Correspondence ,
OFFICE COPY
iA 1
•
October 29, 2004 t =' . �' t � I I
CITY OF TIGARD
Jet Heating OREGON
PO Box 7362
t. Salem, OR 97303
RE: REPLACEMENT OF EXISTING AC UNITS
Project Information
Building Permit: MEC2004 -00700 Construction Type: VN
Tenant Name: Summerfield Occupancy Type: A3
Address: 11205 Summerfield Drive Occupant Load: =
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
1. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
2. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
3. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
4. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
5. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Respect 1 , ,
.n
Se • • • ' lans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
■