amps 1 106.85 106.85 2
Name: PORTLAND WESTERN RAILROAD 401 amps to 600 amps 160.60 2
601 amps to 1,000 amps 240.60 2
Address: 650 HAWTHORNS S E. Over 1,000 amps or volts 454.65 2
City/State/ZIP: SALEM, OREGON 97 3v! - 58 9 3 Temporary services or f • ' ers installation, alteration, and/or
relocation
Phone: (503)365 -7717 Fax: ( ) 200 amps or less 66.85 1
Owner This i nstallation is being made on property that I own which is not 201 amps to 400 amps 100.30 2
int ended for saleinstallation: , l ease T , rent, or exchange, according to ORS 447, 449, 670 and 701. 401 amps to 599 amps 133.75 2
Branch circuits - new, a teration, or extension, per panel
Owner signature: Date: A Fee for branch circuits •ith
❑APPLICANT I ❑CONTACT PERSON above service or fee • fee, 3 6.65 19.95 2
each branch circuit
Business name: B. Fee for branch circuits
Contact name: without service or feed fee, 46.85 2
first branch circuit
Address: Each add' I branch circuit 6.65 2
Miscellaneous (service . feeder not included)
City/State/ZIP: manufactured or m• • tar
dwelling, service and/or eder 90.90 2
Phone: ( ) Fax:: ( ) Reconnect only 66.85 2
E - mail: Pump or irrigation circle 53.40 2
Q CONTRACTOR Sign or outline lighting 53.40 2
Business name: ENERTECH ELECTRIC INC Signal circuit(s) or limi
energy panel, alteration, •
{■ Address: '7925 NE ST. JOHNS RD extension. Describe: Page 2 2
City /State/ZIP: VANCOUVER, WASHINGTON 98665 Each additional arts • • ••• on over allowable in any of the above
A Per inspection 62.50
Phone: (360) 574 Fax: (360) 574 - 6185 /0 %! ` 0 Investigation per hour (1 min) 62.50
CCB Lic.: 82092 7/ ( � 1 Electrical Lic.: 37 - 552C Suprv. Lic.: 3763S Industrial plant per hour 73.75
Vila Si ELECT' CAL PERMIT FEES
uprv. Electrician signature, required: Subtotal: 207.10
Print name: MARK ERICKSON Date: 10/29/07 Plan revie (25 °. /0 of permit fee):
State aura . :e (8% of permit fee): 16.57
Authorized signature: :" " � ..// „ .,';`...•. f j / • TAL PERMIT FEE: 223.67
r . i.
Date 10/29/07 This permit application e pires if a permit is not obtained within 180
Print name: MARK ERICKSON
days after it us been accepted as complete.
CITY OF TIGARD
BUILDING DIVISION PERMIT #: ELC2007 00733
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 10/29/2007
Phone: (503) 639 -4171 c - l�
Inspection Requests (24 Hrs.): (503) 639 - 4175 ��a
P_ r!
INSPECTION WORKSHEET FOR DATE: 11/2/2007 TIME: 7:01AM PAGE: 55
SITE ADDRESS: 07787 SW TECH CENTER DR CLASS OF WORK:
SUBDIVISION: F3URLINGTON NORTHERN RR LOT #: TYPE OF USE:
PROJECT NAME: PORTLAND & WESTERN RAILROAD
DESCRIPTION: 400 amp, 3 phase, 1201208 outdoor service at raihoad tracks.
OWNER: PORTLAND & WESTERN RAILROAD, PHONE #: 503-3657717
CONTRACTOR: ENERTECH ELECTRIC INC PHONE #: 360 -574 -6202
Inspection Request Scheduled For: Date: 11/2/2Q47 Pour Time:
Code # Inspection Description Confirm # Contact # Message
116 Electiical service 058896-01 360 -574 -6202 N
1
CIA c��
Corrections /Comma ts/Instructions:
N iv
PASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: . Yv CS8 LG Date: I1'iO7 - Phone #: (503) 718- 2.ljhl)o
Oct 31 07 04:47p Erickson /enertech 3605746185 p. 2
OCT-31 -200T 03:42PM FROM- 1 - o14 P.UUI /DUI I' U
Panama Gene company
MEMORANDUM
10/31/07
TO: CONTACT: MARK W ENERTECH
PHONE: 503- 849 -6878
CUSTOMER NAME: PORTLAND 8 WESTERN RAIL ROAD
ADDRESS: 7787 SW TECH CENTER DR, TIGARD
FROM: ENGR/SDC: MILD STARR
PHONE 503- 570 -4414
SUBJECT: SINGLE -PHASE SECONDARY LINE -UNE FAULT CURRENT (RMSI
TRANSFORMER DATA
XFMR Impedance ( %): 1.40 % •
TRANSFORMER SIZE: 50 KVA
Secondary VOLTAGE (L to L): 240 v
VAULT —> VAULT j or Pole —> Polk SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Runs) of: [ _
Secondary WIRE Rosistance R: . 0.0773 Ohms/1000'
• Secondary WIRE Reactance X: 0.0258 Ohms/1000'
. I •
VAULT ( or Pole) —> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 110 Feet WIRE SIZE
Number of Service RUNS: 2 Runs) of: 4/0 TX UG
Service WIRE Resistance R: 0.1000 Ohms/1000'
Service WIRE Reactance X 0.0280 Ohms /1000'
FAULT CURRENT: _ 8,711 Amps
for SHORT GRCUrT CURRENT)
(or INTERRUPTING CURRENT)
•
Based on a panel size of: 400 AMP Amps
To Print This Page: ''Ctrl M" and choose 'Print.1 -Phase beta° •
T. ..la • • wn • ammdaan Cerwewo to Excel - mom • • • • 06ST • . 1162000
•
CITY OF TIGARD
BUILDING DIVISION PERMIT #: CLty2007 0;1 "733
13125 SW Hall Blvd., Tigard, OR 97223 D ATE ISSUED: 10/29/20:)7
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175 .n' P1 _
INSPECTION WORKSHEET FOR DATE: 10/31/2007 TIME: 7:00AM PAGE: 74
SITE ADDRESS: 07787 SW TECH CENTER DR CLASS OF WORK:
SUBDIVISION: BURLINGTON NORTHERN RR LOT #: TYPE OF USE:
PROJECT NAME: PORTLAND & WESTERN RAILROAD
DESCRIPTION: 4A0 amp. 3 phase, 120/2.08 outdoor service at railroad tracks.
OWNER: PORTLAND & WESTERN RAILROAD, PHONE #: 603-365-7717
CONTRACTOR: ENERTECH ELECTRIC INC PHONE #: 361157 -6202
Inspection Request Scheduled For: Date: 10/31/2007 Pour Time:
Code # Inspection Description •. • 11 " Contact # Message
115 Eloctiicul service 058715`01 360 -574 -6202 N
Corrections /Comments /Instructions:
d PNOViZt E4V\rp4 N 1 RA Cab F6& A V to 1,t1/48 (..--
,t 8(.'
i f a ll CIO a( V - b R Z V k A I G INA N i AN v M
p Pi-" viq L 1 PacttsrR0 Kr c Wire Vxonr\
❑ PASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
X FAIL X CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: ( Y Q Date: 0 30IO 1 Phone #: (503) 718 - 1-41 h