August 15, 1996 - I
CITY OF TIGA R D
Milne Construction
1312 SW 16th Avenue O REGON
Portland, OR 97201
RE: Professional Autobody Building Plan Review
11643 SW Pacific Hwy #13
PC #: 4 -56c BUP #: 96 -0196 •
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
ACGES$iBI ITI o . � . _
wg . -�iY � . ''� . ~eP � r ... .z�» -.. -..y� ': "?tC 7�� F� ^"'�' • d c-. a:i I
1. An amount equal to 25% of the remodeling cost shall be budgeted for removal of
architectural barriers within the site and tenant space.
A. Barrier removal is determined in accordance with OSSC, Section
1113.1.1., ORS 447.241 (4).
B. The barrier removal plan shall include exterior improvements.
.S - IXF �
1. Provide a Type 4A -40B fire extinguisher within 30 feet of each main door [NFPA
10- 1 -3 -2].
2. All metal parts of the spray booth, exhaust duct, and piping shall be electrically
grounded [NFPA -NEC 70, Article 516- 4(G)].
3. The booth shall have two exits separated a distance apart not less than 1/2 of
the diagonal measurement of the booth [OSSC, Section 1018].
I MECHANic k : A •
.. _ CAL r,:�'� -,'+._ 4- .w k :2;^.'+..:_"3 .
1. Submit a mechanical permit application and three sets of plans with
specifications for the ventilation system (ducting, motor, fan), make -up air
system, and interlocking controls [UFC, Section 4502.5.1 and OMSC, Section
505.6].
2. Is the existing fan shown on the original submittal an exhaust or supply fan?
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
•
Professional Autobody Building Plan Review
PC#: 4-56c BUP#: 96-0196 .
• Page #2
—
• - - ' � `j tj l `''�^z-! t`d`Sk�' +„`1's? '�i:.'`' y:h . 'wg[r ..
i a 'tixAa eft 2 �ry
- — A ��'^�� '
1. Submit a fire suppression permit application and three (3) sets of plans and
component cut sheets and specifications [UFC, Section 4502.8.1 and OMSC,
Section 609.7].
Please submit three copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
Jim Funk -
PLANS EXAMINER
i:■citywide\pc4- 56c.doc
•