Loading...
Correspondence ti L0 June 4, 1997 I � CITY OF TIGARD Oregon Electric Group 1010 SE 11th OREGON Portland, OR 97214 RE: Sister of Providence Building Plan Review 6640 SW Redwood Lane PC #: 5 -175c BUP #: 97 -0287 97 -0284 97 -0285 97 -0286 4-30k, NOTICE TO APPLICANT Under the provisions of the Oregon Structural Specialty Code and National Fire Code, an alarm system is not required for the subject structure. The plan review and subsequent permit issuance is based on compliance to OSSC, Section 1109.1.4 and NFC, Section 1007.3.3. With this in mind, the following items require your attention. 1. Drawing E 6.20S - Provide a pull station near line 5c on the wall at the exit stairs, across from the elevator, and a strobe in stairwell, line 3c. ve 2. Drawing E 6.30S - Provide a strobe at 3rd floor landing, line 6b. t o 3 Drawing E 6.1 P - Provide a strobe in corridor 345. �. Drawing E 6.1P - Provide a pull station adjacent to exit door in corridor 337. Drawing E 6.1 - Provide a pull station behind door entering rooms 322 - 321 - 319, corridor 320. 6. Drawing E 6.1 - Provide a strobe in toilet room 311. Please submit four copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, 0;26.--) R ert Poskin, CB® PLANS EXAMINER 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 l q7 -06 (P OREGON ELECTRIC 3 D GROUP Ili ��I�USi 0t CusfoaFY ("0fi;i,MIi TRANSMITTAL I • TO: Robert Poskin DATE: June '19, 1997 NAME City of Tigard Oregon COMPANY NAME 1325 SW Hall Blvd. • ADDRESS Tigard, OR 97223 CITY, STATE, ZIP REFERENCE: Copies of Orthopedic and Fracture Clinic revised fire alarm drawings. Job #'s 12392, 18030, 18041 and 18042. THE FOLLOWING ITEM S ARE TRANSMITTED: NUMBER ITEM COPIES DATED DESCRIPTION (1) 4 Sets June 19, 1997 Orthopedic and Fracture Clinic drawing copies, cosisting of pages, E6 -1, E6-1P, E6 -20S and E6 -3os. (2) 1 June 19, 1997 Letter of comment. REMARKS: Mr. Poskin: These drawings have been revised per your letter and our telephone conversation. If you have any questions regarding these drawings, please do not hesitate to call. Thank you, cc: file Cityoftigardtrans By: David Nixon 1010 S.E. 11TH AVENUE • PORTLAND, OREGON 97214 -2507 (503) 234 -9900 • FAX (503) 234-1001 — CCB #203 "An Equal Opportunity Company" 'Waal Ekttrti mpap.g,