Correspondence , -- CITY OF TIGAR OREGON November 15, 2001 FILE COP Encompass Mechanical 5711 SW Hood Portland, OR 97201 Re: Cameron Plaza — Permit # MEC2001 -00343 8060 SW Pfaffle Tigard, OR The City of Tigard has completed the review of the submitted plans for the mechanical installation at the above referenced address. This review was performed under the provisions of the State of Oregon Mechanical Specialty Code (OMSC), 1999 edition. The plans are approved subject to the following conditions. 1. Smoke detection shall be provided in the return -air duct of this system. OMSC Section 606. 2. The plans appear to show the ceiling as a return-air plenum. All materials installed in this return-air plenum shall meet the requirements of OMSC Section 602 or be plenum rated by testing. 3. The gas piping shall be tested to ensure that it is gas tight in accordance with OMSC Section 1304.18. 4. A copy of the approved plans shall be on the job site and available to the inspector for inspection purposes at all times. Sincerely, Gary Lampella Building Official c. File • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772