Plans Range Guard wet chemical fire system.
Model RG -4G. 4 gallon capacity. Duct: 10 "x20"
Flow point capacity: 12
Flow points used: 12
Fusible Links
ADP
8 8
15' Type I Hood
- - Single Filter Bank
ADP ADP
B e Q 9(Et 9 9
R R ADP ADP ADP ADP F
13" 13" 13" 13"
20" 20" 27"
42" 48" 48" 48" 48" 45"
O
Remote OFFICE COPY
Manual K
Actuator Class
(in egress)
I I I I I I I
Automatic gas shut 36 "x24" 72 "x24" Griddle 48 "x24" 14 "x15"
off valve. Range Griddle Fryer CITY OF TIGARD
Approved [)11
Conditionally Approved [ ]
See Letter to: Follow [ ]
Attached [ ]
Fire System Drawing Permit Number: T PS x(11 -CV0 S5
Address: 6 v S 4c - .
Front View
By: JAM/Date: ' - 1z -- �i - ma c /
Guardian Fire Protection Job: Biscuits Cafe Notes: Fire system installed in accordance with Range
1012 SW A Avenue Guard technical manual P/N 9127000.
Corvallis OR 97333 Tigard OR UL 300 tested and approved. ULEX -2458
CCB 100355 ex 6/10 Date: 02/09 Drawn by: MAF
05/28/2009 13:40 5417524259 GUARDIAN FIRE PAGE 02/03
The Wet Chemical Fire Suppression System MICE y :..
3-21 Nozzle Summary
•
•
Table 3 -2. Nozzle Summary •
Perimeter Diameter Nozzle!
Hazard Max. Max. Length Flow No.
Duct 50" (165.1 an) 15.25" (39 cm) Unlimited. ADP 11
,.•< ::>vY:.Y w i:i.E is : :- t is i ;` :' jj ��yy
:... .:,..,: Y::,;;;l:.s. -s•.:. . :::. ;:, :.... .. )::�:. s: Yn <e; <.Y i. , .: : vi<M:YI<a.. ,,: . ! F ....... ... .a. .:, ,..<
Length Width Nozzle,/
Hazard , Max. Max. Filters Flow No.
Plenum 10' (3.0 m) 4' (1.2 m) "V" Bank or
Single ADP/1
Hazard Size . Nozzle Height .Notes • Nozzle/
Hazard Inc:hes /cm .Incheslcrll Inches /cm Flow
Four Bunter Range 28 X 28 (71 x 71) 2Oto 42 (521o107) within 9 (23) rad.
of midpoint R
Single Vat Deep Fat Fryer (Drip Boards 1 t o 6 [25 to18)) 18X 18 (46 x 46) 27 to 45 (69 to114) 45° to 90' F/2
4 E ,:y:: :, 7,..
Split Vat Deep Fat Fryer 14x15(36x38) 27 (69)to45 (117) 45 °to90° F2
i+(
Woks 14 to 28 (36 to 71) Dia, within 2 (5)
310 8 (810 20) Deep 35 to 56 (89 t o 142) o f mid point. GRW I t
1
X
Closed Top Chain Broilers 28 X 29 (71 x 74) See 3 -12 See 3 !.: ADP / 1 .
xY,
Pumice Rock (Lava, Ceramic) Charbroier 22 X 23 (56 x58) 24 (61) to 48 (122) 45' [0 90';
I avers of rock F12
„i:j %J. y .,r , :i•<::: aii ['Y,no ":.l' tai«" -
rcoalC
I�
,.,..: i,::, J ................... :: ,.. .:. :. :..:,.: r: ..: n:. v:<: ::,:.:.v:,..:.,:...ki:::.Yr �:....v; - . : •: ...n;::`vi ^L .: •: /.:
,.:r. ......s::.: YS S::.Y:;::..,o.a... <a:c;es:.•:w: ,: y.a.::::::nv: ;;; :;: %r: ............
Elecmc Charbroiler (Open Grid) 24 X 21 (61 x 53) 24(61)1048 (122) 45 °1090` GRIN / 1
0.s'�'. : . p � , �� yr. � r'i;�`s`::::':�:e' .•�' ..:�"x >:�:� .,2. ..), Z�4/ f..' 1i. ����tt :s'1A)�`: « >:�:<>
.... ::: >n.vna :..:.: :n• :..•,,•.i .,:.:::, :. :..N.:' :�.1,.<,. „.,:.:r:.:, •�a:l:,v..:..:.:,w.v.:. .,., >.v w: v. n•. • Y :
Mesquite Charbroller (Ch ips, Wood, Logs) 30 X 24 (76 x 61) 24 (61) to 48 (122) 45' to 90 °;
10(25) Fueldepth DM / 3
. 133 : g< <: `tR Vg;::;
stir ��i:•
Fr;
Tilt Skilletand Braising Pan 24 x 24 (61 x 61) 27.6 in (70 cm) to 46 in (117 cm)
• within perimeter F / 2
• Nozle Nozzle Part
Identification
• No. • Flow No. •
ADP(Appliance- Duct - Plenum) C120011 1
^iFx.y,:
GRW (Gas Radiant -Wok) C120013 1
•
14 a:,•:o. ... ....................... n, ........... :....,a....... sots: :ar.,.. `,frwY... n: :is; a::=.;rt' %... ' ?'sf:.
DM(Mesquite) , C120015 3
•
• U,L,I. Ex 2458 3 Manual Part No. 9127100 (9/97) Badger Fire ProtactIon
05/28/2009 13:40 5417524259 GUARDIAN FIRE PAGE 03/03
-ti
ki4k1OR:01 The Wet Chemical Fire Suppression System
3-22 Cylinder Sizing
Alter finding how many nozzles of each type are required for a system, the sum of all the nozzle flow numbers is
used to determine the number and size of the cylinders required, in acxordance with the cylinder flow number
limits given below. •
Table 34. Cylinder Flow Number Limits
Maximum Flow Numbers of Cylinders
Cylinder Flow Number
RG -1.25G (4,7 L) 4
Single Cylinder Only
(Cannot Manifold)
of iN< }lp
C.):N
RG-4GT or RG-4G&
(15 L)(Long or Short
1 Cylinder 12
2Cylinders 24 Can Manifold
3 Cylinders 36 Up to 4 Cylinders
4 Cylinders as • •
ffl�� :.5'l'•
2 {�
•y�: ��y
a rri�3
Only like cylinders can be manifolded (ie, four RG -4GS, two RG -6G.)
The system can be actuated through various controls, in accordance with Table 3-4. TO actuate a single cylinder
system, use either the Mechanical or Electric Control Head or the A+ Control Box with pressure operated actuator.
To actuate two or three cylinders, use either one or two Tandem Control Heads and a Mechanical or Electric
Control Head or the A+ Control sox with 1 -3 Pressure Operated Actuator(s). To actuate from 1 to 5 cylinders, the
A+ Control Box with Pressure Operated Actuator(s) must be used. For applications requiring 5 -10 cylinders the
BMCS -1 nitrogen releasing system is recommended. Larger systems, 10-100 cylinders, the BMCS -7 nitrogen
releasing system is the recommended means of cylinder actuation. For complete details of the BMCS -i and BMCS-
7 systems, refer to each respective manuals, P/N B900002 and P/N B9000003,
Table 3-4. Actuation Controls
Mechanical or Electric Tandem A+ Control
System Size Control Head Control Head Box BMCS -1 SMCS-7
•
1 Cylinder ,
2 Cylinders
3 Cylinders ■/** •
4 Cylinders /•• J �•.+
•
5 Cylinders , / *• , / i *"
5-10 Cylinders �• - -•.
10+ Cylinders • /• - ° «. ,«
° Requires both a mechanical or electric control head and tandem control head
** Requires a mechanical or electric control head and multiple tandem control heads
* * *BMCS series requires a mechnical or electric control head to actuate.
U.LI.
Ex 2458 3 Manual Pan No. 91271(10 (9(97) Badger Fire Protection