Permit A
CITY OF TIGARD BUILDING PERMIT
PERMIT #: BUP2004 -00253
• DEVELOPMENT SERVICES DATE ISSUED: 7/16/2004
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 PARCEL: 2S112DD -01600
SITE ADDRESS: 15495 SW SEQUOIA PKWY 150
SUBDIVISION: PACIFIC CORP. CENTER ZONING: I -P
BLOCK: LOT: JURISDICTION: TIG
REISSUE: FLOOR AREAS EXTERIOR WALL CONSTRUCTION
CLASS OF WORK: ALT FIRST: sf N: S: E: W:
TYPE OF USE: COM SECOND: sf PROJECT OPENINGS?
TYPE OF CONST: 5N : sf N: S: E: W:
OCCUPANCY GRP: M TOTAL AREA: 0 sf ROOF CONST: FIRE RET?
OCCUPANCY LOAD: 46 BASEMENT: sf AREA SEP. RATED:
STOR: HT: ft GARAGE: sf OCCU SEP. RATED:
BSMT ?: MEZZ ?: REQD SETBACKS REQUIRED
FLOOR LOAD: psf LEFT: ft RGHT: ft FIR SPKL: Y SMOK DET:
DWELLING UNITS: FRNT: ft REAR: ft FIR ALRM : HNDICP ACC:
BEDRMS: BATHS: IMP SURFACE: PRO CORR: PARKING:
VALUE: $ 40,000.00
Remarks: TI, new walls to create retail sales.
Owner: Contractor:
PACIFIC REALTY ASSOCIATES SUMMIT CONSTRUCTION
15350 SW SEQUOIA PKWY #300 -WMI PO BOX 10345
PORTLAND, OR 97224 PORTLAND, OR 97210
Phone:
Phone: F -42 -3841
Reg #: E$i9703 00003246
FEES LIC REQU4
IRED INSPECTIONS
Description Date Amount Mechanical Permit Require
[BUILD] Permit Fee 7/16/2004 $395.80 Electrical Permit Required
TAX 8% State Surchar 7/16/2004 $31.66
Sprinkler Permit Required
[TAX] � Framing Insp
[BUPPLN] Pin Rv 6/1/2004 $257.27 Gyp Board Insp
[FLS] FLS Pin Rv 6/1/2004 $158.32 Susp Ceilng Insp
Total Final Inspection
$843.05
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes
and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is
not started within 180 days of issuance, or if work is suspended for more than 180 days. ATTENTION: Oregon law
requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set forth in OAR
952,9 &1 =0010 t OAR 952 - 001 -0100. You may obtain a copy of these rules or direct questions to OUNC by
c ling (503) 246- 6699`or 1- 800 - 332 - 44.
Is ued By: i ' , J /t / i
Permittee i! -
- Signature: k tw
Call 639 -4175 b p.m. for an inspection the next business day
•
Building Permit Application FOR OFFICE USE ONLY
City of Tigard
Date/B ved
, , I 7 Permit No.: /��
13125 SW Hall Blvd., Tigard, OR 97223 Plan Review/ / 031 �s�
Phone: 503.639.4171 Fax: 503.598.1960 i�l I Date /By: ` Other Permit:
Inspection Line: 503.639.4175 Date Ready /By: 1u 0 PI See Attached Checklist for
Internet: www.ci.tigard.or.us Notified/Method: --7 1 , Supplemental Information
TYPE OF WORK REQUIRED DATA: 1- AND 2- FAMILY DWELLING
❑ Ncw construction ❑ Demolition Permit fees* arc based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
Addition/alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
El I- and 2-family dwelling Valuation: $
y g ❑C ommercial /industrial
CI Accessory building ❑ Multi- family Number of bedrooms:
GI Master builder Other: �.6,) L Number of bathrooms:
JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site address: 15 4q5- ! (i seeRUo IA 16 'K 1*. - .' I$0 New dwelling arca: square feet
City /State /ZIP: 1.1 q ,cp D 1 cg q.224 Garage /carport area: square feet
Suite/bldg. /apt. no.: (5 0 Project name: J 1 ij.j trl izetg. Covered porch arca: square feet
Cross street/directions to job site: Deck arca: square feet
Other structure arca: square feet
REQUIRED DATA: COMMERCIAL - USE CHECKLIST
Subdivision: Lot no.: Permit fees* are based on the value of the work performed.
Tax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
DESCRIPTION OF WORK work indicated on this application.
Valuation: $ Ale O O O
Ikrt W-I- 4L ►J 6-TI t a*l I
Existing building area: square feet
Ncw building arca: square feet
® PROPERTY OWNER ❑ TENANT Number of stories:
Name: / ge4 •7' ' ASyD• . go / D » c 7[,ps7 Type of construction: VA/
Address: 16 6. O Sk) S8QtJQ //4 ��Q,/(e/r 4 Occupancy groups: Ai frm L
City /State /ZIP: Aar/A*0 i De ({? Z 24 (rWd»2D Existing:
Phone: (90 =j) 0/4 • -I i T ? Fax: ( ) New:
[`O APPLICANT ❑ CONTACT PERSON NOTICE
Business name: 4Rock /AI 4 jp p All contractors and subcontractors are required to be
Contact name: �DBL S/�jj� /419-du under with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 21 Af 3 19-1/g jurisdiction in which work is being performed. If the
/State /ZIP: T �y applicant is exempt from licensing, the following reasons
Cit
y 3p Rivapi�tn r /I, �7d iS / apply:
Phone: ( 7 ) 374,- ( r/ / I /� Fax:: (%757) 376 9( ' y
E- mail: . J$ ' I�(JL�I /7� l� Aq,44 T/2GH , GoM
CONTRACTOR
Business name: 71°5 --u.i- 4t41. -r CZN BUILDING PERMIT FEES*
Address: / 3 /Y �'C 5�
5 � � Please refer to fee schedule.
City /State /ZIP: + ( Q . 02- Fees due upon application
Phone: ( ) Fax:( )
Amount received
CCB lie.: (j1 (� 3 l
t�..f41� ? li Date received:
Authorized signature: 1 This permit application expires if a permit is not obtained
within 180 days after it has been accepted as complete.
Print name: 427,, h_" it//Ati Date: 6 * Fee methodology set by Tri -County Building Industry
CITY OF TIGARD 24 -Hour
BUILDING Inspection LIn 503) 639 -4175
MST /
INSPECTION DIVISION • Burliness Line 03) 639 -4171 BUP ax y- /7'� 7
Received / Date Requested — 2 g AM PM BUP d- --- 3
Location l ,5 '7 7 ---J Suite `S MEC
Contact Person Ph ( ) (_;°• D YC Z PLM
Contractor Ph ( _ ) SWR
BUILDING Tenant/Owner ✓ ELC
Footing
Foundation Access: ELC
Ftg Drain ELR
Crawl Drain
Slab Inspection Notes: SIT
Post & Beam
Shear Anchors
Ext Sheath/Shear
Int Sheath/Shear
Framing
Insulation
Drywall Nailing
Firewall
Fire Sprinkler
Fire Alarm 06:11.
Susp'd Ceiling )
Roo =;
PASS PART FAIL
�P_ = ING agI
Post & Beam
Under Slab Utd /
Rough -In wjaEWater Service _
Sanitary Sewer
Rain Drains
Catch Basin / Manhole
Storm Drain
Shower Pan
Other:
Final
PASS PART FAIL
MECHANICAL
Post & Beam
Rough -In
Gas Line
Smoke Dampers
Final
PASS PART FAIL
ELECTRICAL
Service
Rough -In
UG/Slab
Low Voltage
Fire Alarm
Final Reinspection fee of $ required before next inspection. Pay at City Hall, 13125 SW Hall Blvd.
PASS PART FAIL
SITE ❑ Please call for reinspection RE: 0 Unable to inspect — no access
Fire Supply Line
ADA
Approach/Sidewalk Date _ Inspector Ext
Other:
Final DO NOT REMOVE this Inspection record from the job site.
PASS PART FAIL
1 `S � � OFFICE COPY
y
Oregon Non- Residential Energy Code
INSTRUCTIONS - LIGHTING EXCEL FORMS Q 14 Pam, - o ,Z53
This Excel workbook contains all you need to demonstrate compliance with the lighting requirements of the Oregon Non - Residential Energy
Code PRESCRIPTIVE PATH. The forms provide are based on those found in the 2000 COMPLIANCE GUIDE or the 2000 COMPLIANCE MANUAL.
Limitations
- This spreadsheet is limited to 28 predefined fixtures and 9 user defined fixture types. If your building has more than 37 fixtures
in your building, you can try break it two applications (by floor or general area).
- ` V ' ED
Do NOT add additional worksheets. A lot of "under the covers" lookup tables and will not be connected to new she `�+
General JUN 2 4 2004
- Use the COMPLIANCE GUIDE /MANUAL side by side.with this workbook to help you complete these forms. CY �F TIGARD
- You can only enter information in white areas. I all other areas of the worksheets are protected
- Always submit your application with a cover sheet - FORM 2A BUITLDING DIVISION
- Sign and date the form once it is printed.
- Use pull -down menus to select from standardized list of materials.
- The spreadsheet is best viewed on 17" monitor or larger.
- Luminaire IDs entered on Form 5c, Worksheets 5a, and 5b should be exactly the same as in the Schedule of Fixtures on electrical drawing.
Printing
- Use the "Report Manager" under the 'View" menu to quickly print the groups of worksheets.
- Print setup is intended for a laser printer set at 75% scaling factor - you may need to adjust this to suit your printer.
- Sign and date the form once it is printed.
Form 2a
- Use check boxes to indicate the forms and worksheet(s) you use.
Form 5a
- Check appropriate options and fill in information necessary into white boxes.
Form 5b
- Group M occupancy has been condensed into one line. The spreadsheet automatically calculates the budget.
- Use the pull down menus to select the appropriate occupancy.
Form 5c
- The calculation approach is slightly modified - you may enter up to 4 different fixture types per room.
Worksheet 5a
- Worksheet 5a has two different parts - 28 lines allow input of luminaires chosen from the spreadsheet database;
remaining 9 lines allow input of user defined luminaires.
- For more than 37 different types of luminaires you will need to do complete the forms manually or break your building into two applications.
Worksheet sb
- Use the additional 3 pages to list all the fixtures used in your building - totals are combined on bottom of 1st page.
Worksheet 5c
- Use pull -down menus of luminaire types specified in Worksheet 5a.
Visit the Office of Energy's website for the latest energy code information at WWW.ENERGY.STATE.OR.US
INSTRUCTIONS :0 25° \ 5 /f5r2C04
r ,
Form 2a Project Name: VERIZON WIRELESS Page:
SUMMARY
Project 1. Project VERIZON WIRELESS
`. 2. Project Address 15495 SW SEQUOIA PARKWAY
3. City/Town PORTLAND, OREGON 5. County MULTNOMAH
4. Building, Gross Area (ft 2,746 6. No. of floors 1
Chapter Type ID Description Attached
Attached Building Envelope Form 3a Building Envelope - General ❑
Forms and 3b Prescriptive Path - Zone 1 ❑
Worksheets 3c Prescriptive Path - Zone 2 ❑
check boxes to
indicate attached 3d Simplified Trade -off (use CodeComp software) ❑
forms and Worksheet 3a Wall U- factors ❑
worksheets
3b Roof U- factors ❑
3c Floor U- factors ❑
Systems Form 4a Systems - General 0
4b Complex Systems ❑
Worksheet 4a Unitary Air Conditioners - Air Cooled ❑
4b Unitary Air Conditioners - Water Cooled ❑
4c Unitary Heat Pump - Air Cooled ❑
4d Unitary Heat Pump - Water Cooled ❑
4e Unitary AC & Heat Pump - Evaporatively Cooled ❑
4f Packaged Terminal Air Conditioner - Air Cooled 0
4g Packaged Terminal Heat Pump - Air Cooled ❑
4h Water Chilling Packages - Water and Air Cooled ❑
4i Boiler - Gas -fired & Oil -fired ❑
4j Furnaces and Unit Heaters - Gas and Oil -fired 0
Lighting Form 5a Lighting - General 0
5b Interior Lighting Power - Occupancy Method O
5c Interior Lighting Power - Space -by -Space Method ❑
Worksheet 5a Interior Lighting Power 0
5b Lighting Schedule 0
5c Interior Control Credits ❑
Applicant 7. Name KENNETH A. FULLER 10. Telephone 973 - 692 -0222
8. Company NICHOLAS J. TRICARICO, ARCHITECT 11. Date 6/15/2004
9. Signature
Attached No of Pages Description of Document
Documen-
tation
s
. •
1J
Form 2a 40285 VERIZON.xis . . 6/15/2004
Form 5a Project Name: VERIZON WIRELESS Page:
LIGHTING - GENERAL
1. Interior Exceptions (Section 1316.1)
Exceptions ❑ No Interior Lighting. The building plans and specifications do not call for new or
Discussion of qualifying altered interior lighting. Skip to item 4, Exterior building Lighting - General, below.
exceptions on page 5-7. ❑ Exception. The building or part of the building qualifies for an exception from
code lighting requirements. The applicable code exception is Section: 1
Exception(s)
2. Local Shut - off controls (Section 1316.1.2.1,1)
Complies. At least one local shut -off lighting control for every 2,000 square feet of
Exceptions lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
Discussion of qualifying This control(s) is detailed in the building plans on drawing number: I
exceptions on page 5 -8. ❑ Exception. The building or part of the building qualifies for an exception. The
applicable code code exception is Section 1316.1.2.1.1, Exception: I
Portions of the building that qualify:
3. Office Controls (Section 1316.1.2.1,2)
Exceptions ❑ Not Applicable. Contiguous office floor area is not over 2,000 square feet.
Discussion of qualifying ra Complies. All interior lighting systems are equipped with a separate automatic
exceptions on page 5 -9. control to shut off the lighting and local override switching. These control(s) are
detailed in the building plans on drawing number. IE -2
❑ Exception. The building or part of the building qualifies for an exception. The
applicable code exception is Section 1316.1.2.1,2, Exception: I
Portions of the building that qualify:
Definition 4. Exterior Building Lighting - General
El No Exterior Building Lighting. Skip the rest of this form.
EXTERIOR
CI Complies. Complete items 5 and 6 below.
BUILDING LIGHTING
is lighting directed to
illuminate the exterior 5. Exterior Building Lighting Controls (Section 1316.1.2.2)
of the building and ❑ Complies. The building plans require that all exterior building lighting is equipped
adjacent walkways
and loading areas with automatic controls described in Sec. 1316.1.2.2. These controls are detailed
with or without
canopies. in the building plans on drawing number.
❑ Exception. The exterior building lighting is intended for 24 -hour continuous use.
6. Exterior Building Lighting Power (Section 1316.2.2)
❑ Complies. The plans do not call for incandescent lamps greater than 10 Watts
for use in exterior building lighting.
❑ Exception. The building plans indicate luminaires with incandescent lamps greater
than 10 Watts, but they are 5 percent or less of the total installed exterior lamps.
Total number of exterior lights:
Total number of exterior incandescent lights:
•
•
Ferm 5a 40285_VERIZON xis an 5/2004
Form 5b Project Name: VERIZON WIRELESS Page:
INTERIOR LIGHTING POWER - Occupancy Method
Lighting (a) (b) (c) (d) (e) (f)
budget Max Power Lighting
g Group Occupancy Use Ceiling Floor Area Density Power Budget
Height (sq ft) (W /sq ft) ( )
Retail or Retail lighting, department stores, drug
Merchandise M stores, markets, etc. Any 2,746 varies 8,665
(Group M only)
IF under 15ft n/a
IA I ■
Other Occupancy/ -
Use Types
1 15ft or more n/a
See page 5 -11 for — under 15ft n/a
instructions I B w yr
15ft or more n/a -
I e I - under 15ft • n/a -
15ft or more n/a -
F I under 15ft n/a - w Iv
- 15ft or more n/a -
I - w
under 15ft n/a
I ,15ft or more n/a -
I I_
_- under 15ft n/a
15ft or more n/a -
I R I .r - under 15ft n/a -
15ft or more n/a -
1. Total Interior Lighting Power Budget (Watts) for buildin 8,665
Track 2. Total length of track lighting (ft) 66
Lighting 3. Line 2 multiplied by 37.5 Watts /ft 2,456
Power 4. Total amperage of circuit breaker(s) serving track lighting (amps) 60
5. Voltage of circuit breaker serving track lighting (volts) 120
6. Wattage of circuit breaker serving track lighting (line 4 x line 5) 7,200
7. Track Lighting Power (lesser value of line 3 or line 6) 2,456
i
Building's 8. Track Lighting Power (line 7) 2,456
Lighting 9. Total Interior Lighting Power from Worksheet 5b + 1,804
Power 10. Total Control Credit from Worksheet 5c -
11 Total Adjusted Lighting Power = - 4,260
(line 8 + line 9 - line 10) _
12. Does design meet budget? Line 11 must be no greater than line 1. YES
Form 5b 40285_VERIZON.xls 6/15/2004
•
Form 5c Project Name: VERIZON WIRELESS Page:
INTERIOR LIGHTING POWER - SPACE BY SPACE METHOD
Maximum Number of Luminaires Luminaire D escription Areas Where Used
Deemed -to- (a) (b) (c) (d) (e) (f) (g) (h)
Satisfy Luminaire Minimum Luminaires Lamp B allast N/A
Approach Space T •es Pattern S•acin• or •er ft # T .e # T .e Space /Room # s
See p. 5 -13 for Grid 6'x'8' - 0.021 2 F32T8 1 M 0
instructions. Grid 6'x'8' 0.021 2 F40T12 1 E 0
Ballast types used Classrooms Grid 6'x'8' 0.016 3 F32T8 1 E 0
in this form:
Cont. rows 6' apart 0.042 1 F32T8 1 E 0
M = Energy Cont. rows 10' apart 0.025 2 F32T8 1 E 0
Efficient Magnetic .
E = Electronic Corridors Single row 6' o.c. N/A 1 F32T8 1 E 0
Single row 10' o.c. N/A 2 F32T8 1 E 0
Grid 6'x'8' 0.021 2 F32T8 1 M 0
Office(s) Private Grid 6'x'8' 0.021 2 F40T12 1 E 0
Grid 6'x'8' , 0.028 2 F32T8 1 E 0
Grid 6'x'8' 0.21 2 F32T8 1 E 0
Office(s) Open Grid 8'x10' 0.013 3 F32T8 1 • E 0
Grid 8'x10' 0.013 3 F40T12 1 E 0
Restrooms Grid 6'x'8' 0.021 1 F32T8 1 E or M 0
Grid 8'x10' 0.013 2 F32T8 1 E or M 0
Reception Grid 6'x'8' 0.021 2 F32T8 1 M 0
Storeroom(s) Grid 6'x'8' 0.021 1 F32T8 1 E or M 0
_ Grid 8'x10' 0.013 2 F32T8 1 E or M _ 0
Calculation
Approach (a) (b) (c) (d) (e) (f) (g) (h)
Identify and Max. Power Lum. Lamp Ballast Lum. # of Total Budget
d m noires in plans. Room ID Area (sq ft) Density (W /sq ft ID # Type # Type Power Lums. Load (b) x (c )
"Lum" is
abbreviation for 1.5 0 0
Luminaire
Space Typel Oassrooms I - PASSED
_1 1.5 0 0
Space Type Lobbies _ I v PASSED
2 0 0
Space Type: Conference rooms _ __H PASSED
•
V .(..� 1.5 0 0
areas -- PASSED
Space Type Reception ara I �
Form 5 c _O285_VERIZON .xis 6/15;2004
Worksheet 5a Project Name: VERIZON WIRELESS Page:
LIGHTING SCHEDULE
ID is the
identification (a) (b) (C (e)
,number or letter ID Type Lamp / Ballast Description Power (W)
used in your plans
or specification A -B 14ft Rapid Start TO V• 2 -F32T8 1 -ELECT I V 62
'Enter the C-D 14R Rapid Start TO V 2-F32r8 1 -ELECT V 62
number and type of F Incandescent V 75 Watts I V 75
lamps in the
luminaire. See Q Compact fluorescent 2D 2-CF528W /GR10q 1 -ELEC I V 56
Table 5b for typical
lamp codes NONE
Enter the 8 V Wattage
number and type of
ballasts in the V I Wattage
luminaire. For V V
fluorescent and I Wattage
high intensity V V Wattage
discharge lamps,
typical Wattage
abbreviations are: V V I Wattage
MAG STD for V'
V
Magnetic Standard I Wattage
Nr
V Wattage
MAG EE for g
V
Energy Efficient I I Wattage
Magnetic
V Wattage
ELECT for V'
Electronic Wattage
See Table 5b for I
CI MEM
V Wattage
other ballast V
abbreviations
CI V
CI EMI
I
V Milll
CI V
Mil
l- ILTEM
I» Wattage
User Defined Fixtures - Cut Sheets must be included to verify wattage of complete luminaire
ID Fixture and Lamp Description Power
•
"j. 4.
Worksheet 5a 40285 VERIZON.xls 6/15/2004
Worksheet 5b Project Name: VERIZON WIRELESS Page:
INTERIOR LIGHTING POWER Worksheet No 5b -1
• Enter the
quantity for every (a) (b) ( C) (d) (e) (f)
non - exempt Room or
Luminaire. Do not Quantity of Luminaire Lighting Power
consider track Sheet No. Room or Plans Designation Luminaire ID Luminaires* Power (Watts) (d) x (e)
lighting on this E -2 'RETAIL 1A-8 V 10 62 620
worksheet. Track
lighting is ! I ' V
0 0
accounted for on
Form 5b i I V 0 0
" Additional E -2 103 - SERVICE ! A-8 1 V 2 62 124
pages may be E -2 103 - SERVICE ' F I V 5 75 375
necessary if
building has more E -2 RETAIL I V 5 75 375
rooms than there
are lines in this E -2 WORK AREA 1 C-D 1 V 3 62 186
form
E -2 BREAK ROOM I C -D I V 2 62 124
C -D I V 62 0
1 I' 0 0
F I 75 0
0 0
' 0 0
0 0 _
0 0
0 0
0 0
V 0 0
0 0
I 0 0
I 0 _ 0
I 0 0
V 0 0
0 0 _
• V 0 0
V 0 0
I . 0 0
0 0
IF YOU DO NOT HAVE ENOUGH SPACE FOR ALL YOUR FIXTURES, USE ADDITIONAL PAGES RIGHT
Worksheet 5b -1 Total 1,804
Other Pages
List the additional Worksheet No. Description (optional) Worksheet Totals
worksheets necessary
to catalog all 5b -1 1,804
luminaires in building 5b -2
5b -3 _
(��'�;/ ;'Y. 5b-4 -
f T r ' � '�
\ Total Interior Lighting Power (of all worksheets) 1,804
Worksheet No 5b -1
Worksheet 5b 40285_VERIZON.xls 6; 15/2004
C
. Worksheet 5c Project Name: VERIZON WIRELESS Page:
INTERIOR CONTROL CREDITS if applicable
Definitions (a) (b) (c) (d) (e) (f)
LUMEN # of Luminaire Power
MAINTENANCE Luminaires Power Control Code Adjustment Control Credit
CONTROL Room or Plans Designation w /Controls (Watts) . (see below) Factor (b) x (c) x (e)
A device capable of RETAIL 62 55 I " 0.10 0.0
maintaining a preset
illumination level by 0 0 SS I V 0.10 0.0
automatically 0 0 SS I " 0.10 0.0
adjusting the
luminaire power. 103 - SERVICE 62 ss I v 0.10 0.0
DAYLIGHT 103 - SERVICE 75 ss V 0.10 0.0
SENSING CONTROL RETAIL 75 I V 0.10 0.0
A device that WORK AREA 62 ss I v 0.10 0.0
automatically adjusts
the power input to BREAK ROOM 62 ss . I 'v 0.10 0.0
electric lighting near
windows to maintain 0 62 ss v 0.10 0.0
desired workplace
illumination, taking 0 0 SS v 0.10 0.0
advantage of 0 75 ss v 0.10 0.0
daylight. Should be
capable of reducing 0 0 55 v 0.10 0.0
electric power to 50
percent or less of 0 0 SS V I 0.10 0.0
maximum power.
Three typical types of 0 0 55 1r 0.10 0.0
daylight sensing
• 0 0
controls are: SS V 0.10 0.0
0 0 -- S$ I V 0.10 0.0
Single- stepped •
control - 0 0 SS ■ 0.10 0.0
Automatically turns a
light on or off when 0 0 55 1r 0.10 0.0
daylight levels 0 0 55 v 0.10 0.0
exceed lighting
requirements 0 0 SS I V • 0.10 0.0
Multi- stepped 0 0 55 I V 0.10 0.0
dimming - Dims light
in discrete steps. For 0 0 55 v 0.10 0.0
example, dims light 0 0 0.10 0.0
by 25 percent, 50
percent, 75 percent 0 0 SS
0.10 0.0
and off.
0 0 SS V 0.10 0.0
Continuous dimming -
Dims light in a 0 0 SS V 0.10 0.0
continuous fashion 0 0 SS mr 0.10 0.0
0 0 ss v 0.10 0.0
1. Total Control Credits (Watts) 0
Power Automatic Lighting Control Control Code Power Adjustment Factor
Adjustment Single -Step On/Off Dimming SS 0.10
Factors Daylight Sensing Multiple Stepped Dimming MS 0.20
Continuous Dimming CD 0.30
Lumen Maintenance LM 0.10
r ,
V I
Worksheet 5c 40285_VERIZON.xls .. 6/15/2004