Correspondence ( 11/11 CITY OF TIGARD September 25, 2003 OREGON Boulder Engineering Clifford D. Holmes 811 West Cedar Phone: (208) 478 -4613 Pocatello ID 83201 Fax: (208) 478 -4617 RE: ELECTRICAL PLANS REVIEW Dear Mr. Holmes: Project Information Permit: ELC 2002 -00245 Tenant: Space Age Fuel Address: 16875 SW Pacific Hwy. This plans review is based on the 2002 edition of the National Electrical Code (NEC). The revisions received on September 18, 2003 have been reviewed and are not approved as submitted. The following items shall be revised (revisions clouded) on the plans and addressed in a response letter. Two complete sets of the revised plans and the response letter shall be submitted to this office for review and approval prior to issuance of the electrical permit. Please note: Loose pages are not acceptable. 1. Explain to which "kitchen equipment" the demand factor of .65 is applied. to and how does the equipment complies with the provisions of Article 220.20. 2. Revise the grounding detail to include the rebar of the building. See Article 250.50 If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446. Sincerely, Herb Stabenow Plans Reviewer C:Boyles Electric • file 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772