Correspondence 1 ---4644 # \ lV ii�l March 1, 2003 CITY OF TIGARD OREGON Sara Hylland American Security 5411 SW Mcloughlin Boulevard Portland, OR 97202 RE: FIRE ALARM SYSTEM Project Information Building Permit: BUP2004- 00042. Construction Type: VN Tenant Name: Shady Lane Occupancy Type: B Address: 9780 SW Shady Lane Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the main building entrance is acceptable. 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief. All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, TVFR99 -01 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Visuals (Section 1109.14 OSSC) 5. Visual signal appliances shall be provided in the building in each of the following areas: • Restrooms and any other general use area (e.g., meeting rooms) • Hallways • Lobbies • Common use areas. 6. Visual alarms shall be located not less than 80 inches and not more than 96 inches above the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6 inches below the ceiling. 7. Visual alarms shall have a minimum candela rating of 75 candelas. 8. No place in a room shall be more than 50 feet from a visual signal. 9. No place in a common corridors or hallways shall be more than 50 feet from a visual signal. 10. In large rooms exceeding 100 feet across and without obstructions 6 feet or more above the floor, devices may be placed around the perimeter spaced at a maximum of 100 feet apart. Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. 1109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful , rian Bl.. ck, Senior Plans Examiner FILLCOPY February 23, 2003 Sara Hylland American Security 5411 SW Mcloughlin Boulevard Portland, OR 97202 RE: FIRE ALARM SYSTEM Project Information Building Permit: BUP2004 -00042 Construction Type: ? Tenant Name: Shady Lane Occupancy Type: ? Address: 9780 SW Shady Lane Occupant Load: ? Area: • NA Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The following information is required prior to the approval of the submitted permit information. • Provide floor plans drawn to scale indicating the location of the proposed devices. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner