Loading...
Correspondence h � � Iy A September 20, 2005 - ' . *a CITY OF TIGARD OREGON T & L Communications Ross Bushaw PO Box 87387 Vancouver, WA 98387 RE: FIRE SPRINKLER SYSTEM MODIFICATION — MG Project Information Building Permit: BUP2005 -00362 Construction Type: III -B • Tenant Name: MG Occupancy Type: B Address: 15495 SW Sequoia #140 Occupant Load: 79 Area: 7,855 sq ft Stones: 1 Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition, Oregon Fire Code 2004 edition; and NFPA 13. The submitted plans are approved subject to the following. HYDROSTATIC TESTING Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test certificate required by NFPA 13, 16.1 shall be completed and signed by both the installer and building owner. TESTING: - Section 16.2.1 1. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual leakage. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. WATERFLOWALARMS: - Section 6.9.1 2. Water flow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed on the system will result in an audible alarm on the premises within 5 minutes after such flow begins and until such flow stops. • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 SPRINKLER SYSTEM MONITORING:. OSSC 901.6. - NFPA 72 3. All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all sprinkler systems shall be electrically monitored where the number of sprinklers are less than 20 HANGERS: 4. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2. 5. The maximum distance between hangers for listed nonmetallic pipe shall be modified as specified in the individual product listings. SWAY BRACING: - Section 9.3.5 - 9.3.5.8 6. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. SPARE SPRINKLERS: - Section 6.2.9 7. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: a. For systems having less than 300 sprinklers, not fewer than six sprinklers Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Res. = , 1 i al Henzel, Senior Plans Examiner 4 u i � n i A i i p g lj I I August 16, 2005 CITY OF TIGARD OREGON PacTrust Dennis Pagni 15350 SW Sequoia Pkwy, #300 Portland, OR 97224 RE: MG - REVIEW Project Information Building Permit: BUP2005 -00362 Construction Type: III -B Tenant Name: MG Occupancy Type: B Address: 15495 SW Sequoia #140 Occupant Load: 79 Area: 7,855 sq ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 International Fire Code as amended by TVF &R. The following information is required in order to complete the review. 1. Provide Oregon Energy Forms showing project meets OSSC Energy chapter 13. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec 11y� Val e , Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 • 1 : I August 15, 2005 CITY OF TIGARD OREGON PacTrust Dennis Pagni 15350 SW Sequoia Pkwy, #300 Portland, OR 97224 RE: MG - REVIEW Project Information Building Permit: BUP2005 -00362 Construction Type: III -B Tenant Name: MG Occupancy Type: B Address: 15495 SW Sequoia #140 Occupant Load: 79 Area: 7,855 sq ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are approved subject to the following conditions. 1. The main exterior door or doors are permitted to be equipped with key - operated locking I , devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. 2. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. 1011.1 OSSC • 4. All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. 1008.1.8 OSSC • 5. Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. 1006.3 OSSC FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 6. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. 1006.2 OSSC 7. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. Deferred Items: * Fire Sprinklers * Fire Alarms NOT PART OF TIES REVIEW: * Electrical * Mechanical System * Plumbing 8. Safety glazing including but not limited to: the following locations: Each unit of glazing shall be permanently identified by the manufacturer. 2406 OSSC. Some of these locations are as follows: a. Glazing in ingress and means of egress doors. b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical edge is within a 24" arc of the door in a closed position and whose bottom edge is less than 60" above the floor or walking surface except when there is an intervening wall or other permanent barrier between the door and the glazing. 9. American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy 110.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Resp al Henzel, Senior Plans Examiner