February 18, 2004 CITY OF TIGARD
Pete Russell OREGON
Source Refrigeration
5506 SE International Way
Milwaukie, OR 97222
RE: REMODEL REFRIGERATION SYSTEM
Building Permit: MEC2004 -00015 Construction Type: III -N
Tenant Name: Safeway Occupancy Type: M
Address: 15570 SW Pacific Highway Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
FIELD TESTS
• Every refrigerant- containing part of every system that is erected on the
premises, except compressors, condensers, vessels, evaporators, safety devices,
pressure gauges and control mechanisms that are listed and factory tested, shall be
tested and proved tight after complete installation before operation. Tests shall
include both the high- and low- pressure sides of each system at not less than the
lower of the design pressures or the setting of the pressure relief device(s). The
design pressures for testing shall be those listed on the equipment nameplate.
1108 OMSC
• Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.