Correspondence (74 � February 18, 2004 CITY OF TIGARD Pete Russell OREGON Source Refrigeration 5506 SE International Way Milwaukie, OR 97222 RE: REMODEL REFRIGERATION SYSTEM Building Permit: MEC2004 -00015 Construction Type: III -N Tenant Name: Safeway Occupancy Type: M Address: 15570 SW Pacific Highway Occupant Load: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The submitted plans are approved subject to the following. FIELD TESTS • Every refrigerant- containing part of every system that is erected on the premises, except compressors, condensers, vessels, evaporators, safety devices, pressure gauges and control mechanisms that are listed and factory tested, shall be tested and proved tight after complete installation before operation. Tests shall include both the high- and low- pressure sides of each system at not less than the lower of the design pressures or the setting of the pressure relief device(s). The design pressures for testing shall be those listed on the equipment nameplate. 1108 OMSC • Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfu , tan Bl.�� , Senio ans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 1-