Correspondence City of Tigard, Oregon • 13125 SWHall Blvd. • Tigard, OR 97223 •
July 19, 2007
® .
RE: MECHANICAL TI
4N t 'ro'' '+. Y L4 ¥E
oTIRRD
Project Information
Building Permit•. MEC2007 -00435 Construction Type: IIIB
Tenant Name: Pacstar Occupancy Type: B
Address: 15055 SW Sequoia Occupant Load: 120
Area: NA. Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
submitted plans are approved subject to the following
GENERAL
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
3. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
4. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
5. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
6. Smoke detectors shall be installed in return air systems with a design capacity greater
than 2000 cfm. Upon activation, the smoke detector shall shut down the air
distribution system. Smoke detectors shall be connected to a fire alarm system and
shall activate an audible and visible alarm at a constantly attended location. 606.2,
606.4 & 606.4.1 OMSC
7. VAV boxes shall be supported by non - combustible elements that are designed and
constructed to accommodate the weight and dynamic loads and shall be sway braced.
920.2 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
-1 ' 0010
Dan Nelson,
Senior Plans Examiner