RE: 196123 Geraldene Moyle Electrical Plan Review
Carl Jr's
The plans submitted were reviewed for conformity with the 1996 National Electrical
Code (NEC) and the State of Oregon Electrical Specialty Code. The following was
noted:
1. The 1996 NEC is the minimum electrical requirement.
2. Need the service electrical fault current projections.
3. Service will require grounding the electrode to the rebar (UFER) system.
4. Engineer requirements for grounding conductor in all conduits will be enforced.
5. NEC and Mechanical Codes requie GFCI protected receptacles on roof to
service mechanical equipment.
6. All food processing equipment to have label from approved testing lab. This
includes the heat blanket, which needs inspection prior to installation (cover).
7. Sheet E -3 lists the following systems that need permits prior to any cover (wall or
ceiling) inspections:
A. HVAC system
B. Computer (Data) system
C. Cash Register (Cash wrap)
D. Auto Mobile system (Drive -up)
E. Speaker system
F. Nutone - may be part of speaker
G. Fire system
H. Security system
I. Signs
8. Pay telephone vender to coordinate installation with Electrical Inspector.
9. Telephone Board (E -3/8), Irrigation, ATM (E -2/3), and Telephone equipment not
to violate clearance (NEC 110 -16) of Electrical Service Equipment and Panels.
10. Restroom and lavatory receptacles, plug, and hand driers to be GFCI protected.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
196123 Geraldene Moyle Electrical Plan Review
Page #2
11. The feeder to rooftop fan gutter to be sized per NEC 430 -62(a) along with the
applicable TAP rules.
12. There will be no plumbing or mechanical equipment, line or vents in the Electrical
Room.
13. Electrical Room may not meet NEC 110 -16 requirements for clearance (3 feet)
unless doors will give full access. The lighting in this room may not be adequate.
14. The locked Electrical Room to be accessible, NEC 240 -246.
Please contact Michael Rudd at 503 - 639 -4171, x356, to discuss the electrical notes.