Correspondence
• June 4, 1997 .ter - �' ° 1_� Oregon Electric Group CITY OF TIGARD 1010 SE 11th O REGON Portland, OR 97214 RE: Sister of Providence Building Plan Review 6640 SW Redwood Lane PC #: 5 -175c BUP #: 97 -0287 97 -0284 97 -0285 -T— 3 03 97 -0286 NOTICE TO APPLICANT Under the provisions of the Oregon Structural Specialty Code and National Fire Code, an alarm system is not required for the subject structure. The plan review and subsequent permit issuance is based on compliance to OSSC, Section 1109.1.4 and NFC, Section 1007.3.3. With this in mind, the following items require your attention. ,1. Drawing E 6.20S - Provide a pull station near line 5c on the wall at the exit stairs, across from the elevator, and a strobe in stairwell, line 3c. ve 2. Drawing E 6.30S - Provide a strobe at 3rd floor landing, line 6b. (1 3. Drawing E 6.1P - Provide a strobe in corridor 345. v 4 Drawing E 6.1P - Provide a pull station adjacent to exit door in corridor 337. (J -. Li t V Drawing E 6.1 - Provide a pull station behind door entering rooms 322 - 321 - 319, corridor 320. 6. Drawing E 6.1 - Provide a strobe in toilet room 311. Please submit four copies, of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, R ert Poskin, CB© PLANS EXAMINER 13125 SW Hail Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772