Correspondence PRECISION AIR Fax :503- 848 -6971 Sep 28 '03 8:10 P.02 • 71) Z // Lv'Dwi3 • g~l4- (p^' s7Q�Tirr�/ Aso re/ 4 ohng' FP," P RA` -� 11 " A 14 Aitujik September 16, 1998 CITY OF TIGARD Precision Air OREGON 16833 SW Rigert Rd. Beaverton, OR 97007 RE: North American Van Lines Mechanical Plan Review 15495 SW Sequoia Pkwy: PC #: 09 -28c . MEC #: 98 -0400 • Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: i sir r r r • .m ,! ��irr, "y� ,h.L('� p h i}f.{� 'y�'. .. _� 2 t _ u r ,. ..'�'�',�_� �... s{i�•c"L `...: ._Ls, i�ar z:: Jt 1.' Provide an engineer's analysis of each structural member supporting the additional HVAC units. The engineer shall submit plans, computations and specifications. Each plan and computation shall bear the original seal of the engineer licensed to practice as such. [OSSC, Section 1063.2]. 2. The attachment of permanent equipment (HVAC) supported by the building's structural components shall be designed to resist the total design seismic forces sii`j prescribed in Section 1603.2 of the Structural Specialty Code. Provide an Pit- engineer's design specifying attachment requirements [OSSC, Section 106.3.2 P j (2- and OMSC, Section 304.4]. 3. Each individual roof - mounted HVAC shall be permanently labeled as to the areas it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped with a power disconnect. A 120 -volt receptacle shall be located within 25' of each unit.[OMSC, Section 309.1]. Please submit two copies of revised submittal documents and a letter indicating your response to .the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, Ro rt Poskin, CBO SENIOR PLANS EXAMINER . • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639-4171 TDD (503) 684 -2772 r :114 4, //441"11 " ) September 16, 1998 - CITY OF TIGARD Precision Air O REGON 16633 SW Rigert Rd. Beaverton, OR 97007 RE: North American Van Lines Mechanical Plan Review 15495 SW Sequoia Pkwy: P. C #: 09 -28c MEC#: 98 -0400 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: MECHANICAL 1. Provide an engineer's analysis of each structural member supporting the . additional HVAC units. The engineer shall submit plans, computations and specifications. Each plan and computation shall bear the original seal of the engineer licensed to practice as such. [OSSC, Section 106:3.2]. 2. The attachment of permanent equipment (HVAC) supported by the building's structural components shall be designed to resist the total design seismic forces prescribed in Section 1603.2 of the Structural Specialty Code. Provide an engineer's design specifying attachment requirements [OSSC, Section 106.3.2 and OMSC, Section 304.4]. • • - 3. Each individual roof - mounted HVAC shall be permanently labeled as to the • areas it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped with a power disconnect. A 120 -volt receptacle shall be located within 25' of each unit [OMSC, Section 309.1]. Please submit two copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, • • Ci4os Rob rt Poskin, CBO • SENIOR PLANS EXAMINER pn.r.me aniknoae a.aopm� • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 PRECISION AIR Fax:503- 848 -6971 Sep 28 '03 8:10 P.01 TO go8cter loos,Ci A✓ G 0 F 7740tWAO Ago el. . i iM £d /ercisro../ i41-. 2 r MC G -oyo0 #Z G124 Zs fl Or_i'AI[. - o,.) %t+E geoPRO j 4 f . Um 17 �4. 1 4ii (I re l0rb.144 FOR% „ G41l Fo, A )I ✓i . - .Z.v5PFc70 l IGtr s 2TE.•^ • w; li ar SeP,"4 y 4 c s Te cT 1 c e} t r 4i, h y 074CC 4944 S%'#- • Fasten unit to a� oust with 1" wide J /� 20 gauge strap on alt 4 corners of unit / UNIT BOTTUM CANT STRIP M1 - NAILOR STRIP _ RIGID INSULATION ROOFING MATERIZL 18 GUAGE METAL ; MANUFACTURED CURB CURB DETAIL •