Loading...
Correspondence • June 29, 1995 Hunter Davisson 3410 SE 20th Portland, OR 97202 Re: Boston Market 13935 SW Pacific Hwy. Plan Check 6-61C The plans have been reviewed for conformity to the applicable codes. Please submit the foll w''items to complete the plan review process. 91. The attachment of permanent nonstructural components shall be designed to resist the total design seismic forces prescribed in Section 2336(b) of the Structural Specialty Code. Provide an engineer's design specifying attachment requirements of condensing units 15, 16, 21 and 22. The mechanical permit will be processed when we are in receipt of the installation requirements. If you have any questions, please do not hesitate to call. Sincerely, James Funk Plans Examiner H : \LO G I NU I M\M EC 95 -0205