Correspondence Gia Ih
June 1, 2004 �" ''
CITY OF TIGARD
Martin W. Hanson O REGON
PacTrust
15350 SW Sequoia Parkway, Suite 300
Portland, OR 97224
RE: TENANT MODIFICATION
Project Information
Building Permit: BUP2004 -00236 Occupancy Type: B
Tenant Name: Pacific Star Communication Construction Type: VN
Address: 15055 SW Sequoia Parkway, #100 Occupant Load: 148
Area: 12,999 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following conditions.
1. The main exit shall be provided with signage indicating "THIS DOOR MUST
REMAIN UNLOCKED DURING BUSINESS HOURS" Section 1003.3.1.8 OSSC
2. Exit doors shall be provided with panic hardware.1007.2.5 OSSC
3. Exit signs shall be illuminated at all times and shall be provided with a second source
of power that will provide 1 '/2 hours of illumination in case of primary power loss.
1003.2.8.5 OSSC
4. The means of egress shall be provided with illumination of not less than 1 foot candle
at the floor level anytime the building is occupied. The means of egress illumination
shall be provided with a second source of power in case of primary power
1003.2.9.2 OSSC
5. Provide a 2 -A rated fire extinguisher located so that no usable space has a distance
greater than 75 feet to the extinguisher. Standard 10 -1, Chapter 3 TVFR99 -01.
FYI Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings,
etc, will be charged a deferred submittal fee based on the valuation of the portion of
the work being deferred. The minimum fee shall be $200.00.
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the
Building Official has issued a certificate of occupancy 109.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and proces '.: _ he documents.
Respectful ,
an B . "I ck,
Senio ' lans Examiner