RE: TI OREGON COMMUNITY CREDIT UNION - REVIEW
Project Information
Building Permit: BUP2005 -00442 Construction Type: 5 -B Sprinidered
Tenant Name: Oregon Community Credit Union Occupancy Type: B
Address: 12280 SW Scholls Ferry Rd Occupant Load: 23
Area: 2,007 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are
approved subject to the following conditions.
1. Storage room; Where Table 302.1.1 permits an automatic fire- extinguishing system
without a fire barrier, the incidental use area shall be separated by construction capable
of resisting the passage of smoke. The partitions shall extend from the floor to the
underside of the fire- resistance -rated floor /ceiling assembly or fire- resistance -rated
roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be
self - closing or automatic- closing upon detection of smoke. Doors shall not have air
transfer openings and shall not be undercut in excess of the clearance permitted in
accordance with NFPA 80.
2. Exits and exit access doors shall be marked by an approved exit sign readily visible from any
• direction of egress travel. Access to exits shall be marked by readily visible exit signs in
cases where the exit or the path of egress travel is not immediately visible to the occupants.
1011.1 OSSC
3. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
4. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 'h hours of illumination in case of primary power loss. 1006.3 OSSC
FYI Additional exit signs may be required by the city field inspector to clearly indicate the
path of egress.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
NOT PART OF THIS REVIEW:
* Electrical * Sprinklers
* Mechanical * Plumbing
5. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in
such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respect
Val Henzel,
Senior Plans Examiner