Correspondence September 2, 2004
Jeremy Hunt
Protemp Assoc., Inc.
9788 SE 17 Avenue
Portland, OR 97222
RE: HVAC MODIFICATIONS
Building Permit: MEC2004 -00578 Construction Type: VN
Tenant Name: Geodesign Occupancy Type: B
Address: 15575 SW Sequoia Pkwy, #100 Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
3. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
4. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
5. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
6. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC