Loading...
Correspondence r , r h City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 April 10, 2008 I1 , 1 RE: MECHANICAL REFRIGERATION T I GARD Project Information Building Permit: MEC2008 -00151 Construction Type: 5 -B Tenant Name: Rialto Pool Occupancy Type: A3 Address: 14411 SW Pacific Hwy. Occupant Load: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. 1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon insignia of compliance located on the exterior side of the panel located nearest the door prior to final inspection. 2) Every refrigerant - containing part of every system that is erected on the premises shall be tested and proved tight after complete installation, and before operation. Tests shall include both the high and low- pressure sides of each system and shall not be pressured down until verification of the City of Tigard Building Inspector. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. _ . Respec ully Dan Nelson, Senior Plans Examiner (503)718 -2436 dann@tigard- or.gov I Phone: 503.639.4171 • Fax: 503.684.7297 .. www.tigard- or.gov • TTY Relay: 503.684.2772