From: Hettervig, Paul <phettervig @pmc- g.com>
Sent: Thursday, May 24, 2012 11:04 AM
To: Dan Nelson
Subject: RE: Plan review for Burgerville Hood
Attachments: Burgerville Tigard- Drawings - SHOP.PDF •
Dan
Attached are the shop drawings. The hood O &M is found here, which has detailed
instruction on hanging the hood. The grease duct O &M is found here, which has detailed instruction installation. The
grease duct is ETL listed under file number 1000082319SAT -006 EEV and complies with UL 1978 and UL 2221
standards. If there are any questions, don't hesitate to respond.
Please let me know if this is acceptable or if you need anything else.
Thanks,
Paul.
Paul Hettervig
Sheet Metal Division Manager
Plumbing Mechanical Contractors Group.
2000 SE Hanna Harvester Dr
Milwaukie, Or 97222
PH# 503 - 656 -7400
Cel# 503 - 804 -6569
Fax# 503 - 655 -0620
•
From: Dan Nelson jmailto:DanNC�tigard- or.govl
Sent: Thursday, May 24, 2012 9:48 AM
To: Hettervig, Paul
Subject: Plan review for Burgerville Hood •
Dan Nelson
Senior Plans Examiner
City of Tigard •
dannC tigard- or.gov
(503)718 -2436
F(503)624 -3681
•
•
DISCLAIMER: E -mails sent or received by City of Tigard employees are subject to' public record laws. If requested, e-mail
1
RE: COMMERCIAL EXHAUST HOODS r I
�� � rrF._ce V1G
Project Information
•
Building Permit: MEC2012 -00269 Occupancy Type: A -2
Tenant Name: Burgerville Construction Type: 5B
Address: 12785 SW Pacific Hwy. Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2010 edition and The Oregon Fire Code 2010 edition. The following corrections
need to be submitted for review prior to issuing of the permit.
1) Please provide drawings showing connection of hood to structure.
2) Please provide connection details of makeup air unit on roof.
3) Provide listing and installation instructions for grease duct.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
•
RE: COMMERCIAL EXHAUST HOODS
Project Information
Building Permit: MEC2012 -00269 Occupancy Type: A -2
Tenant Name: Burgerville Construction Type: 5B
Address: 12785 SW Pacific Hwy. Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2010 edition and The Oregon Fire Code 2010 edition
Ducts exposed to the outside atmosphere shall be protected against corrosion in an
approved manner. 506.2 OMSC
A Performance Test shall be conducted upon completion and before final approval of
the installation of the ventilation system. The performance test shall verify the rate of
airflow to be in compliance with the approved plans. 507.17 OMSC
The exhaust and make -up air system shall be electronically interlocked to ensure that
the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC
An automatic fire suppression system shall be provided to protect the surface of the
heat - processing appliances and the exhaust system serving the appliances. 509.2
OMSC
Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be
provided with a permanent means of access grade or floor level. 306.5 OMSC
Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Exhaust fan mounting An upblast fan shall be hinged and supplied with a flexible
weatherproof electrical cable to permit inspection and cleaning. The ductwork shall
extend a minimum of 18 inches (457 mm) above the roof surface. OMSC 506.5.3
Supports Type I hoods shall be secured in place by noncombustible supports. All Type
I and Type II hood supports shall be adequate for the applied load of the hood, the
unsupported ductwork, the effluent loading, and the possible weight of personnel
working in or on the hood. OMSC 507.6
•
Compensating hoods Manufacturers of compensating hoods shall provide label
indicating minimum exhaust flow and /or maximum makeup airflow that provides capture
and containment of the exhaust effluent. OMSC 508.2
• All deep -fat fryers shall be installed with at least a 406 mm (16 in.) space
between the fryer and surface flames from adjacent cooking equipment. 12.1.2.4
• Where a steel or tempered glass baffle plate is installed at a minimum 203 mm (8
in.) in height between the fryer and surface flames of the adjacent appliance, the
requirement for a 406 mm (16 in.) space shall not apply. 12.1.2.5
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents. ;.
•
Respectfully,
Dan Nelson,
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
•