Loading...
Plans c. 6,6/ aa 90 '4 /5 -1„) //5 ) Sera tqco Fire & Building► Products 1_ 1001 r p - r T_ Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 , .. , E , ; s Y 1 ' ■ a * ye �I� Series TY - FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General mospheres. Although corrosion resis- tant coated sprinklers have passed the standard corrosion tests of the appli- Description cable approval agencies, the testing is i,,„$ not representative of all possible cor - , The Series TY-FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it 8.0 K- factor, Upright and Pendent is recommended that the end user be Sprinklers described in this data sheet consulted with respect to the suitability are quick response - standard cover- of these coatings for any given corro- age, decorative 3 mm glass bulb type sive environment. The effects of ambi- spray sprinklers designed for use in ent temperature, concentration of ,' °-, light or ordinary hazard, commercial chemicals, and gas /chemical velocity, _ -- occupancies such as banks, hotels, should be considered, as a minimum, `` -- shopping malls, etc. along with the corrosive nature of the The recessed version of the Series chemical to which the sprinklers will be - TY-FRB Pendent Sprinkler, where ap- exposed. plicable, is intended for use in areas An intermediate level versions of the with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet , Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- ( cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 recessed adjustment or up to 3/4 inch / Y (19,1 mm) of total adjustment from the WARNINGS flush pendent position, or a two -piece The Series TY - FRB Sprinklers de r - ~• Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and + . inch NPT) Recessed Escutcheon with maintained in compliance with this - 1/4 inch (6,4 mm) of recessed adjust document, as well as with the applica- ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro TY3231 - Pendent 5.6K,1/2 "NPT total adjustment from the flush pen- tection Association, in addition to the TY4131 - Upright 8.0K, 3/4 "NPT dent position. The adjustment provided standards of any other authorities hav TY4231 - Pendent 8.OK, 3/4 ,. NPT by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may the accuracy to which the fixed pipe impair the performance of these de- drops to the sprinklers must be cut. vices. Technical Corrosion resistant coatings, where The owner is responsible for maintain- applicable, are utilized to extend the ing their fire protection system and de- Data life of copper alloy sprinklers beyond vices in proper operating condition. that which would otherwise be ob- The installing contractor or sprinkler Approvals tained when exposed to corrosive at manufacturer should be contacted UL and C -UL Listed. with any questions. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval IMPORTANT information including corrosion resis- Always refer to Technical Data tant status.) Sheet TFP700 for the "INSTALLER Model /Sprinkler WARNING" that provides cautions Maximum Working Pressure with respect to handling and instal- Identification 175 psi (12,1 bar) lation of sprinkler systems and corn- Discharge Coefficient ponents. Improper handling and in- Numbers K = 2.8 GPM /psili (40,3 LPM/bar" " stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM /barli a sprinkler system or its compo TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM /psi (80,6 LPM/bar / nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2"NPT K = 8.0 GPM /psi (115,2 LPM /bar / to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B TY3131 - Upright 5.6K, 1/2"NPT Page 1 of 8 JULY, 2004 TFP171 Page 2 of 8 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 6 �= -1- t 5 2 -t /a" � I ■ = � 7l1s° (57,2 mm) �� B I ( 11 O , M 1 mmINAL ) I ' 4 I � �� �� !I ipi i 1� N MAKE -IN 1 r 2 1- 9/16" `_ 2-3/16" (39,7 mm) WRENCH (55,6 mm) iv ∎ �y i 3 , i . 111 FLATS JP 4 1 7 SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. 1/2" NPT ** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20 PLATE SEATING * * NOMINAL RECESSED • SURFACE NP MAKE-IN ESCUTCHEON SSU* T DEFLECTOR � t ' i S 2-3/16° — I - . 7/16° (55,6 mm) l � � OM ll� I NM ( 11AK,1 mmOMINAE IN L ) I ll � ; 4 i 1-1/2° Or ` 1 2- 3/16° 1 — 2 (38,1i mm) WRENCH (55,6 mm) 3 III -- . FLAT I S 1 SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1 1/2° NPT ** 1 ` 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT Y ` m Finishes Bulb Glass v Sprinkler: Refer to Table A and B Compression Screw Bronze Operation v Recessed Escutcheon: White Coated, Deflector Copper /Bronze 1- Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which B expands when exposed to heat. When 0 the rated temperature is reached, the 'o) Physical Characteristics fluid expands sufficiently to shatter the ¢ Frame Bronze glass Bulb, allowing the sprinkler to E Button Brass /Copper activate and water to flow. a Sealing Assembly o ' Beryllium Nickel w/Teflont } r 4 . t TFP171 Page 3 of 8 ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20 PLATE SEATING * * NOMINAL RECESSED SURFACE NF T MAKE-IN ESCUTCHEON DEFLECTOR 6 I 5 „,- ito � r g r r3 2 -3/16° INN 7/1 m (55,6 mm) � I NOMINAL mm) t NOMINAL 4 � MA -IN w 1-1/2” I 1I 1pi , � � 1 2 3/16" , � 2 (38,1 mm) WRENCH 1 (55,6mm) O 3 ���r - � � � r F LATS = — 1 4 SSP DEFLECTOR * 2-7/8 (73,0 mm) DIA. 1 1/2" NPT ** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2° (12,7 mm) STYLE 30 or 40 PLATE SEATING * * NOMINAL RECESSED SURFACE NP MAKE -IN ESCUTCHEON SSU* T DEFLECTOR 6 __ rrr'T7 =1T�R� 4 T - 1/2° (s 2 -5/16" 5 � Ti!..__Iii � (12,7 mm (58,7 mm) - � � I 1- NOMINAL I ' 4 I ��� MAKE IN ' W ,7 m m) lIj I ijp 1 � 2 -1/4° � 2 ,7 WRENCH (57,2 mm) 9' • (39 -- - _ - -- -.. -- - °• - --- • FLAT 0 3 1 SSP DEFLECTOR * f— 2 -7/8° (73,0 mm) DIA. 3/4° NPT f PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of Design NFPA 13, and FM Approval is based Installation Criteria on the requirements of FM's Loss Pre- vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow - The Series TY-FRB Pendent and Up- eon, as applicable, is to be used for ing instructions: right Sprinklers are intended for fire recessed pendent installations. protection systems designed in ac- NOTES cordance with the standard installation Do not install any bulb type sprinkler if rules recognized by the applicable the bulb is cracked or there is a loss of Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler • Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob- K TYPE TEMP. BULB NATURAL CHROME WHITE*** tained with a torque of 10 to 20 ft.lbs. LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm) of . A maximum ito be of 30 ft.lbs. (40,7 Nm) of torque is to be used d to install sprinklers with 3/4 NPT con - 135°F/57°C Orange nections. Higher levels of torque may PENDENT 155 °F /68 °C Red distort the sprinkler inlet and cause (TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler. and 175 °F /79 °C Yellow Do not attempt to make -up for insuffi- UPRIGHT 200 °F /93 °C Green cient adjustment in the escutcheon (TY1131) 2.8 286 °F /141 °C Blue plate by under- or over - tightening the 1/2" sprinkler. Readjust the position of the NPT 135 °F /57 °C Orange sprinkler fitting to suit. RECESSED 155 °F /68 °C Red PENDENT The Series TY -FRB Pendent and Up- (TY1231)* 175 °F /79 °C Yellow right Sprinklers must be installed in Figure 5 200 °F /93 °C Green 1, 2, 5 accordance with the following instruc- tions. 135 °F /57 °C Orange Step 1. Pendent sprinklers are to be RECESSED 155 °F /68 °C Red installed in the pendent position, and PENDENT upright sprinklers are to be installed in (TY1231)** 175 °F /79 °C Yellow the upright position. Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap- 135 °F /57 °C Orange plied to the pipe threads, hand tighten PENDENT the sprinkler into the sprinkler fitting. 155 °F /68 °C Red (TY2231) _ Step 3. Tighten the sprinkler into the and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type UPRIGHT 2OOF/93°C Green 6 Sprinkler Wrench (Ref. Figure 13). 4.2 (TY2131) With reference to Figures 1, 2, 3, and 286 °F /141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to 1/2" be applied to the sprinkler wrench NPT 135 °F /57 °C Orange flats. RECESSED 155 °F /68 °C Red PENDENT (TY2231)• 175 °F /79 °C Yellow The Series TY -FRB Recessed Pen - Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in accordance with the following instruc- 135°F/57°C Orange tions. RECESSED 155"F/68°C Red Step A. After installing the Style 10. PENDENT 20, 30, or 40 Mounting Plate, as appli- (TY2231) ** 175 °F /79 °C Yellow cable, over the sprinkler threads and Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the pipe threads, hand tighten the sprin- NOTES: kler into the sprinkler fitting. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W -Type Sprinklers. 7 Recessed Sprinkler Wrench (Ref. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- Figure 14). With reference to Figure 1, 5. Approved by the City of New York under ME EA 354 -01 -E. 2, 3, and 4, the W -Type 7 Recessed 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to kiers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in- Recessed Escutcheon, as applicable. stalled or the finish coat has been ap- Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment plied, slide on the Style 10, 20, 30, or Recessed Escutcheon, as applicable. p ty ••• Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY-FRB N/A: Not Available Sprinkler and push the Closure over the Mounting Plate until its flange TABLE A comes in contact with the ceiling. LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint should be present. The diameter of the should be obtained with a torque of 7 air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi - (1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with temperature ratings. 1/2 NPT connections. A leak tight 3/4 4 " TFP171 Page 5 of 8 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE* LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)• 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3231)** 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200 °F /93 °C Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)• 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231) ** 175 °F /79 °C Yellow Figure 12 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research. Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428 -4444 /Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS v • Page 6 of 8 TFP171 2 -7/8° DIA. 2.7/8° DIA. 5/8±1/4° (73,0 mm) 3/4° (19,1 mm) 1/2±1/8° (73,0 mm) 1/2' (12,7 mm) (15,9±6,4 mm) 2 -1/4° DIA. 1 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1 /8° 1/8° II ./. ra 0 ., G• r l MOUNTING 111/ MOUNTING I SURFAC . SURFACE ��r•ti,. ,,r, -,��� , CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm) TY -FRB 13/16° (20,6 mm) TY-FRB 1 -1/16° (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT • 2 -7/8° DIA. 2 -7/8° DIA. 5/8 ±1/4° (73,0 mm) 3/4° (19,1 mm) 1/2±1/8° (73,0 mm) 1/2° (12,7 mm) (15,9±6,4 mm) 2 -114' DIA. 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° •�' (3,2 mm) •� ( 3,2 mm) • ILU , Ili � ' MOUNTING MOUNTING : SURFACE ■ SURFACE -- - .. -- CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm) TY -FRB 3/4° (19,1 mm) TY -FRB 1° (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT used to cover a clearance hole, may and after installation. Sprinklers dam - Care and delay the time to sprinkler operation in aged by dropping, striking, wrench M • a fire situation. twist/slippage, or the like, must be re- aintenance Sprinklers that are found to be leaking has a cracked p bulb or that lost The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec- NOTES painted, plated, coated or otherwise ommended to be initially performed for corrosion altered after leaving the factory. Modi ion resistant coated sprinklers, Before closing a fire protection system fied sprinklers must be replaced. p after the installation has been com main control valve for maintenance Sprinklers that have been exposed to work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor- it controls, permission to shut down the have not operated, should be replaced rosion resistant coating. Thereafter, affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25 o btained from the proper authorities b y wiping the sprinkler with a cloth or should suffice; however, instead of in and all personnel who maybe affected by brushing it with a soft bristle brush. spectin from the floor le a random by this action must be notified. sampling of close -up v i nspec- Care must be exercised to avoid dam- tions should be made, so as to better • Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- it ., TFP171 Page 7 of 8 • 2 -7/8' DIA. 2 -7/8' DIA. 5/8±1/4' (73,0 mm) 3/4° (19,1 mm) 1/2±1/8' (73,0 mm) 1/2' (12,7 mm) (15,91-6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' 1/8' M •�' (3,2 mm) •� (3,2 mm) - 111, M_- �lglf O i f \ izA u m .- All (), � , f MOUNTING MOUNTING , SURFAC VP SURFACE -_ - =_ ;_._ „_ T CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA. 2 -7/8' DIA. 5/8±1/4' (73,0 mm) 3/4' (19,1 mm) 1/2±1/8' (73,0 mm) 1/2' (12,7 mm) (15,9±6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) - 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING • FITTING 1/8' 1/8' v 1 .if; (3,2 mm) , ' Ili (3,2 mm) , N i - /_ —� , Nv A x+, - 111 % - , M OUNTING MOUN . SURFACE 1 SURFACE � CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm) TY -FRB 13/16' (20,6 mm) TY-FRB 1 -1/16' (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may e WRENCH be affected by the corrosive conditions RECESS present. WRENCH RECESS h!- The owner is responsible for the in- (END °A° USED FOR spection, testing, and maintenance of 1/2° NPT MODELS) ' f \ i ' their fire protection system and de- �. vices in compliance with this docu- ment, as well as with the applicable ` , standards of the National Fire Protec- WRENCH RECESS (END °B” PUSH WRENCH tion Association (e.g., NFPA 25), in ( USED FOR IN TO ENSURE addition to the standards of any other 3/4° NPT MODELS) ENGAGEMENT authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturer should be contacted relative to W - TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, local requirements and /or national W - TYPE 7 RECESSED tested, and maintained by a qualified codes. SPRINKLER WRENCH • Inspection Service in accordance with c . • Page 8 of 8 TFP171 P/N 57 - XXX - X - XXX i I TEMPERATURE MODEUSIN RATING SPRINKLER _ . 330 2.8K UPRIGHT (1 /2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C ,. 340 4.2K UPRIGHT (1 /2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1 /2 "NPT) TY2231 3 WHITE (RAL9010)" 200 200 °F /93 °C 370 5.6K UPRIGHT (1 /2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1 /2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3 /4 "NPT) TY4131 391 8.0K PENDENT (3 /4 "NPT) TY4231 ' Eastern Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon: Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es- DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N Warranty LIMITED TO LABOR CHARGES, RE- (specify). . GARDLESS OF WHETHER TYCO Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2' (15 mm) Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P /N56- 701 -9-010 • against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010 manship when paid for and properly ABILITY EXCEED AN AMOUNT WhitsRAL9010• P/N 56-701-3-010 Brass Plated P/N 56- 701 -2 -010 installed and maintained under normal EQUAL TO THE SALES PRICE. use and service. This warranty will ex THE FOREGOING WARRANTY IS 1/2" (15 mm) pire ten (10) years from date of ship- Style 20 ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9 -010 ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56-705-4-010 components manufactured by compa- IMPLIED. INCLUDING WARRANTIES White RAL9010" P/N 56- 705 -3 -010 Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT Brass Plated P/N 56- 705 -2 -010 Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4• (20 mm) components which have been subject POSE, Style 30 to misuse, improper installation, corro- Chrome Plated P/N 56- 705 -9 -011 sion, or which have not been installed, White Coated P/N 56 -705 -4 -011 maintained, modified or repaired in ac- White Plated o' P/N 56- 705 -3 -011 cordance with applicable Standards of r der�ng Brass Plated P/N 56- 705 -2 -011 the National Fire Protection Associa- Procedure 3/4° (20 mm) tion, and /or the standards of any other Style 40 Authorities Having Jurisdiction. Mate- eontaiatvgun local distributor for avail- Chrome Plated P/N 56- 700 -9 -010 rials found by Tyco Fire Products to be abq y. indicate the White Coated P/N 56 -700 -4 -010 defective shall be either repaired or WI product White RAL9010• P/N 56 -700 -3 -010 replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700 -2 -010 o option. Tyco Fire Products neither as- the complete List for p y complete listing 'Eastern Hemisphere sales only. sumes, nor authorizes any person to of Part Numbers. assume for it, any other obligation in Sprinkler Wrench: connection with the sale of products or Sprinkler Assemblies with NPT Specify: W - Type 6 Sprinkler Wrench, parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387. shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench, incomplete information supplied by temperature rating), Series TY FRB P/N 56- 850 -4 -001. Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating), • PRODUCTS BE LIABLE, IN CON- P/N (specify from Table C). TRACT, TORT, STRICT LIABILITY OR ' UNDER ANY OTHER LEGAL THE - TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446