Correspondence 2 -10 -1998 12 :09PM • FROM MCGINNIS- ENGINEERING 503 794 0435 P. 1
A2 c 97 -6J y34
'McGinnis Engineering
MECHANICAL CONSULTANTS
14030 S.E. Rupert Drive • Milwoukie, OR 97267
(503) 794-0434 • FAX (503) 794.0435
February 10, 1998
Mr. Jerry Bennett
Super One Inc.
10950 SW Fifth
Beaverton, OR 97005
Re: Best Western Motel, 16105 SW Pacific Highway
Dear Jerry:
The following change is required on Sheet M 1; add 1 -Hr fire dampers in two 10 -inch dia. ducts
penitrating the One Hour wall at the Pool for EF -7 & OA to F -3,
Please call if you have questions.
Sincerely, ,cia FR OF ,
Larry R. McGinnis, P.E. ` ` �,�� •
Go
cc,Robert D. Poskin,C.B 4>1.- .O. ' 9 ,p 1.- > . X96~ `'�
M cG`
R.
•
•
CITY OF TIGARD
February 5, 1998 OREGON
Super 1, Inc. •
10950 SW Fifth
Suite #150
Beaverton, OR. 97005
RE: Best Western Motel PC# 11 -2
16105 SW Pacific Highway MEC# 97 -0436
Your Mechanical drawings have been reviewed for compliance to the Oregon Mechanical
Specialty Code, the following items require your attention.
1. Provide fire dampers at the horizontal penetrations into the pool area, from units labeled
RT -1, EF -7, and RT -1. This wall is a one -hour separation from the motel.
If you have questions, please feel free to call me at 639 -4171 X 392.
Sincerely,
Rob D. Poskin, C.B.O.
Plans Examiner