RE: Noah's Bagel Mechanical Plan Review
15660 SW Pacific Hwy #A -4
PC #: 7 -73c MEC #: 96 -0247
Submittal documents for the above referenced project have been reviewed for
confor ance with the applicable 1996 Oregon Specialty Codes and other applicable
code and standards. The following comments are noted:
1 The mechanical system shall provide outside air for each occupant in all portions
of the building [OSSC, Section 1202.2.1, Table 12 -P].
ij A. Specify on the plan the amount of outside air provided for the occupancy
[OSSC, Section 1202.2.1].
The amount of BTU's being provided exceeds that of a simple HVAC system -
[OSSC, Section 1313.2]. Provide a schedule on the plan setting forth the
requirements' and specifications for compliance with a complex HVAC system
I [OSSC, Section 1313.3]. '°
P -P. Provide an engineer's analysis of each structural member supporting the
additional HVAC units [OSSC, Section 106.3.2].
Each individual roof - mounted HVAC shall be permanently labeled as to the areas
it serves [OMSC, Section 304.5]. In addition, each unit shall be equipped with a
power disconnect and a 120 -volt receptacle shall be located within 25' of each
unit [UMC, Section 309.1].
Please submit three copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.