Loading...
Correspondence (------ August 12, 1996 CITY OF TIGARD HVAC Inc. 815 SE Sherman OREGON Portland, OR 97214 RE: Noah's Bagel Mechanical Plan Review 15660 SW Pacific Hwy #A -4 PC #: 7 -73c MEC #: 96 -0247 Submittal documents for the above referenced project have been reviewed for confor ance with the applicable 1996 Oregon Specialty Codes and other applicable code and standards. The following comments are noted: 1 The mechanical system shall provide outside air for each occupant in all portions of the building [OSSC, Section 1202.2.1, Table 12 -P]. ij A. Specify on the plan the amount of outside air provided for the occupancy [OSSC, Section 1202.2.1]. The amount of BTU's being provided exceeds that of a simple HVAC system - [OSSC, Section 1313.2]. Provide a schedule on the plan setting forth the requirements' and specifications for compliance with a complex HVAC system I [OSSC, Section 1313.3]. '° P -P. Provide an engineer's analysis of each structural member supporting the additional HVAC units [OSSC, Section 106.3.2]. Each individual roof - mounted HVAC shall be permanently labeled as to the areas it serves [OMSC, Section 304.5]. In addition, each unit shall be equipped with a power disconnect and a 120 -volt receptacle shall be located within 25' of each unit [UMC, Section 309.1]. Please submit three copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, ., Jim Funk PLANS EXAMINER i:\citywide\pc7- 73c.doc • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772