Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
/542 3o P Automatic Fire Alarm System ( A�5 3 v Material Submittal for D DAMONS CLUBHOUSE 1) CENTRAL PROCESSING UNIT. A. Notifier Model# AFP -200 2) ADDRESSABLE PULL STATIONS A. Notifier Model# BGX -101L 3) DUCT DETECTOR • A. Notifier Model# DHX -502 4) INTELLIGENT THERMAL DETECTORS A Notifier Model# FDX -551 5) INTELLIGENT IONIZATION DETECTORS A. Notifier Model# CPX -551 6) INTELLIGENT DUCT DETECTOR HOUSING A. Notifier Model# DHX -501 7) SIGNALING STROBES A. System Sensor Model# S2475ADA 8) SOUNDER STROBES A. System Sensor Model# P2475ADA 9) VOLTAGE DROP CALCULATIONS. DEVICES - ZONE 1 10) VOLTAGE DROP CALCULATIONS. HORN /STROBES - ZONE -1 11) VOLTAGE DROP CALCULATIONS. HORN /STROBES - ZONE - 2 12) BATTERY CALCS August 13, 1997 A -102 N O T I F I E R An g Fire Panel "— A Pittway Company Software Release 2 Section: Intelligent Fire Alarm Control Panels GENERAL M EA The AFP -200 is a compact, cost - effective, intelligent fire alarm control with a capacity of 301 individually identified 104 -93 -E 441 and controlled points and an extensive list of powerful (not MEA approved 0V4A5.AY features. The AFP -200 provides capabilities that exceed S635 CS118 for security) most large intelligent systems, at a cost comparable to am California U.S. Coast Guard .T conventional control panels. � � State Fire 1c1W FEATYRES l Marshal 161.002/23/1 \� 1 • 198 intelligent device capacity (99 analog detectors and jog 7165 -0028:164 94/00004 99 monitor /control modules). Style 4, 6, or 7. i4 ; ; • Overall 301 point capability (198 intelligent points, 4 ' . P P tY ( 9 P --- . programmable NAC circuits, 99 programmable relays). .° . • Network ready (reference NOTI • FIRE • NETT" and NAM- . <` -�" }'� AFP -too h 232 catalog sheets for more information). • Intelligent features: " t;. " .. ;7 X45 ✓ Manual sensitivity adjustment. i .. 4' ' ✓ Day /Night automatic sensitivity adjustment. 710iVi,4; ,, F "x . ✓ Drift compensation (U.S. Patent Pending) meets UL ` + ` °mmaQ ,..-;, ,„ ; requirements as a calibrated test instrument. t _:- a B O ✓ Auto detector test (meets NFPA 72). - , , ...„t4-3 -. 0===o- f/ Maintenance alert (two separate algorithms). '-ar- `, a° . - 0i ii =` _;' ✓ Pre -alarm (AWACSTM U. S. Patent Pending). L - `� s ' ✓ Activate local sounder base on pre - alarm. ° ;:� r : ` -., 4/ LED blink control for sleeping areas. ,,-").-,v Y = °- -- `� ✓ Automatic device type check._ y ; • Releasing features: ; .-. :f 0NOTIPIlR' ✓ Four independent hazards. ; . s; ✓Sophisticated cross -zone (three options) w _ x a/ Delay timer and Discharge timers (adjustable). F,. ;, r ✓ Abort (four options). The AFP -200 • Optional DACT, with AC fail delay. 16.125" H x 14.5" W x 5.5" D • LCD -80 remote display /control. • MMX -2 two -wire detector interface provides compatibility • ACS annunciators (EIA -485), including LDM custom. with many non - NOTIFIER detectors for retrofit applica- • Printer interface (80 column and 40 column printers). lions (consult factory for latest compatibility listings). • 5.0 A usable regulated output power, plus 3.0 A expander. • Dual rate charger for up to 90 hours of standby power. • 80 character LCD display, backlit. • Two -Stage option for bell circuits (Canada). • Real time clock, with European format option. • Tornado Warning activates different Notification Circuit • History file with 650 event capacity in nonvolatile memory. code. Includes non - erasable shadow history. • Non -alarm points for lower priority functions. • Waterflow or supervisory selection per point. • Remote ACK/Silence /Reset/Drill via MMX modules. • Alarm Verification selection per point, with tally. • Automatic time control functions, with holiday exceptions. • Walk Test reports 2 devices set to same address. • Rapid poll algorithm for manual stations. Responds in < 2 • Positive Alarm Sequence (PAS) Presignal per NFPA 72. seconds. • Silence inhibit and Auto Silence timer options. • Operates with untwisted, unshielded wire (up to 1000 feet) • March time /temporal /California code for bell circuits. for retrofit applications (U. S. Patent 5, 210, 523). • Field- programmable on panel or on PC, with user - defined • UL listed for Fire Signaling per Standarc.1864 & NFPA 72. passwords, plus Autoprogram feature. • UL listed for Burglary applications per Standard 1076. • UL- listed modem interface allows remote /off -site system • UL listed for Releasing per NFPA 12,12A, 12B,13,15, 16. integration. • UL listed for Critical Process Monitoring. • FM approved for Agent Release and Preaction /Deluge. • • Approved for marine applications by U.S. Coast Guard NOTI•FIRE•NETTu is a trademark of NOTIFIER, 1994. and Lloyd's Register of shipping. This document is not intended to be used for installation purposes. We try to keep our product information up-to -date and accurate. We cannot cover all specific applications or ISO -9001 anticipate all requirements. All specifications are subject to change without notice. For Engineering and Manufacturing more information, contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 Quality System Certified to • International Standard ISO-9001 0 N OTI FI E R 12 Clintonville Road, Northford. Connecticut 06472 Made in the DN -3783 — Page 1 of 4 SYSTEM BLOCK DIAGRAM SLC Intelligent Loop i FIRE X X m �) 198 devices -. NOTL•FIRE•NET SDX -551 CPX -551 FDX -551 - BGX -101L MMX -1 CMX -2 Optional Network Interface t via the NAM -232 IDC IAC , EIA -485 99 software zones AFP -200 ®e 4-- ■ ■ --• ®C� CD= =II 11 WW1 Irma mil cm imi i UM 4-01 ■ �° -U rlJ u_ NELJ u_ tlM 1J_ mLJ .:= �.J u= �. CM MU uM �l [ Mil I = �i 1 MI I f1= RS -232 ZrJ ❑= marl rim mu CM MBE um 4 Notification or ACM-8R ACM /AEM -16AT Release Circuits Relay LED Annunciator Control 0 0 0 0 0 CRT -2 tt, „,r c, z � 01 o .. ■ 0 0 0 - pin. 1 K o«: M_:..:... > • > �.. I I (I I I I LDM -32 Custom Graphics PRN-4 Printer EIA -232 interface for CRT, EIA -485 loop for printer, or PC computer. LCD or LED Four standard annunciators. Notification or Releasing circuits. E --ixa. :..n. . {ti: SLC loop. Full Alpha t = keyboard for I t t . > Up to 198 devices menu - driven ' i l n �R 4 V: =;; on a single pair �„ C� at4 ._ of wires. ; programming. �` U�. t ? = a ....... O ti 5 ampere r **! .� ` `� . �., Slot for regulated , M %ono . ...ti, . � - optional power supply. _ „ -� ,. ,-. . � � � � module. . Voltmeter/ _ . .; Ammeter 12 AN batteries. 80 character backlit Option. Up to 90 hours standby power. LCD display. Page 2 of 4 — ON-3783 AWACS Advance Warning Addressable Combustion Sensing (U.S. Patent Pending) SMOKE OBSCURATION % per foot 30/ _ ALERT ACTION ALARM Warning at panel Shut off power Evacuate building of possible fire to equipment monitored and call fire department by this detector PREALM SMOKE(PHOTO) PREALM SMOKE(PHOTO) ALARM: SMOKE(PHOTO) e r FLOOR 3 EQUIP RACK 5 FLOOR 3 EQUIP RACK 5 FLOOR 3 EQUIP RACK 5 2% — ALERT: 0.22% 1.40% ACTION: 0.51% 1.40% FrRE DEPT CALLED - 11:25 P 12/25/93 D66 11:36 P 12125!93 D66 11:59 P 12/25/93 066 •�M • • ; o r —.. �".'•s's'c'y` "r •`7 � f- - q ,�, 1 % • . -.. . . , .-., ue • __ r a" aaa5 iia� r� � . o -.. ,t.�,, A * 3: ' - - 4,7 .., � s ,. . x`. 'a�A"' fYt` - tx*.afir '"'.74 » +7i.r., - _ -� � ,,:, :„ a=r;s: _„,,a,ic y :,, ,a-„.= ic:- „'zX,4,. - 241 ,; : -4- , - '01 _ - :: -.: , .y-a ° ^,? 4 1z.' _-� x,•, - .,a:it,,e. _ MtR;:'.:•'i4 0i ., . 4 s1.. - - -. TIME ALERT and ACTION levels are completely adjustable in the field to suit the cleanliness and stability of the environment. ALARM levels are field adjustable to one of 3 levels within the UL permitted range. ACTION levels latch and may be used to perform control functions. ALERT levels self - restore and may be used to activate a local sounder base before general ALARM evacuation. FIELD PROGRAMMING - 3 WAYS 1. AUTO - PROGRAM AUTOPROGRAM The AFP -200 identifies all devices that are connected, PLEASE WAIT determines the type of device, and loads default values (general alarm) into non - volatile memory. This is com- pleted in less than 30 seconds. 2. ON - LINE EDIT While still providing fire protection, the AFP -200 program may be completely edited from the front keypad. Menu 0 = CLR 1 = AUTO 2 = POINT trees permit easy change of any parameter without refer- 3 = PASSWD 4 = MESSAGE ral to the programming manual. Recall, increment and edit 5 = ZONES 6 = SPL ZONES function speeds entry of alphanumeric labels. New pro- 7 = SYS 8 = CHECK gram check routine catches common errors. 3. OFF -LINE PC I SYSTEM PARAMETERS I The complete AFP -200 program may be created in 1/ SYSTEM TIME: use 2/ LEOS BIM: VV an off -line PC compatible computer, then loaded 3/ STYLE TERM()D SUPO) 8 -388 s) : 38B into the AFP -200 EIA -232 port. The program may 5/ SILENCE INHIBIT TIMER 6/ AUTO SILENCE TIMER e, -gee s): b also be off - loaded to a PC at any time. High speed 8/ ALARM VERIFY 11MER fe -6e �): 6a data transfer completes upload or download in less 8/ SYS. NORMAL PESSA6E:I , 98 Oe1ey ((68-188 s)• V than 1 minute. The PC program may also be used Ze Za 91 Oelay (8 -68 c 68 188 ABPAS: ORT: ULI CROSS: Y SOAR 8,18 -15 win): 15 to access remote AFP -200 systems over dial -up 20 92 Delay ((B -6e s 6e ABORT: ell CROSS: V SORN ( (0.10 -15 win) 15 20 93 Delay ( - s in ABM; MA CROSS: V SORN (SOS -15 win). 15 a 90. Delay (8 -68 s 68 ABORT ell CROSS: V SORN (e 18 -15 win): 15 phone lines, providing detail status information and Zo 95' OM(hl� : :ow) 12iw) 12 : :15 BFF Ah:n. 15 OFF(hhq 11 : -/5 Su:V M /s Su:V M :M T T : •V YV Y : •M 1hM }h :V F F : :N S:V X M L; H :N M 2t 96' OM((hh history file search /sort. o $. glagobA 1101 82/82 83/03 1 84/80 85/85 06/96 97/87 88/08 89/89 2s 99 , ALERT LEUEL =882 ACTION LEUEL=B87. DOME Press ESC DN -3783 — Page 3 of 4 AGENCY LISTINGS AND APPROVALS COMPATIBLE DEVICES, EIA -232 Port See page 1 for listing agencies and file numbers. These Model Description listings and approvals apply to the basic AFP -200 control PRN-4 80 column printer. panel. In some cases, certain modules may not be listed VS4095/S2 Printer, 40 column, 24 V. Mounted in exter- -- by certain approval agencies, or listing may be in process. nal backbox (Order from Keltron, Inc.). Consult factory for latest listing status. SPECIFICATIONS CRT -2 Video display terminal. NAM -232 Network Interface Module to HOTI • FIRE. • Primary input power; 120 VAC, 50/60 Hz, 3.0 Amps. NET wire or fiber models. • Total Internal 24 VDC Power - 5.0 A (total shared power). COMPATIBLE DEVICES, RS -485 Port ✓ High Ripple Regulated Power - 1.5 A (suitable for EIA -485 devices, except ACM -8R) - 1.0 A max. Model Description (see catalog sheets) standby. ACS Series Remote Serial Annunciator /Control systems. ✓ Non - resettable Power - 500 mA. LCD-80 Remote LCD display. ✓ 4 -wire Smoke Detector Power - 500 mA. LDM Series Remote custom graphic driver modules. ✓ Four built-in Notification Circuits • NAC Circuit 1 - 2.25 A ACM -8R Remote relay module. 8 FomrC relays. • NAC Circuits 2-4 - 2.25 A (shared total) NIB -96 Network Interface Board. Note: with optional AVPS Power Supply NA C circuits 3 & RPT -485 Series Repeater, isolator and /or fiber optic 4 are expanded to 3.0 A (8.0 A total power). modem. • Battery charger range: 7 AH - 17 AH. UDACT Universal Digital Communicator. • Charge high rate: 29.1 V. Float Rate: 27.0 V. • Relay contact rating: 2.0 A @ 30 VDC. PRODUCT LINE INFORMATION SYSTEM CAPACITY Model Description • Total programmable input/output points: 301 BEAFP -200G - Basic AFP -200 equipment kit. Includes • Intelligent Detectors: 99 main board with display and keypad, door, hardware • Addressable monitor /control modules: 99 and manual. Backbox (SBB -4X or SBB -4XR) ordered • Programmable NAC (bell) circuits in panel: 4 separately. • Programmable software zones: 99 BEAFP -200R - Same as BEAFP -200G, but includes a red • Programmable remote relay /annunciator points: 99 door. • LCD -80 annunciators per system: 4 BEAFP -200GE - Same as BEAFP -200G but 230 VAC. • ACS annunciators per system: 10 BEAFP -200RE - Same as BEAFP -200R but 230 VAC. CONTROLS AND INDICATORS SBB-4X - AFP -200 Backbox (no door), gray. 6 LED indicators: AC Power; Fire Alarm; Pre - Alarm; Su- SBB -4XR - AFP -200 Backbox (no door), red. pervisory/Security; Alarm Silenced; System Trouble. CAB -AM - Heavy duty outer enclosure. Required for ma- 21 Membrane Switch Controls: Acknowledge /Step; Si- rine agency approved applications. lence; Evacuate; System Reset; 12 key Alpha pad; 4 4XTM - Plug -in Transmitter Module. Provides municipal cursor keys; Enter. box & remote station connection. LCD Display: 80 characters (4 X 20) with long -life LED RTM-8 - Plug -in Relay Transmitter Module. Provides 8 backlight. Form -C relays, plus transmitter. COMPATIBLE INTELLIGENT DEVICES 4XMM - AmmeterNoitmeter. Model Description TR-4XG - Gray Trim Ring for semi -flush mounting (TR- CPX -551 Ionization Smoke Detector. 4XR for red). CPX -751 Low Profile Ionization Detector. DP- AFP200 - Full length dead front panel (required for SDX -551 Photoelectric Smoke Detector. Canadian Applications). SDX -751 Low Profile Photoelectric detector. PS -1270 - Battery, 12 volt, 7.0 AH, (two required). SDX -551TH Photoelectric with thermal element. PS -12120 - Battery, 12 volt, 12.0 AH, (two required). FDX -551 Fixed Thermal (Heat) Sensor. PS -12170 - Battery, 12 volt, 17.0 AH (two required). FDX -551R Fixed and Rate-of-Rise thermal sensor. AVPS -24 - 3.0 A Expansion supply (requires BB -17). BX -501 Detector Base, high profile. B710LP Detector Base, low profile. BB-17 - Battery box, required for PS- 12170, or if AVPS -24 8501 BH Sounder Base. is used. DHX -501 Duct Housing with Alarm relay. 911AC - Digital Alarm Communicator/Transmitter. DHX -502 Duct Housing without Alarm relay. PK -200 - Programming kit for PC. Includes diskette, MMX -1 Monitor Module. cable, and instructions. MMX -2 Two wire detector monitor module. - ROM- AFP200SP - Spanish language kit. Includes soft- MMX -101 Miniature Monitor Module. ware IC, manual and labels. CMX -2 Control Module ARCHITECTURAL/ BGX -101L Manual Fire Alarm Station, Addressable. ENGINEERING SPECIFICATIONS ISO -X Isolator Module. Complete specifications are available on 3.5" (1.44 mbyte) WordPerfect® is a registered trademark IBM compatible diskette, in WordPerfect & ASCII formats. of WordPerfect Corporation. Page 4 of 4 — DN -3783 November 14. 1996 H -130 NOT 1 Fl E R Addressable M a Manual l Pull Station A Pittway Company Section: Intelligent/Addressable Devices • GENERAL California The BGX -101 L is an addressable manual pull station with a 1 State Fire key -lock reset feature. It provides the AM2020, AFP1010, Y`. 0-0028:003 AFP -400, AFP -200, and System 5000 (equipped with an 0V4A5.AY 11 AIM -200 module) with one addressable alarm initiating in- S692 (AFP -200) ' Out. 0W6A2.AY (AM- 2020 /AFP1010) l II leM FEATURES ADA 93/00141 • Within ADA 5 lb. pull force when used without break -tube (models manufactured after 10 -1 -96, identified by an under station spring). • Highly visible. - • ---..- • Easily operated (dual- action). • Attractive shape and textured finish. - • Semi -flush, mounts to a standard single -gang (2.125" mini- X 5 mum depth), double -gang, or 4" square electrical box. • Operates with or without a crush tube. • Handle latches in down position to clearly indicate the 1 4 I • • station has been operated. - • Key reset. • Screw terminals for easy connection to SLC Loop Channel. • • Optional trim ring. . — • Meets UL 38, Standard for Manually Actuated Signaling PUSH N Boxes. TH EN CONSTRUCTION • Shell, door, and handle are molded of durable LEXAN® (or . polycarbonate equivalent) with a textured finish. , • PULL DOWN • 16 gauge steel back plate. p4 OTg F I E R OPERATION Pulling the handle down causes it to latch in the down posi- tion. The handle is restored manually by using a mechani- The BGX -101 L cal key which allows the top of the case to pivot forward and Addressable Manual Pull Station the spring - loaded handle to return to its normal position. The case can then be pivoted back to its normal position and secured with the key. Each manual station, on command from the control panel, PRODUCT LINE INFORMATION sends data to the panel representing the state of the manual Model Description switch. Two rotary decimal switches allow two -digit address BGX -101 L Standard unit. Dual action. Works with, or setting. without, a fiber crush -tube. Includes key locking feature. BG -TR Optional trim ring. 6 -1/2" High, 5 -1/8" Wide, LEXAN® is a registered trademark of GE Plastics, a subsidiary of 5/32" Deep. General Electric Company. SB - Surface backbox. This document is not intended to be used for installation purposes. We try to keep our product information up-to -date and accurate. We cannot cover all specific applications ISO -9001 or anticipate all requirements. All specifications are subject to change without notice. Engineering and Manufacturing For more information, contact NOTIFIER. Phone: (203) 484.7161 FAX: (203) 484 -7118 Quality System Certified to International Standard ISO-9001 Made in the U.S.A. 1 j� N OTI Fl E R 12 Clintonville Road, Northford, Connecticut 06472 DN -3189 — Page 1 of 2 INSTALLATION ` • The BGX -101 L will mount semi -flush into a single -gang, / a d v double -gang, or standard 4" square electrical outlet box, - . Q 6 I or will surface mount into the Model SB -10 surface backbox. If the BGX -101 L is being semi -flush mounted, then the • m , a optional trim ring (BG -TR) may be used. The BG -TR is ® ® usually needed for semi -flush mounting with 4" or double- • I c. gang boxes (not with single -gang boxes). c I— 1�4� n , ELECTRICAL SPECIFICATIONS �� Q d z Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. • r \ Maximum SLC loop current: 230 NA. • ce a - • • V ARCHITECTURAL/ Q ® ® C Rotary ENGINEERING SPECIFICATIONS Decimal Manual Fire Alarm Stations shall be addressable, fiber O ® ® O Switches break -tube (or non -fiber break -tube) type, equipment with (_) ( +) a key operated test -reset lock in order that they may be tested, and so designed that after emergency operation, The SLC Loop Channel they cannot be restored to normal except by using a key. • • ID M An operated station shall automatically condition itself so as to be visually detected, as operated, at a minimum distance of one hundred feet, front or side. Manual stations shall connect with two wires to one of the j I control panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual sta- The BGX - 101 L (back view) tions shall provide two -digit address setting by use of ro- tary decimal switches. Manual stations shall be constructed of LEXAN® (or poly - carbonate equivalent) with clearly visible operating instruc- ' lions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches or larger. Stations shall be suitable for surface mounting on matching backbox, or semi -flush mounting on a standard A single -gang, double -gang box, or 4 inch square box, and shall be installed within the limits defined by the Ameri- cans with Disabilities Act (ADA) dependent on manual station accessibility or per local requirements. Manual View from 4=118" stations shall be Underwriters Laboratories Inc. listed. TOP • 1-318" 0' 1 -1/8" '-- Optional 1 -3/8" ' surface ,r,;i backbox o FIRE I 0 View from SIDE 5-1/2" 0 I PUSH IN 1 THEN PULL V DOWN NOTIFIER - ;4--- 2 -3/4" —► Page 2 of 2 — DN -3189 June 11, 1997 11-121 N OTI Fl E R DHX -502 A Pittway Company Intelligent Duct Detector Housing Section: Intelligent/Addressable Devices GENERAL MEA 41> The DHX -502 Series Duct Housing is designed to sample 427 -91 -E air currents passing through a duct and allows the early 0T3A9AY detection of developing fire. The DHX -502 Duct Housing S1115 CS308 will accommodate either the CPX -551 Intelligent Ionization ML154 Califomia Sensor or the SDX -551 Intelligent Photoelectric Sensor, (DHX -502A) ��c,� Marshal either of which provides continuous analog monitoring of �F`s7f 3240- 0028:158 the unit's sensitivity. When sufficient smoke is sensed, an I'" " " I alarm signal is initiated at the AM2020 control panel, AFP1010 control panel, AFP -200 control panel or AIM -200 module (supports the SDX -551 detector head only) moni- toring the detector, and appropriate action can be taken to shut off fans and blowers, change over air handling sys- tems, etc. This can prevent the rapid distribution or isola- tion of toxic smoke and fire gases throughout the areas '�� ,• served by the duct system. i. The DHX -502 duct detector system features the superior ‘ 7 - s r, • 1 (I capabilities of an intelligent sensor in a unit that is easy to Ty ' 7 � -t " It .. install and maintain, making this duct detector the new in- `" dustry standard , t • FEATURES 1 ,: • Accommodates intelligent ionization or photoelectric heads. • Continuous sensitivity monitoring and alarm verification The DHX - 502 Intelligent Detector Duct Housing from the panel. • Simple change -out of detector heads: twist -in, twist -out. • Easy and quick mounting to round or rectangular ducts. • Outputs for remote test station (separate 24 VDC is re- SPECIFICATIONS quired). • Air velocity rating from 500 to 4,000 feet per minute. Dimensions: 14 -1/2" (36.8 cm) wide, 5" (12.7 cm) high, • UL 268A listed. 3 -1/2" (8.9 cm) deep. • Clear polycarbonate cover for convenient visual inspec- Weight: 2 lbs., 8 oz. (1.1 kg). tion of sampling tube filters. Operating temperature range: 0 °C to 49 °C (32 °F to • Rugged Noryl® housing (mounting portion). 120 °F). • Three -year limited warranty. Operating humidity range: 10% - 93% relative humidity. • Optional remote LED (RA400Z). Air duct velocity: 500 to 4,000 feet per minute. CONSTRUCTION AND INSTALLATION UL listed to 268A. The twist -in, twist -out detector and base allow the removal ELECTRICAL RATINGS of detectors easily and quickly for cleaning and mainte- Voltage range: 14.5 to 28.0 VDC peak nance. In addition, detector heads can be changed to fit Standby current (nominal): 150 pA at 24 VDC. the application without removing the duct housing. The DHX -502 comes with a built -in exhaust tube. Sampling Power -up surge at max. rated voltage: 1.5 mA -sec. tubes are available to fit ducts from 1 to 10 feet wide. LED current (nominal): 6 mA at 24 VDC. This document is not intended to be used for installation purposes. We try to keep our product information up-to -date and accurate. We cannot cover all specific applications or ISO -9001 anticipate all requirements. All specifications are subject to change without notice. For Engineering and Manufacturing more information, contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 Quality System Certified to • International Standard ISO - 9001 0 N OTI Fl E R 12 Clintonville Road, Northford, Connecticut 06472 Made in the DN - 3530 — Page 1 of 2 • INLET TUBE SELECTION PRODUCT LINE INFORMATION Model Description Outside Duct Width Inlet Tube Required DHX -502" Intelligent Duct Housing. NOTE: Intelligent Duct Housing is priced without Inlet Tube or . Sensor Head. Order one Inlet Tube and one Up to 2 feet ST-1.5 Sensor Head for use with each Intelligent Duct Housing. 2 to 4 feet ST-3 CPX -551" Intelligent Ionization Sensor Head. NOTE: The CPX -551 is for use with the AM2020, 4 to 8 feet ST-5 AFP1010, and AFP200 only. This sensor head, when installed in a DHX -501, is not sup - ported by the AIM -200. 8 to 10 feet ST -10 SDX -551" Intelligent Photoelectronic Sensor Head. ST -1.5 Metal Sampling Tube, duct widths 1' - 2'. *NOTE: Inlet tube is required and must be purchased sepa- ST -3 Metal Sampling Tube, duct widths 2' - 4'. rately. Order one inlet tube for each duct detector housing you order. ST -5 Metal Sampling Tube, duct widths 4' - 8'. ST -10 Metal Sampling Tube, duct widths 8' - 10'. RA400Z Remote LED. F36 -05-00 Replacement Filters. MO2.04 Test Magnet. ® P48 -21 -00 End Cap for Sampling Tube. IIIIIIIIIII A2650 -00 Installation Kit (parts bag). RS24 RS14 Photoelectronic Replacement Screen. Ionization Replacement Screen. MOD400R Sensitivity Test Kit. CRT400 Ionization Cover Removal Tool. 156- 473 -00 Applications Manual, Duct Detectors. RTS451 Remote Test Station. IIIIIIIIIIII * *Order A" suffix for Canadian (ULC) listed versions. RA400Z Remote Annunciator LED Page 2 of 2 — DN -3530 FDX -551 Series H-110 m N OTI F I E R® Intelligent Thermal Detectors A Pittway Company Catalog Section: Intelligent / Addressable Devices April 12, 1995 • GENERAL California State Fire The FDX -551 Series intelligent thermal detector is used ® L M with the AM2020, AFP1010, AFP -200, and AIM -200 ad- i -mil 7270 - 028:150 vanced multiplex systems to measure thermal levels caused S747 CS630 (FDX - 551) by . a fire and report the analog level of the thermal mea -Cy FDX-551A 7270 - 028:167 surement to the control panel.The use of analog informa- I I MEA (FDX -551R) tion provides significant benefits to the end user, installer ��ll/►���� and serviceman in ways which are not possible with a con- 004AO.AY 460 - 92 - i(.0`i•I ti venfiona/type system. Since this detector is also addres- (FDX - 551) 104 - 93 - rssk sable, it will help firemen to more quickly locate a fire dur- 004A7.AY 290 - 91 - p 4 y (FDX - 551 R) 93/00141 ing its early stages. US Coast Guard BASES SEPARATELY LISTED. CONTACT FEATURES 161.002/27/0 FACTORY. • Dual Thermistors. 161.002/23/0 • Rate -of -Rise model (FDX -551 R),15 °F (9.4 °C) per minute • Factory preset at 135° F (58 °C). • Addressable by device. . ; P,.. • Direct DECADE 01 -99 entry of address. • 2 -Wire loop connection. `' • Visible LEDs "blink" every time the unit is addressed: r - -. — Optional with AM2020 software revision 5 or higher. - ° — Optional with AFP1010. ., M, — Optional with AFP -200. . ,� F • 360° field viewing angle of the visual alarm indicators -. ! f (Two LEDs). LEDs illuminate steady during alarm. • • Integral Communications and Built -in Device Type !den - tification. • Compact, Stylish Design. • Remote test feature from the panel. • Built -in functional test switch activated by external mag- net. • Low standby current. • Listed to UL -521. • Separate base allows interchange of Photoelectric, Ion- ization and Thermal sensors. • Built-in tamper-resistant feature. • SEMS screws for wiring of the separate base. • Designed for Direct Surface or Electrical Box Mounting. • 94 -5V plastic flammability rating. • Sealed against back pressure. • Remote LED output connection to optional RA400Z re- °z • Plugs into separate base for ease of installation and main- mote LED annunciator. tenance. c. • Optional sounder, relay and isolator bases. • Optional recessed base mounting kit (RMK400). This document is not intended to be used for installation purposes. We try to keep our [SO -9001 product information up to date and accurate. We cannot cover all specific applications or Engineering and Manufacturing ■ anticipate ail requirements. All specifications are subject to change without notice. For more u Qality System Certified to information, contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 International ality Standard ISO-9001 0 N OTI Fl E R' 12 Clintonville Road. Northford, Connecticut 06472 Made ,n the U.S.A. Page 1 of 2 APPLICATIONS SPECIFICATIONS Use thermal detectors for protection of property. Operating Temperature 32° -120 °F For further information call Notifier for manual 156 -407- Operating Voltage/ 00, Applications Manual for System Smoke Detectors ", Current Range 15 -28 V (Peak DC), 5 mA current which provides detailed information on detector spacing, for visible LEDs latched on. placement, zoning, wiring, and special applications. Detector Standby Current: 150 NA maximum. B524RB or B524 BI: < 700 uA @ 24 VDC (includes CONSTRUCTION detector) These detectors are constructed of Lexan® in an off -white Sensor Electronic, Dual Thermistors. color. Fixed temperature alarm 57° C. (135° F.) The FDX -551 Series plug -in intelligent thermal detector Rate of Rise Option 15 °F (9.4 °C) per minute. is designed to commercial standards and offers an at- Relative Humidity 10 %'to 93 %. tractive appearance. Weight 6 oz. (170 gm.) BX -501 Base Dia. 6.2 inches (15.8 cm). INSTALLATION B501 Base Dia. 4.0 inches (10.3 cm). The FDX -551 Series plug -in intelligent thermal detector B524RB Relay Base: Screw terminals: Up to 14 AWG uses a separate base to simplify installation, service and Relay type: Form -C maintenance. Rating: 2 A © 30 VDC resistive .3 Installation instructions are shipped with each detector. 1. A @ 110 VDC inductive 1.0 A ®30 VDC inductive A specially designed tool allows maintenance personnel B524B1 Isolator base: Dimensions: 6.2 in. (157 mm) x 1.4 to plug -in and remove the sensors without using a lad- in. (36 mm). der. Maximum: 25 devices between isolator bases. Mount base (all base types) on box which is at least 1.5" PRODUCT LINE INFORMATION deep. Suitable boxes include: Model Description • 4" square box FDX -551 Intelligent Thermal Sensor • 3 -1/2" or 4" octagon box. FDX -551 R Intelligent Thermal Sensor. with Rate -of -Rise • Single gang electrical box (except relay isolator base) feature. • Use a 4" square with B501 BH base. FDX -551A Intelligent Thermal Sensor. ULC Version • Use a 3 -1/2" or 4" octagon or 4" square box for the FDX-551RA Intelligent Thermal Sensor with Rate of Rise. B524RB or B524B1 base. ULC Version NOTE: Because of the inherent supervision provided by Bases (order separately) the SLC loop, end -of -line resistors are not required. Wir- BX -501 Standard U.S. Base. ing'7taps" or branches are permitted for Style 4 (Class B501 Base, flangeless (European style). "B ") wiring. 8501 BH Flangeless base (B501) with 24 VDC, 85 OPERATION dBA internal horn. B524RB Relay base. Each FDX -551 Series uses one of 99 possible addresses B524BI Isolator base. Isolates SLC Loop against on a control panel SLC loop. It responds to regular polls Loop short. from the control panel and it reports its type and status, including the analog level of its heat sensing elements. If Other Accessories it receives a test command from the panel (or a local XR5 Removal Tool. magnet test), it stimulates its electronics and reports an XP -4 Extension Pole for Removal Tool. alarm analog level. It blinks its LEDs when polled and RMK400 Recessed mounting kit for 500 series detec- turns the LEDs on when commanded by the panel (de- tors (requires B501 base). tector blink is optional on the AM2020, AFP1010, and SMK400 Surface Mounting Kit for 500 series detec- AFP-200). The FDX -551 Series offers features and per- tors. Provides for entry of surface wiring formance that represent the latest in thermal detector conduit. A B501 base is required. technology. RA400Z' Remote LED. Mounts to single gang box. o Supported by BX -501 and 8501 bases only. Architectural / Engineering Specifications Specifications are available from Notifier for the AM2020, AFP1010, AFP -200, or System 5000 AIM -200 module on an IBM compatible 3.5" disk in Wordperfect© 5.1 and ASCII for- mats. Page 2 of 2 H -100 8 cPxz551 N OTI Fl ER* Intelligent o a on Detector A Pittway Company Catalog Section: Intelligent/Addressable Devices February 7, 1996 GENERAL California tzr: State Fire The CPX -551 Intelligent Ionization Detector is used with the u , Marshal AM2020 Advanced Multiplex System, AFP1010, AFP -400, ® j -tai 7271 - 0028:149 AFP -200, and System 5000 (w /AIM -200 module) to sense products -of- combustion and report the measured level of such 51115 CS388 1 products in analog form to the control panel. The use of (CPX-551A) analog information provides significant benefits to the end OW6AZ.AY user, installer and serviceman in ways not possible with a �L.I� BSA MEA (AM- 2020/AFP1010) conventional -type system. Since this detector is also addres- I \k tit�l 0V4A5.AY sable, it will help firemen to more quickly locate a fire during ~� 578 -81 -SA 289 -91 -E 93/00141 290 -91 -E (AFP -2 its early stages. OV2A3.A .AY FEATURES US Coast Guard BASES SEPARATELY • Unique unipolar dual chamber provides exceptional stabil- 161•002/27/0 LISTED. CONTACT jt FACTORY. • Factory preset at 1.06% nominal sensitivity for panel alarm threshold level. • Fully coated circuit boards and superior RF /transient protec- tion. • Withstands maximum air velocities up to 1,500 feet - per - - . . y minute without triggering a false alarm. ' " "�- • Addressable by device. 7 _ • Direct Decade 01 -99 entry of address. • 2 -wire loop connection. • Visible LEDs "blink" when the unit is addressed: i '°�- - Optional with AM2020 software release 5 (or higher). .' I 3 ��I' a ' ° . ' - Optional with AFP1010. r ''''=F 4 a ' - - Optional with AFP -200. '' Y, F N. - O with AFP - 400. " " 'S ! • 360° field viewing angle of the visual alarm indicators (two LEDs). LEDs illuminate steady during alarm. I t - - "- _ ,l I • Integral communications and built -in type identification. - • Compact, stylish design. • Remote test feature from the panel. • Built -in functional test switch activated by external magnet. • Low standby current. • 94 -5V plastic flammability rating. • Listed to UL -268. • Removable cover and insect- resistant screen for field clean- • Built -in tamper- resistant feature. ing. • Sounder base option. • Remote LED output connection. • Designed for direct surface or electrical box mounting. 'Optional relay, isolator, or sounder bases. • Sealed against back pressure. APPLICATIONS ° z • Plugs into separate base for ease of installation and main- Use ionization detectors in life -safety applications to provide N tenance. a broad range fire - sensing capability, especially fast, flaming • Separate base allows interchange of photoelectric, ioniza- fires. Where smoldering fires are anticipated, a photoelectric tion and thermal detectors. sensor may provide faster response. This document is not intended to be used for installation purposes. We try to keep our product information up- to-date and accurate. We cannot cover all specific applications or anticipate all ISO -9001 requirements. All specifications are subject to change without notice. For more information, Engineering and Manufacturing contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 Quality System Certified to International Standard ISO -9001 rJ N OTI F I E R. 12 Clintonville Road, Northford, Connecticut 06472 Made in the U.S.A. Page 1 of 2 Location of holes SPECIFICATIONS to access and release Operating Voltage: 15 -28 V (Peak DC). locking prongs. Current Range: 5 mA current for visible LEDs latched on. rl��1t11 _. — Standby Current: 150 iiA maximum. Cover and screen are • removable for cleaning. Detector Standby Current - B524RB or 852481: < 700 uA @ 24 VDC Locking prongs. (includes detector). `0 Sensitivity: 1.5% nominal. Sensor: Unipolar, dual- chamber. Ambient Temp.: 0° to 49 °C (32° to 120 °F). • Relative Humidity: 10% to 93 %. Max. Air Velocity: 2,500 feet -per- minute (without triggering a false alarm). CONSTRUCTION Weight: 5.3 ounces (160 grams). These detectors are constructed of LEXAN® in an off- BX -501 base dia.: 6.1 inches (15.5 cm). white color. • B501: 4.0 inches (10.2 cm). The CPX -551 plug -in series of smoke detectors are de- signed to commercial standards and offer an attractive B524RB Relay Base: Screw terminals: Up to 14 AWG. Relay type: Form -C. appearance. Rating: 2.0 A @ 30 VDC resistive. INSTALLATION 0.3 A @ 110 VDC inductive. The CPX -551 Plug -In Detectors use a separate base to 1.0 A : 30 VDC inductive. Dimensions: 6.2 in. (157 mm) simplify installation, service and maintenance. A spe- x 1.4 in. (36 mm): cially designed tool allows maintenance personnel to plug- Standby: < 700 uA ® 24 VDC. in and remove the sensors without using a ladder. B524BI: Dimensions: 6.2 in. (157 mm) Mount base (all base types) on box which is at least 1.5 x 1.4 in. (36 mm). inches deep. Suitable boxes include: Maximum: 25 devices between • 4° square box isolator bases. • 3-1/2" or 4" octagonal box. PRODUCT LINE INFORMATION • Single -gang box. • Use a 4" square (1.5" deep) box when using the CPX with Model Description the 8501BH'sounder base. CPX -551 Intelligent Ionization Sensor. • Use a 3 -1/2" or 4" octagonal or 4° square base for the CPX -551A Intelligent Ionization Sensor. B524RB or B524B1 base. Canadian (ULC) approved. NOTE: Because of the inherent supervision provided by Bases... the SLC loop, end -of -line resistors are not required. Wir- BX -501 Standard U.S. Base ing '7-taps" or branches are permitted for Style 4 (Class (a base is required for each CPX -551). "B) wiring. B501 Base, flangeless European style. B501 BH Sounder base assembly OPERATION (includes a B501 mounting base) Each CPX -551 uses one of 99 possible addresses on a B524RB Intelligent relay base. System 5000 (w /AIM -200 module), AFP -200, AFP -400, B524B1 Intelligent isolator base. AM2020 Advanced Multiplex System, and AFP1010 SLC Other Accessories... loop. It responds to regular polls from the system and RMK400 Recessed Mounting Kit for 500 Series detectors. reports its type and status, including the analog level of its XR5 Removal Tool. unipolar chamber. If it receives a test command from the XP-4 Extension Pole for Removal Tool. panel (or a local magnet test) it simulates its chamber and RA400Z* Remote LED. Mounts to a single -gang box. reports the analog level. It blinks its LEDs when polled, •Supported by BX - 501 and 8501 bases only. and turns the LEDs on steady when commanded (LED blink is optional on the AFP -200, AFP -400, AFP1010 and ARCHITECTURAL /ENGINEERING AM2020). SPECIFICATIONS a The CPX -551 Intelligent Ionization Sensor's unique unipo- For specifications, request a copy of the Architect/Engineer Speci- ° lar chamber responds quickly and uniformly to a broad range of smoke conditions and can withstand wind gusts fication Disk, available from NOTIFIER Literature Services, on up to 1,500 feet -per- minute without sending an alarm IBM format 3.5" 1.44 Mbyte magnetic disk. This disk includes files level signal. Because of the unipolar chamber, the CPX- in both ASCII and WordPerfect® 5.1 formats. 551 is approximately two times more responsive than WordPerfect® is a registered trademark of the WordPerfect most ionization sensors. This makes it a more stable Corporation. detector. LEXAN® is a registered trademark of General Electric. Page 2 of 2 Sj ectrAlert Horns an ro es .1r SPECTR4 pectrAlert series strobes, horns, and horn/strobes are leading a revolution in design for ADA/UL 1971 compliant products. These easy to install, attractive products feature reduced FIRE current draw FIRE ` � through a redesigned reflector /xenon bulb R( configuration that uses light energy -4• ; '- �: efficiently, minimizing ki 0 , strobe amperage requirements. SpectrAlert also uses no room in the back box, leaving the entire box free for wiring and eliminating the need for a deep back box. • Low current draw: reductions as high as 45% • Two field selectable /reversible tones: • SpectrAlert strobe and horn/strobe take up - 3,000 Hz interrupted zero room in the back box - Electromechanical ■ Easy one -screw mounting of strobe and • Synchronize horn and strobe and silence horn /strobe to mounting plate horn over two wires with optional ■ Field selectable /reversible temporal 3 Sync•CircuitTM module pattern or non - temporal 3 continuous • Horn /strobe can be wired either in tandem pattern horn tones or independently ■ Field selectable /reversible high -low dBA • Universal mounting plate included with each output on horn unit 24 • alth.,- - . ! , _ • . .‘ P Y • • Mounting Plates MDL Sync•CircuittM Module ■ Small Footprint, Universal (included with each • Synchronizes strobes and unit), and Surface Mount Skirt allow mounting horn /strobes of SpectrAlert Series products in any • Allows silencing of horns on a application 2 -wire circuit SPEC7RALERT SERIES HORNS AND STROBES • Avg. mA' Avg. mA' Red White Voltage Candela ® Nom- VDC ® Nom. FWR' . U.S- / Canada U.S. / Canada Hom/Strobes P1215 P1215W 12 15 124 167 P121575 P121575W 12 15/75 152 181 P2415 / P24154 P2415W / P2415 WA 24 15 78 98 P241575 / P141575A P241575W / P241575WA 24 15/75 91 111 P2475 / P2475A P2475W / P2475WA 24 75 148 167 P24110 / P24110A P24110W / P24110WA 14 110 165 209 P241575F ( "FUEGO" lettering for Latin American installations) 24 15/75 91 111 Strobes 51215 51215W 12 15 114 • 157 S121575 5121575W 12 15/75 142 171 52415 / 524154 52415W / 52415WA 14 15 53 80 5241575 / 5241575A 5241575W / 5241575 WA - - - - - - - 24 - - 15/75 - - 66 93 - 52475 / 52475A 52475W / 52475WA 24 75 123 159 524110 /524110A 524110W /S24110WA 24 110 140 191 5241575F ("FUEGO" lettering for Latin American installations) 24 15/75 66 93 Horns H12/24 / 1412/244 H12/24W / H12/24WA 12/24 NA 12 / 23 12 / 21 Syn•crcuit Module MDL / MDLA MOLW / MOLWA 12/24 NA 16 24 Small Footprint Mounting Plate for Single Gang Only S -MP S -MPW NA NA NA NA Surface Mount Back Box Skirt BBS 885W NA NA NA NA Universal Mounting Plate (replacement) D-MP D -MPW NA NA NA NA Agency Listings: UL. ULC FM, CSFM, MEA Canadian model numbers end in "A". Latin American model numbers end in "F". All SpectrAlert products are designed for wall mount only Installation of less than 75 candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.1). However it is the responsibility of the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. . All t 5/75 candela strobes or horn/strobes are recommended for 10' • 10• rooms or less. • For a complete listing of SpectrAlert current requirements, please refer to Inc SpectrAlert Current Draw rable or Installation Manual Horn and horn/strobe current draws assume horn is set at temp 3, electromechanical tone and !ugh audibility. . '• FWR _ Full Wave Rectified 25 Wire Drop Calculation HORN/STROBES ZONE 1 Voltage Applied: 1 „ ‘ Volts Wire Run Length 1130 '1 Feet (one way): --I "' — Wire Run Current 1 0-095 I Amps Wire Size: lig [ - •1 AWG :ill ‘- eZ:Lag Ambient Temperature: Fr - deg. F - z...4mtle- • -- Voltage Drop: 10:1 i : Volts Percent Drop of 10.615 i % System Voltage: End Of Run Voltage: 1 Volts • Wire Drop Calculation DEVICES ZONE 1 Voltage Applied: [ :. Volts Wire Run Length 100.: ..,-, 1 ,, t_, :, , z ; ..:, Fee (one way): - ,'' ..- --- Wire Run Current: I I Amps _,....,;.:,,,-,.....,......' Wire Size: in , i AWG 4.4...„.,*,:.-i: •- __ . Ambient . 1 ,,, 1 Temperature: rt I deg. F Voltage Drop: 1 0.989 Volts Percent Drop of 14.123 i % ' System Voltage: n 1 i it' ' Ithgag End Of Run Voltage: 1 1 Volts ' ' ' Wire Drop Calculation HORN /STROBES ZONE 2 Voltage Applied: 1 =' I Volts Wire Run Length 00:_, 47,:,1 Feet (one way): �r >� f .10 •: Amps tC Wire Run Current: Am s I� CIA � ,,�,; Wire Size: [y'g _ : AWG Ambient Temperature: 1-.! deg. F Voltage Drop: 10.088 a Volts Percent Drop of 10 System Voltage: ' =-� f End Of Run Voltage: (23.91 Volts JOB NAME: THE ROCKWOOD LIBRARY GRINNELL AUTOMATED FIRE ALARM SYSTEM AFP -200 BATTERY CALCULATION WORKSHEETS NORMAL STANDBY CONDITION , ; ALARM CONDITION _ Quantity Load Total Load Total Detectors/Modules /Pull Stations (amps) (amps) • FDX -551 2 x 0.00015 0.00 0.00015 0.00 MMX -101 r 2 x 0.0002 0.00 2 0 0.00 CMX -2 r 2 a 0.0001 0.00 0 0.00 CPX -551 9 x 0.00015 0.00 0 0.00 DHX -501 1 x 0.026 0.03 0.087 0.09 UDACT 1 x 0.04 0.04 0.075 0.08 Spare 0 x 0 0.00 0 0.00 Control Panel Power Supply . - 1 x 0.1 0.10 0.1 0.10 Main Processor Board 1 x 0.098 0.10 0.175 0.18 x 0 0.00 __, 0 0.00 _ x 0 0.00 0 0.00 x 0 0.00 0 0.00 a 0 0.00 0 0.00 Horns /Strobes/Bells P2475ADA 9 ( x 0.00 0.00 0.185 1.67 S2475ADA 2 x 0.00 0.00 0.17 0.34 Sum Total Standby Load (Amy 0.27 Multiply by Standby Time (24 hours) x 24 _ Total Standby AH 6.39 Sum Total Alarm Load (Amps) 2.44 Multiply by Alarm Time (10 minutes) = .166 x 0.083 Total Alarm AH 0.4054218 Total Standby AH 6.39 Total Alarm AH 0.4054218 TOTAL Standby and Alarm AH 6.7954218 Safety Factor (1.2) x 1.2 TOTAL SYSTEM AMPERE HOURS REQUIRED 8.15451 BATTERY SIZE PROVIDED' 14 f110 1.4 S