Plans /5yg5 Atap /yo 19 5- o Lec
- Global Project Valdes:
4ts SI I ,ENT Project Name:jAlG Standby Hours:I 24 1
K N I G I I" I' Project ID:110812 -05 1 Alarm Mins:1 5
Prepared By :1T & L Communications, Inc. I Derating Factor:) 1.2
SK -5208 Calculations Date:18/31/2005 I Voltage Drop Warning
Threshold % :1 10
Panel ID: 1SK -5208 I Model: SK5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps
Location: 'Bldg 1 I Volts: 24 VDC Max Panel Current: 6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop
Circuit Name Qty Standby Alarm & Type 1000 Ft. One -Way Ohms EOL p
SK5208 ' SK -5208 Main Control 1 0.140 0.160
NAC -CKT SK -5208 Prgm'd NAC's 2 0.000 0.080
ALM -RLY SK -5208 Pgm Alm Rly 0.000 0.000
SK -5217 SK -5217 Zone Expdr 0.000 0.000
SK -5235 SK -5235 LCD Remote 1 0.035 0.050
SK -5280 SK -5280 Display Mod 0.000 0.000
SK -5220 SK -5220 Dir Con Mod 0.000 0.000
SK -7181 SK -7181 Zn Cnvtr 0.000 0.000
IDC -1 Initiating Device Ckt 1 0.000 0.095
IDC -2 Initiating Device Ckt 2 0.000 0.095
IDC-3 Initiating Device Ckt 3 0.000 0.000
IDC-4 Initiating Device Ckt 4 0.000 0.000
IDC-5 Initiating Device Ckt 5 0.000 0.000
IDC-6 Initiating Device Ckt 6 0.000 0.000
IDC -7 Initiating Device Ckt 7 0.000 0.000
IDC -8 Initiating Device Ckt 8 0.000 0.000
IDC -9 Initiating Device Ckt 9 0.000 0.000
IDC -10 Initiating Device Ckt 10 0.000 0.000
IDC -11 Inactive, Add SK-5217 0.000 0.000
IDC -12 Inactive, Add SK -5217 0.000 0.000
IDC -13 Inactive, Add SK -5217 0.000 0.000
IDC-14 Inactive, Add SK- 5217 0.000 0.000
• IDC -15 Inactive, Add SK -5217 1 0.000 0.000
IDC -16 Inactive, Add SK-5217 0.000 0.000
IDC-17 Inactive, Add SK -5217 0.000 _ 0.000
IDC -18 Inactive, Add SK -5217 0.000 0.000
1DC -19 Inactive, Add SK 5217 0.000 0.000
IDC -20 inactive, Add SK-5217 0.000 0.000
IDC -21 Inactive, Add SK -5217 0.000 0.000
IDC -22 Inactive, Add SK -5217 0.000 0.000
IDC -23 inactive, Add SK -5217 0.000 0.000
IDC -24 inactive, Add SK -5217 0.000 0.000
IDC -25 Inactive, Add SK -5217 0.000 0.000
IDC -26 Inactive, Add SK -5217 0.000 0.000
IDC -27 Inactive, Add SK -5217 0.000 0.000
IDC -28 Inactive, Add SK -5217 0.000 0.000
IDC -29 Inactive, Add SK -5217 0.000 0.000
IDC 30 Inactive, Add SK -5217 0.000 0.000
NAC -1 Notification Appi Ckt 1 0.000 0.699 #14 Solid 2.52 40 0.20 23.86 0.59%
NAC -2 Notification Appl Ckt 2 0.000 0.733 #14 Solid 2.52 100 0.50 23.63 1.54%
NAC-3 inactive, Add NAG -CKT 0.000 0.000 #14 Solid 2.52 0 0.00 2400 0.00%
NAC-4 Inactive, Add NAC -CKT 0.000 0.000 #N /A 2.52 0 0.00 24.00 0.00%
Aux Aux Power Out 0.000 0.000 #14 Solid 2.52 _ 0.00 24.00 0.00%
Total Standby Current (Amps) 0.175 1.912 Total Alarm Current (Amps)
Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins)
Total Standby AH Required 4.206 0.159 . Total Alarm AH Required
Total Combined AR Required 4.37 Command Shortcuts
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 5.24 1 Configure Circuits Print Page
El 511ivi
h \tc;: I Circuit Configuration
Project Information
Project Name: AIG Project ID: 10812 -05
Prepared By: T & L Communications, Inc. Date: 8/31/2005
Ckt. Number: IDC -1 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 1
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
1 System Sensor 1451 0.000 0.100 0.000 0.100
#N /A 0.000 0.000 0.000 0.000
#NIA 0.000 0.000 0.000 0.000
#N /A 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.095
Ckt. Number: IDC -2 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 2
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
3 System Sensor 2100TS Duct Detector 0.000 0.100 0.000 0.300
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.095
Ckt. Number: 1DC -3 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 3
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
0 Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.000
tiILENT
fle
h'LCIII Circuit Configuration
Project Information
Project Name: AIG Project ID: 10812 -05
Prepared By: T & L Communications, Inc. Date: 8/31/2005
Ckt. Number: NAC -1 Panel ID: SK -5208
Ckt. Name: Notification App! Ckt 1 Max NAC Current: 3.0 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
2 System Sensor P2475 Hom /Strobe 0.000 0.148 0.000 0.296
2 System Sensor S241575 Strobe 0.000 0.049 0.000 0.098
1 System Sensor SS24110 Strobe 0.000 0.140 0.000 0.140
1 System Sensor P24110 Horn /Strobe 0.000 0.165 0.000 0.165
0.000 0.000
Totals 0.000 0.699
Ckt. Number: NAC -2 Panel ID: SK -5208
Ckt. Name: Notification Appl Ckt 2 Max NAC Current: 3.0 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
3 System Sensor P24110 Horn /Strobe 0.000 0.165 0.000 0.495
2 System Sensor S241575 Strobe 0.000 0.049 0.000 0.098
1 System Sensor SS24110 Strobe 0.000 0.140 0.000 0.140
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.733
Ckt. Number: NAC -3 Panel ID: SK -5208
Ckt. Name: Inactive, Add NAC -CKT Max NAC Current: 3.0 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
0 Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
1 I 0.000 0.000
Totals 0.000 0.000
n
VIEGEINI ED
CITY OC TIGAaD
ns‘ otl
BU11_DMG D""
FIRE ALARM SYSTEM OPERATIONAL MATRIX
LOCATION: AIG ALARM TROUBLE SUPERVISORY MISCELLANEOUS
PANEL TYPE: SILENT KNIGHT 5280
41 et, / q e, Lae cif
k tcv ? � ? cS` �` t `7 e �`` a te° � �c�t�e k`' * v. s r,
� ' P �� ,�� �r s' ys' S ec, ` ~ � `
CAUSE � �'� P c P C� P �d� � e � e � d� ATAT 4- REMARKS
SMOKE DETECTORS • • • • •
HEAT DETECTORS
MANUAL PULL STATIONS
WATERFLOW SWITCH
TAMPER SWITCH
SYSTEM RESET
•
SIGNAL SILENCE •
FIRE ALARM TROUBLE(OPEN,
SHORTS, OR GROUNDS) ON • • •
INITIATION OR SIGNALING CIRCUITS
HVAC RETURN DUCT DETECTORS • • • •
KITCHEN SUPPRESSION SYSTEM
AC POWER FAILURE 40111
AIG
S ; EOL ZONE 1
D EOL ZONE 2
These Detectors provided and installed by HVAC contractor
7
D EOL `ONE 3 LOCATION TO BE DETERMINED AT INSTALLATION
D EOL ZONE 4
SILENT KNIGHT
5208
75 75 1557775157511 110
A A I S I INDICATING Z -1
110 110 110 1575 1575110
12V7 AMP 12V7 AMP E INDICATING Z-2
INDICATING ZONE 3, 4 NOT USED
120 Volt AC 20 AMP Circuit
A U D I B L E / V I S I B L E N O T I F I C A T I O N
SPECTF!e
Selectable Output Strobe SYSTEM
and Horn Strobes �� SENSOR
Models Available 41-; ; -' `_
Strobes P1224MC Fbm /s , : - -,
Red White FIR E
S1224MC S1224MCW F 4 f F t R E
S1224MCP S1224MCPW
S1224MCK p F S1224MCSP I
Horn /Strobes
E 0
Red White $ `' N . , i t
P1224MC P1224MCW f `\
P1224MCP P1224MCPW 1 - ;'
MC P1224MCK ; .-, ` . i
I
P1224MCSP r ' _
Horns f '
`—
Red White ' .
H12/24 H12/24W S1224MC Strobe
H12/24K
Product Overview
Operates on either 12V or 24V SpectrAlert Selectable Output Horns, Strobes, and Horn /Strobes offer enhanced fea
Widest range of candela options: tures that include the widest range of candela options available and the capability to
12V: 15 and 15/75 candela recognize and self- adjust for either 12 or 24 volt operation. With an overall feature
24V: 15, 15/75, 30, 75, 110 candela set that combines performance, installation ease, flexibility, and a consistent,
aesthetically pleasing appearance, the SpectrAlert Selectable Output devices
Easy candela selection provide both the innovation and efficiency synonymous with the SpectrAlert name.
- Lower current draw Performance. SpectrAlert selectable output wall -mount horns, strobes, and horn /strobes
Easy DIP switch selection for horn offer key performance features long associated with the SpectrAlert name. The select -
options able candela strobes and horn/strobes offer average current draws that are not only
lower than conventional fixed- candela SpectrAlert products, but also lower than similar
Easy mounting with QuickClickTM selectable candela products. By consuming less current, the ability to connect even more
Synchronizable with MDL devices per loop is possible, resulting in a lower installed cost.
Sync•CircuitTM module Installation. SpectrAlert selectable output horns, strobes, and horn/strobes offer the
Meets UL1971, NFPA72, and ADA same installation- friendly features synonymous with the SpectrAlert name, such as the
signaling requirements option of 2- and 4 -wire operation; the ability to use standard size backboxes with no
encroachment into the box; and universal mounting incorporating the labor - saving
All strobe and horn /strobe models incorporate a QuickClick"" feature. Such labor - savings features make wire connections simple and fast,
new patent- pending voltage booster design that
has a more consistent Bash bulb voltage over further reducing installed cost.
the range of candela selections. The benefit to Flexibility. SpectrAlert selectable output strobes and horn/strobes offer the broadest
the customer is a high quality strobe device. range of candela options. In addition, the selectable output strobes and horn/strobes
can operate on either 12V or 24V, with no setting required; the device recognizes and
0 self - adjusts to the correct current automatically. Temporal 3 or Continuous tone options
L C continue to be available, in either an Electromechanical or 3kHz pattern.
LISTED (a549V602NK17954 Aesthetics. SpectrAlert selectable output horns, strobes, and horn/strobes incorporate
(5549V 702NK13751
"-,' s4 011 the same stylish, low profile design of the conventional SpectrAlert products, for a con -
�� MEA sistent and aesthetically pleasing appearance across the entire product line.
14111 ® approved
7125-1209:222 122 -02 -E
7135-1209:223 3014150 126-02-E
w
Engineering Specifications
General fire protective service. Horn/strobe shall be wired as a primary
SpectrAlert horns, strobes and horn/strobes shall be capable of signaling notification appliance and comply with the Americans
mounting to a standard 4" x 4" x 1 back box or a single gang with Disabilities Act requirements for visible signaling appliances,
2" x 4" x 1 back box using the universal mounting plate flashing at 1Hz over the strobe's entire operating voltage range.
included with each SpectrAlert product. Also, SpectrAlert prod - The strobe light shall consist of a xenon flash tube and associated
ucts, when used in conjunction with the accessory Sync•Circuit lens/reflector system. The horn shall have two tone options, two
Module, shall be powered from a non -coded power supply audibility options (at 24 volts) and the option to switch between
and shall operate on 12 or 24 volts. 12 volt rated devices shall a temporal 3 pattern and a non - temporal continuous pattern.
have an operating voltage range of 9 -17.5 volts. 24 -volt rated Strobes shall be powered independently of the sounder with the
devices shall have an operating voltage range or 17 -33 volts. removal of factory installed jumper wires. The horn on horn/
SpectrAlert products shall have an operating temperature of strobe models shall operate on a coded or non -coded power sup -
32° to 120 °F and operate from a regulated DC or full wave ply (the strobe must be powered continuously).
rectified, unfiltered power supply.
Synchronization Module
Strobe Module shall be a System Sensor Sync•Circuit listed
Strobe shall be a System Sensor SpectrAlert Model to UL 464 and shall be approved for fire protective service. The
listed to UL 1971 and be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1Hz and horns
strobe shall be wired as a primary signaling notification appliance at temporal 3. Also, the module shall silence the horns on horn/
and comply with the Americans with Disabilities Act require- strobe models, while operating the strobes, over a single pair of
ments for visible signaling appliances, flashing at 1Hz over the wires. The module shall be capable of mounting to a 4 x
strobe's entire operating voltage range. The strobe light shall con- 4 x 2 back box and shall control two Style Y (class B) or
sist of a xenon flash tube and associated lens/reflector system. one Style Z (class A) circuit. Module shall be capable of multiple
zone synchronization by daisy chaining multiple modules together
Horn /Strobe Combination and re- synchronizing each other along the chain. The module
Horn/Strobe shall be a System Sensor SpectrAlert Model shall not operate on a coded power supply.
listed to UL 1971 and UL 464 and shall be approved for
Specifications
Walk Test Weight, strobe and horn /strobe Voltages
SpectrAlert horn /strobe and horn only 8.8 oz. 12 or 24VDC and FWR unfiltered
work on "walk tests" with time dura-
Mounting Operating voltage range*
tions of 4 seconds or greater 4" x 4" x 1 /2" or 2" x 4" x 1 12V: 8- 17.5V; 24V: 16 -33V
Input Terminals standard boxes Operating voltage range* (with
12 to 18 AWG Indoor Operating Temperature Sync•Circuit module, MDL)
Dimensions 32 °F to 120 °F (0 °C to 49 °C) 12V: 9- 17.5V; 24V: 17 -33V
Strobe and horn /strobe with universal Maximum humidity *Note for Strobes: Do not exceed; 1)
plate 95% as tested per UL464 16-33 or 8 -17.5 voltage range limit;
5" x 5 X 2 2) maximum number of 70 strobe lights
Strobe and horn /strobe with small Operating Temperature when connecting the MDL Sync module
footprint plate Weatherproof (horn and horn /strobes) with a maximum line impedance of 4
3 x 5 x 25/16" 32 °F to 150 °F (0 °C to 66 °C) ohms per loop and; 3) maximum line
Horn with universal mounting plate (outdoor strobe only) impedance as required by the fire alarm
5" x 5 x 15/16" -40 °±9 °F to +151 °±9°F control manufacturer
Horn without mounting plate (-40°±5°C to +66 °t5 °C) U.S. Patent Numbers
2 x 5 x 15/16" ULC Canadian Models 5,593,569
-40 °C to 66°C 5,914,665
Weight, horn only 6,049,446
7.2 oz.
SpectrAlert Ordering Information
Model Description Model Description
P1224MC Selectable Output Horn /Strobe, 12/24 volt, red H12/24 Horn, 12/24 volt, red
P1224MCW Selectable Output Horn /Strobe, 12/24 volt, white H12/24W Horn, 12/24 volt, white
• P1224MCP Selectable Output Horn /Strobe, 12/24 volt, red, H12/24K Horn, 12/24 volt, red, weatherproof
plain housing Accessories
P1224MCPW Selectable Output Horn /Strobe, 12/24 volt, MDL Sync•Circuit Module, red
white, plain housing
P1224MCK Selectable Output Horn /Strobe, 12/24 volt, red, MDLW Sync•Circuit Module, white
weatherproof MDLA Sync•Circuit Module, red, Canadian model
P1224MCSP Selectable Output Horn /Strobe, 12/24 volt, red, MDLWA Sync•Circuit Module, white, Canadian model
"FUEGO" housing
S-MP Small Footprint Mounting Plate, red, for single -
S1224MC Selectable Output Strobe, 12/24 volt, red gang back box
S1224MCW Selectable Output Strobe, 12/24 volt, white S-MPW Small Footprint Mounting Plate, white, for single -
S1224MCP Selectable Output Strobe, 12/24 volt, red, plain gang back box
housing BBS Surface Mount Back Box Skirt, red
S1224MCPW Selectable Output Strobe, 12/24 volt, white, BBSW Surface Mount Back Box Skirt, white
plain housing D-MP Universal Mounting Plate (replacement), red
S1224MCK Selectable Output Strobe, 12/24 volt, red,
D-MPW Universal Mounting Plate (replacement), white
weatherproof
S1224MCSP Selectable Output Strobe, 12/24 volt, red, WBB Weatherproof Back Box
"FUEGO" housing
Notes
Agency Listings - Indoor models: UL, ULC, FM, CSFM, MEA. Weatherproof models: UL, CSFM (strobe only), MEA, ULC.
All of these SpectrAlert products are designed for wall mount only. All weatherproof models must use weatherproof back box model WBB. Installation
of less than 75 candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). Howevey it is the responsibility of
the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. All 15/75 candela strobes or horn/
strobes are recommended for 20' x 20' rooms or less.
•
a
System Sensor Sales and Service
System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor - Far East System Sensor - India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.524.6253 Ph: 85.22.191.9003 Ph: 91.124.237.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.524.6259 Fx: 85.22.736.6580 Fx: 91.124.237.3118
Ph: 800 /SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor - Australia System Sensor - Russia
Fx: 630/377-6495 Ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
Documents -on- Demand Fx: 44.1403.891921 Fit: 65.6273.2610 Fx: 613.54.281.172 Fx: 70.95.937.7983
800/736 -7672 x3
www.systemsensor.com
0 2004 System Sensor. The company reserves the right to change product specifications without notice. A050325-004.10/04