Loading...
Correspondence , OFFICE COPY iA 1 • October 29, 2004 t =' . �' t � I I CITY OF TIGARD Jet Heating OREGON PO Box 7362 t. Salem, OR 97303 RE: REPLACEMENT OF EXISTING AC UNITS Project Information Building Permit: MEC2004 -00700 Construction Type: VN Tenant Name: Summerfield Occupancy Type: A3 Address: 11205 Summerfield Drive Occupant Load: = The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The submitted plans are approved subject to the following. 1. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 2. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. 304.10 OMSC 3. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 4. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 5. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Respect 1 , , .n Se • • • ' lans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 ■