Loading...
Specifications 6g 1 ° 0 , 00 7 - 000 GI tqco Fire & Building :` . 'iAl�. Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series DS -1 — 5.6 K- factor Dry Type Sprinklers Quick and Standard Response, Extended Coverage General manufacturer should be contacted with any questions. Description The Series DS -1 Dry Type Sprinklers =� must only be installed in fittings that The Series DS -1, 5.6 K- factor, Quick meet the requirements of the Design y -w -. -, Response (3 mm Bulb) and Standard Criteria section. • - ' Response (5 mm Bulb), Extended Coverage Horizontal Sidewall, Dry = ,,,,. � Model/Sprinkler Sprinklers are decorative glass odel /Sprinkler 4 l bulb automatic sprinklers. They are in- Identification tended for use in applications where the sprinklers and /or a portion of the Numbers connecting piping may be exposed to freezing temperatures (e.g., horizontal TY3338 - (3 mm Bulb Type) piping extensions through a wall to TY3358 - (5 mm Bulb Type) protect an unheated area of a build- ing). The Series DS -1 Extended Cov- erage Horizontal Sidewall Sprinklers Technical Water Tube Stainless Steel are designed for extended coverage Spring Stainless Steel use in light hazard occupancies Data Sealing Assembly (ECLH). Beryllium Nickel w/Teflon" Approvals WARNINGS UL d C -UL Listed. NYC A roved. Escutcheon C Steel Type Sprinklers pp *Registered Trademark of DuPont The Series DS -1 Dry yp p (Refer to Table A) described herein must be installed and Maximum Working Pressure Patents maintained in compliance with this 175 ps (12,1 bar) U.S.A. Patent No. 5,188,185 document, as well as with the applica- ble standards of the National Fire Pro- Inlet Thread Connection Operation tection Association, in addition to the 1 inch NPT standards of any other authorities hav- Discharge oe Coefficient ing jurisdiction. Failure to do so may K = 5.6 GPM When the Series DS -1 is in service, impair the performance of these de- (80,6 LPM /bar1i2) water is prevented from entering the vices. assembly by the Plug & Belleville Seal - The owner is responsible for maintain- Temperature Ratings ing Assembly (Ref. Figure 1) in the ing their fire protection system and de- Refer to Tabl A Inlet of the Sprinkler. The glass Bulb contains a fluid that expands when ex- vices in proper operating condition. Finishes posed to heat. When the rated tern - The installing contractor or sprinkler Sprinkler: Natural Brass, Chrome perature is reached, the fluid expands Plated, White Polyester sufficiently to shatter the glass Bulb, Escutcheon: White Coated or Chrome and the Bulb Seat is released. The IMPORTANT Plated compressed Spring is then able to ex- Always refer to Technical Data Physical Characteristics pand and push the Water Tube as well Sheet TFP700 for the "INSTALLER Inlet Copper as the Guide Tube outward. This action . WARNING" that provides cautions Plug Copper simultaneously pulls inward on the with respect to handling and instal- Yoke Stainless Steel Yoke, withdrawing the Plug & Belleville lation of sprinkler systems and corn- Casing . . . Galvanized Carbon Steel Seal from the Inlet allowing the sprin- ponents. Improper handling and in- Insert Bronze kler to activate and flow water. - stallation can permanently damage Bulb Seat Stainless Steel a sprinkler system or its compo- Bulb Glass nents and cause the sprinkler to fail Compression Screw Bronze to operate in a fire situation or cause Deflector Bronze it to operate prematurely. Frame Bronze Guide Tube Stainless Steel Page 1 of 6 APRIL, 2004 TFP520 s Page 2 of 6 • TFP52O SPRINKLER FINISH TY3338 HSW (3 mm Bulb Type) w/ Standard Escutcheon . (Ref. Fig. 2) TY3358 HSW (5 mm Bulb Type) w/ Standard Escutcheon (Ref. Fig. 2). Temperature Bulb Natural Chrome White Rating Color Code Brass Plated Polyester 135 °F /57 °C Orange 1, 2, 3 155 °F /68 °C Red . 1, 2, 3 Notes: 1. Listed by Underwriters Laboratories, Inc. (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches). 3. Approved by the City of New York under MEA 352 -01 -E. TABLE A SERIES DS -1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS APPLICATION Coverage ( Min Min Temperature Top Of Deflector To W x L Flow Pressure Rating Ceiling Distance (2) . FT x FT (m x m) GPM (LPM) PSI (BAR) °F Inches (mm) TY3338 HSW 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) (3 mm Bulb Type) 1 6 x 18 (4,9 x 5,5) 29 (110) 26.8 (1,85) For Quick Response 135 & 155 4 to 12 Light Hazard 16 x 20 (4,9 x 6,1) 32 (121) 32.7 (2,25) (100 to 300) Extended Coverage Per NFPA 13 18 x 16 (5,5 x 4,9) 29 (110) 26.8 (1,85) APPLICATION Coverage ( Min Min Temperature Top Of Deflector To W x L Flow Pressure Rating . Ceiling Distance ( FT x FT (m x m) GPM (LPM) PSI (BAR) °F Inches (mm) TY3358 HSW 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) • (5 mm Bulb Type) 4 For Standard Response 1 6 x 18 (,9 x 5,5) 29 (110) 26.8 (1,85) 135 & 155 4 to 12 Light Hazard 16 x 20 (4,9 x 6,1) 32 (121) 32.7 (2,25) (100 to 300) Extended Coverage Per NFPA 13 18 x 16 (5,5 x 4,9) 29 (110) 26.8 (1,85) Notes: 1. The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet (4,3 m). . 2. To meet the deflector -to- ceiling distance of 4 to 12 inches (100 to 300 mm), the centerline of the sprinkler waterway must be - 4 -7/16 to 12 -7/16 inches below the ceiling. • TABLE B SERIES DS -1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS UL AND C -UL INSTALLATION CRITERIA ` TFP52O Page 3 of 6 PLUG WITH YOKE CASING INSERT FRAME 3 or 5 mm DEFLECTOR GASKETED SPRING BULB PLATE SEAL , ■v Q1� T'T ��ikr � I-lI I I I . I�- ��t ' � . t ` �. ,.rai..� 1 ! 1! �WIS a_ / WATER GUIDE BULB VENT COMPRESSION INLET 1° NPT SPRING TUBE TUBE SEAT HOLE SCREW FIGURE 1 TY3338 (3 mm BULB) AND TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY • ORDER LENGTHS: Design 2 -1/2° to 48° 4° t 1/8° (63,5 to 1219,2 mm) Criteria IN 1/4° (6,4 mm) (101,6 ± 3,2 mm) INCREMENTS FACE OF The Series DS -1 Sprinklers are in- FACE OF MOUNTING tended for use in fire sprinkler systems 1 -3/4° DIA. SURFACE designed in accordance with the ex- , ;- 1 , — SPRINKLER (44,5 mm) FITTING tended coverage installation guide- _ lines provided by NFPA 13 and the ���I� ii _ 3° DIA. installation criteria provide by Table B. 11 lr� (76,2 mm) The Series DS -1 Dry Type Sprinkler is r \I to be installed in the 1 inch NPT outlet LT or run of malleable or ductile iron .._, ' SPRINKLER FITTING threaded tee fittings that meet the di- ------ (REFER TO DESIGN CENTERLINE 7/16° mensional requirements of ANSI CRITERIA SECTION) OF WATERWAY (11,1 mm) • B16.3 (Class 150) or cast iron threaded tee fittings that meet the di- FIGURE 2 mensional requirements of ANSI TY3338 (3 mm BULB) AND TY3358 (5 mm BULB) B16.4 (Class 125) with the end sprin- EXTENDED COVERAGE HORIZONTAL SIDEWALL kler fitting on a branch line to be w/ STANDARD ESCUTCHEON plugged as shown in Figure 2. For wet pipe sprinkler systems, the Series DS -1 Dry Type Sprinklers may also be installed in the 1 inch NPT , a cal Tee oa the fol Tyco P od- SiA� WRENCH ucts CPVC fittings: (P /N 80145) 1" x 1" WRENCH NPT Female Adapter or (P /N 80249) RECESS 1° x 1° x 1" NPT Sprinkler Head Adapt- er Tee. PUSH WRENCH ' , NOTE INTO ENSURE G r 9 ENGAGEMENT 0 Do not install the Series DS -1 into any WITH SPRINKLER r other type fitting without first consult- WRENCH FLATS / • ing the Technical Services Depart- ment. Failure to use the appropriate FIGURE 3 fitting may result in: failure of the sprin- W -TYPE 7 SPRINKLER WRENCH kler to properly operate due to forma- tion of ice over the inlet Plug or binding of the inlet Plug; or, insufficient en- gagement of the inlet pipe threads with consequent leakage. • Branch, cross, and feedmain piping connected to Dry Sprinklers and sub- _ ject to freezing temperatures must be pitched for drainage in accordance with the minimum requirements of the National Fire Protection Association for dry pipe sprinkler systems. When Dry Sprinklers are to be used in i Page 4 of 6 TFP520 wet pipe sprinkler systems protecting liquid from the bulb. With the sprinkler weepage past the Inlet seal and that areas subject to freezing temperatures held horizontally, a small air bubble the sprinkler needs to be removed for (e.g., horizontal extensions into freez- should be present. The diameter of the determining the cause of leakage (e.g. ers), consideration must be given to air bubble is approximately 1/16 inch an improper installation or an ice plug). the appropriate length of the sprinkler (1,6 mm). The fire protection system control that will prevent freezing of the water valve must be closed and the system in the connecting pipes due to conduc- A leak tight 1 inch NPT sprinkler joi drained before removing the sprinkler. tion. When the temperature surround- should be obtained with a torque of 20 ing the wet pipe sprinkler system is to 30 ft.lbs. (26,8 to 40,2 Nm). Higher Sprinklers that are found to be leaking maintained at a minimum temperature e l eve l s o f t orque may distort the sprin- or exhibiting visible signs of corrosion m n tained , t a follo are the min kler inlet with consequent leakage or must be replaced. of mum recommended lengths between impairment of the sprinkler Automatic sprinklers must never be the face of the sprinkler fitting and the Do not attempt to compensate for in- painted, plated, coated, or otherwise outside surface of the protected area sufficient adjustment in an Escutcheon altered after leaving the factory. Modi- (i.e., length exposed to minimum am- Plate by under- or over - tightening the tied sprinklers must be replaced. bient of 40 °F /4 °C): Sprinkler. Readjust the position of the Sprinklers that have been exposed to • 12 inches (300 mm) when the tern- sprinkler fitting to suit. corrosive products of combustion, but perature within the protected area Step 1. Horizontal sidewall sprinklers have not operated, should be com- is - 20 °F / -29 °C are to be installed in the horizontal pletely cleaned by wiping the sprinkler posi tion with their centerline of water- with a cloth or by brushing it with a soft • 18 inches (450 mm) when the tern- way perpendicular to the back wall and bristle brush. perature within the protected area parallel to the ceiling. The word "TOP" Care must be exercised to avoid dam - is -40°F/-40°C on the Deflector is to face towards the age - before, during, and after instal- • 24 inches (600 mm) when the tern- ceiling. lation. Sprinklers damaged by drop - perature within the protected area Step 2. With pipe thread sealant ap- or She striking ' must nch replacedP Also, is -60°F/-51°C plied to the inlet threads, hand tighten For protected area temperatures be- the sprinkler into the sprinkler fitting. replace any sprinkler that has a tween those given above, the minimum cracked bulb or that has lost liquid from recommended length from the face of Step 3. Wrench tighten the sprinkler by its bulb (Ref. Installation Section). the fitting to the outside of the pro- wrenching on the Casing with a pipe The owner is responsible for the in- tected area may be determined by in- wrench whenever the casing is readily spcction, testing, and maintenance of terpolating between the indicated val- accessible. Otherwise, use a W -Type 7 their fire protection system and de- ues. Sprinkler Wrench (Ref. Figure 3). The vices in compliance with this docu- wrench recess of the W -Type 7 is to be ment, as well as with the applicable NOTE applied to the sprinkler wrench flats standards of the National Fire Protec- (Ref. Figure 3). When Dry Sprinklers penetrate a wall tion Association (e.g., NFPA 25), in into an area subject to freezing, the Step 4. After the wall has been in- addition to the standards of any other clearance space around the Sprinkler stalled /finished, slide on the outer authorities having jurisdiction. The in- Casing must be completely sealed in piece of the Escutcheon until it comes stalling contractor or sprinkler menu- order to prevent the leakage of moist in contact with the ceiling /wall. facturer should be contacted relative air into the freezing area which might to any questions. result in the Frame, of condensate Ca and It is recommended that automatic around the Frame, Deflector, Bulb sprinkler systems be inspected, Seat, Bulb. Failure to prevent the formation of condensate could result in M tested, and maintained by a qualified Ins ection Service in accordance with the build -up of ice around the releasing p components. This could result in an The Series DS -1 Dry Type Sprinklers local requrements and /or national inadvertent operation of the sprinkler must be maintained and serviced in code. or impaired operation due to reduced accordance with the following instruc- thermal sensitivity. tions: Limited NOTES Warranty Installation Absence of the outer piece of an es- cutcheon, which is used to cover a Products manufactured by Tyco Fire The Series DS -1 Dry Type Sprinklers clearance hole, may delay the time to Products are warranted solely to the must be installed in accordance with sprinkler operation in a fire situation. original Buyer for ten (10) years the following instructions: Before closing a fire protection system against defects in material and work - NOTES main control valve for maintenance manship when paid for and properly The Series DS 1 muston/ybe installed work on the fire protection system that installed and maintained under normal in fittings that meet the requirements it controls, permission to shut down the use and service. This warranty will ex- of the Design Criteria section. affected fire protection systems must pire ten (10) years from date of ship - be obtained from the proper authori- ment by Tyco Fire Products. No war - Refer to the Design Criteria section for ties and all personnel who may be ranty is given for products or other important requirements regard- affected by this action must be notified. components manufactured by compa- ing piping design and sealing of the A Vent Hole is provided in the Bulb Hies not affiliated by ownership with clearance space around the Sprinkler Seat (Ref. Figure 1) to indicate if the Tyco Fire Products or for products and Casing. Dry Sprinkler is remaining dry. Evi- components which have been subject Do not install any bulb type sprinkler if dence of leakage from the Vent Hole is to misuse, improper installation, corro- the bulb is cracked or there is a loss of an indication that there may be sion, or which have not been installed, TFP52O Page 5 of 6 maintained, modified or repaired in ac- ABOUT THE POSSIBILITY OF SUCH Sidewall Dry Type Sprinkler. cordance with applicable Standards of DAMAGES, AND IN NO EVENT • 5.6 K- factor. the National Fire Protection Associa- SHALL TYCO FIRE PRODUCTS' LI- • tion, and /or the standards of any other ABILITY EXCEED AN AMOUNT • Order Length. . Authorities Having Jurisdiction. Mate- EQUAL TO THE SALES PRICE. rials found by Tyco Fire Products to be THE FOREGOING WARRANTY IS Dry Type Sprinklers are furnished defective shall be either repaired or based upon Order Length as ' replaced, at Tyco Fire Products' sole MADE IN LIEU OF ANY AND ALL , measured from the face of the wall ' option. Tyco Fire Products neither as- OTHER WARRANTIES EXPRESS OR to the face of the sprinkler fitting sumes, nor authorizes any person to IMPLIED. INCLUDING WARRANTIES (Ref. Figure 2). After the measure - assume for it, any other obligation in OF MERCHANTABILITY PARTICULAR PUR- AND FIT- ment is taken, round it to the near - connection with the sale of products or NESS FOR A P est 1/4 inch increment. parts of products. Tyco Fire Products POSE shall not be responsible for sprinkler • 1 Inch NPT Inlet Connection. system design errors or inaccurate or Ordering • Temperature Rating. incomplete information supplied by Buyer or Buyer's representatives. Procedure •Sprinkler Finish. IN NO EVENT SHALL TYCO FIRE • Standard Escutcheon and Finish. PRODUCTS BE LIABLE, IN CON- Contact your local distributor for avail- • Part Number fro Table C. TRACT, TORT, STRICT LIABILITY OR ability, and please specify the follow - UNDER ANY OTHER LEGAL THE- ing 2. W -Type 7 Sprinkler Wrench. ORY, FOR INCIDENTAL, INDIRECT, 1. Sprinkler. Refer to the Price List for complete SPECIAL OR CONSEQUENTIAL • listing of Part Numbers. DAMAGES, INCLUDING BUT NOT . LIMITED TO LABOR CHARGES, RE- • Bulb Size (3 or 5 mm) GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED • Extended Coverage Horizontal g P/N 60 - XXX - X - XXX ORDER LENGTH (1) (EXAMPLES) 055 5.50° SPRINKLER ESCUTCHEON MODEUSIN FINISH FINISH 082 8.25° 350 EC Sldewall 3 mm Bulb TY3338 1 NATURAL BRASS WHITE 180 18.00° (1 °NPT), 135F/57C 4 WHITE POLYESTER WHITE 187 18.75° 351 EC Sldewall 3 mm Bulb TY3338 (1 °NPT), 155F/68C 9 CHROME PLATED CHROME PLATED 372 37.25° 0 CHROME PLATED WHITE 480 48.00° 950 EC Sldewall, 5 mm Bulb TY3358 3 WHITE (RAL9010)' WHITE (RAL9010)° (1° NPT), 135F/57C 951 EC Sldewall, 5 mm Bulb TY3358 (1° NPT), 155F/68C NOTES (1). Dry Type Sprinklers are furnished based upon "Order Length" as measured per Figure 2. After the measure- ment is taken, round it to the nearest 1/4 inch increment. Eastern Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS (Use Prefix `I" for ISO 7 -R1 Connection, e.g., I -60- 350 -1 -180) Page6of6 TFP520 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 AUTOMATIC SPRINKLERS - ' FIRE PROTECTION PRODUCTS J (ctauIicr V34, 1(8.0 Models V3401, V3402, V3405 and V3406 Standard Spray • Pendent, Upright and Recessed Pendent Standard and Quick Response PRODUCT DESCRIPTION These Model V34 standard assembly effort. This sprin- ture rises causing the liquid spray sprinklers are kler is available in various in the bulb to expand. designed to produce large temperature ratings (see When the ambient temper - �, discharge capacity in a chart on page 2) and fin- ature reaches the rated ' _ hemispherical pattern stan- ishes to meet many design temperature of the sprin- '' ' V3405 dard commercial applica- requirements. kler, the bulb shatters. As a - ' _. V3406 tions. The design The recessed pendent result, the waterway is Recessed incorporates state-of-the- should be utilized with a cleared of all sealing parts Pendent u u c art, heat responsive, frangi- and water is discharged - -? Q Q Model V34 recessed V3405 O bl glass bulb design (stan- towards the deflector. The y V3406 8 escutcheon which pro - i, „ a.a dard or quick response) for vides up to 3 /a" (19 mm) of deflector is designed to dis '.' °°°"°` prompt, precise operation. adjustments. tribute the water in a pat ' ` ` . L The die cast frame is more tern that is most effective ,ii t_ ^. S rinkler O eration IT, ' el ' s treamlined and attractive P P in controlling the fire. ��, The operating mechanism than traditional sand cast is a frangible glass bulb Coverage frames. It is cast with a which contains a heat For coverage area and 's hex -sha ed wrench boss to sprinkler placement, refer P3.$. p responsive liquid. During a Pendent mil allow easy tightening from fire, the ambient tempera to NFPA 13 standards. V3401 ` - ma angles. reducing Upright TECHNICAL SPECIFICATIONS Models: V3401, V3402, V3405, MATERIAL Finishes: ® V3406 SPECIFICATIONS ❑ Plain brass Style: Pendent, Upright or Upright Deflector: ❑ Chrome plated Recessed Pendent Bronze per UNS C22000 ❑ White painted ** Nominal Orifice Size: "/32" Pendent Deflector: ❑ Flat black painted ** (14 mm) Bronze per UNS C51000 ❑ Custom painted ** 7 K - Factor. 8.0 imp. (11,5 Si.") . Bulb: Glass with glycerin solu O Lead t ion. ❑ Proprietary Nickel Teflon Nominal Thread Size: Bulb Nominal Diameter: coating PT (20 ing ❑ Standard: 5,0 m 155, 200, 286SR Only: L' N Max. . Working Pressure: ~ Max 175 psi (1200 kPa) ❑ Quick Response: 3,0 mm U Wax ) Factory Hydrostatic Test: Load Screw: Bronze per UNS ❑ Wax over lead ir�� 'I 100% @ 500 psi (3450 kPa) Pip Ca p: Bronze per UNS P For cabinets and other accesso- ries refer to se arate sheet. Pip Cap: Min. Operating Pressure: C65100 NOTE: Weather resistant recessed 7 psi (48 kPa) escutcheons available upon request. UP Temperature Rating: See Seal: Teflon* tape ^ For K- Factor when pressure is mea- e chart on page 2. Spring: Beryllium nickel sured in Bar, multiply S.I. units by 10.0. Frame: Die cast brass 65 -30 Teflon is a registered trademark of � Lodgement Spring: Dupont Co. Stainless steel per UNS S30200 •• Also, UL Listed for corrosion resis- ACCESSORIES Lance. (Exaggerated for clan ry) Installation Wrench: - ❑ Open End: V34 ❑ Recessed: V39 2547 Rev.E 6/04 ® Registered Trademark of Victaulic o Copyright 2004 Victaulic SKU 9WCAS- 66ULHQ Printed in U.S.A. 0 APPROVALS/LISTINGS Nominal Approved Temperature Ratings °F/°C f G K- Factor - Orifice Size Imperial Deflector Model Inches/mm S.I.^ Response Type UL FM ULC NYC/MEAt CSFM § 1%2 8.0 Standard Uri 135 - 360 135 - 360 135 - 360 135 - 360 135 - 360 • V3401 14 11.5 Upright 57 - 182 57 - 182 57 . 182 57 - 182 57 - 182 17,62 8.0 St Pendent 135 - 360 135 - 360 135 - 360 135 - 360 135 - 360 V3405 14 11,5 57 -182 57.182 57.182 57 -182 57 -182 V3405 "y, 8.0 Standard Recessed Pendent 135 - 286 135 - 200 135 - 286 135 - 286 135 - 286 14 11.5 Up to Vi Adjustment 57 - 141 57 - 193 57 . 141 57 . 141 57 - 141 nAa 8.0 Quick • Uri 135 - 286 135 - 286 135 - 286 135 - 286 135 - 286 V3402 14 11.5 Upright 57. 141 57.141 57.141 57 -141 57 -141 V3406 rAu 8.0 Quick Pendent 135 - 286 135 - 286 135 - 286 135 - 286 135 - 286 u 14 11.5 57.141 57 -141 57 -141 57 -141 57 -141 V3406 iv, 8.0 Quick Recessed Pendent 135 - 200 135 - 200 135 - 200 135 - 200 135 - 200 14 11.5 Up to h Adjustment 57 - 193 57 - 193 57 - 193 57 - 193 57 - 193 V3406 n 8.0 Quick Recessed Pendent 135 - 200 No 135 - 200 135 - 200 135 - 200 14 11.5 Up to 44 Adjustment 57 - 193 57 - 193 57 -193 57 - 193 # Listings and approval as of printing. 0 All are approved open, except for areas designated 'No ". ^ For K- Factor when pressure is measured in Bar, multiply S.I. units by 10.0. t MEA #62 -99 -E. § CSFM #7690- 0531:112 Temperature - °FPC Sprinkler Victaulic Nominal Maximum Glass RATINGS Temperature Part Temperature Ambient Temp. Bulb Classification Identification Rating Allowed Color All glass bulbs are rated for 135 100 temperatures from -65 °F Ordinary A 57 38 Orange ( -54 °C) to those shown in Ordinary C 155 100 Red adjacent table. Intermediate E 175 150 79 65 Yellow Intermediate F 2 9 3 1 6 5 0 Green - 26 High J 1 2 10 7 Blue 0 Extra High # K 18 149 Mauve - # M Open _ No Bulb # Standard response only. All are approved open, except for areas designated 'No ". - 150/65 if wax coated. ORDERING INFORMATION Please specify the following when ordering: ❑ Sprinkler Model Number ❑ K- Factor ❑ Sprinkler Finish ❑ Style ❑ Thread Size ❑ Escutcheon Finish ❑ Temperature Rating ❑ Quantity ❑ Wrench Model Number . .A WARNING 1 • Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation 31 of any sprinklers. I •Always wear safety glasses and foot protection. �_ � • Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. • Installation rules, especially those governing obstruction, must be strictly followed. U • Painting, plating, or any re- coating of sprinklers (other than that supplied by Victaulic) is not allowed. Failure to follow these instructions could result in serious personal Injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton, Pennsylvania 18044-0031, 610 - 559 -3300. 40.15 - 2 5` DIMENSIONS I M----- aria T (3lmm fl 2'W , r • (64 mm) i 1.. 45 mm ) i t 2W _., (64 mm) Luii we IIII (33 mm) Standard Pendent - V3405, V3406 Standard Upright - V3401, V3402 2W (60 mm) Max. Hole 2' (51 mm) Min. Hole • I I 1 Lb' (16} (1 rnm) �AIju lirOM � rya Ceiling Tile � /I', ,I�� (� ) r 1 1 . 134• (47 mm) 1 Finished Surface , (34 mm) • MAXIMUM RECESS 2'Hii (75 mm) MAXIMUM EXTENSION 1 12" Adjustment Recessed - V3405, V3406 (Drawing not to scale) • lib' (60 mm) .. Max. Hole 2• (51 mm) Mln. Hole ii �� { : is" . _ ' p m I wAr (3m) mt mm) M Arm Typical Ceiling Tile �� ®� 1 m) ( � �ullU � - Tl Finished Surface � ,' / (2 (29 mm) . • (46 mm) v MAXIMUM RECESS 2 (75 mm) —+ MAXIMUM EXTENSION 3/4 Adjustment Recessed - V3405, V3406 (Drawing not to scale) EMMEMEMMI AVAILABLE WRENCHES V34 V34 Recessed Open End V3401, V3402 Upright, ✓ ✓ V3405, V3406 Pendent V3405, V3406 Recessed Pendent ✓ - • 40.15 - 3 • • • DISTRIBUTION PATTERNS - MODELS V3405, V3406 • K8.0 STANDARD PENDENT AND RECESSED PENDENT •.;r DISTRIBUTION PATTERNS — TRAJECTORY - 10' ` 3,0m • 28'm N, \ 7 psi -- - - -- 48 kPa 6' s ` 1,8m \ \ -` 15 psi 103 kPa ` 4' \ .\ 1,2 m . . 30 psi s ` \ .. 207 kPa 2' . N 0,6 m \ 0 2' 4' 6' 8' 10' 12' 14' ` ` 16' 0,6 m 1,2 m 1,8 m 2,4 m 3.0 m 3,7 m 4,3 m 4,9 m MODELS V3401, V3402 • K8.0 STANDARD UPRIGHT ' DISTRIBUTION PATTERNS — TRAJECTORY 3,Om� �` 2,4 m \ 7 psi - - - - -- 48 kPa 6' \ 1,8 m \ 15 psi 103 kPa 4' \ \ \ •1,2 m \ `. 30 psi • `` • 207 kPa 2' \ , 0,8 m `\ `. • 0 • 2' 4' 6' 8' 10' 12' 14' 16' 0.6 m 12 m 1.8 m 2,4 m 3,0 m 3,7 m 4,3 m 4,9 m NOTES: . 1. Data shown is approximate and can vary due to differences in installation. 2. These graphs illustrate approximate trajectories. floor-wetting, and wall- wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of . coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings. Approvals and Warranties. 3. All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section - of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic Company. All products to be Installed In accordance with current Victaulic installation/assembly instructions. Vlctaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. 4a15-4 7- Z6( VSR -F P POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL, ULCandCSFMListed, FMandLPCBApproved,NYMEA Accepted, CE Marked Service Pressure: Up to 450 PSI (31 BAR) Minimum Flow Rate forAlarm:10 GPM (38 LPM) Maximum Surge: 18 FPS (5,5 m/s) Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250VAC �•, , 2.0 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: • Suitable for indoor or outdoor use with factory installed gasket and die -cast housing. • • NEMA 4/IP54 Rated Enclosure - use with appropriate A I `` conduit fitting. ,i .. • Temperature Range: 40 °F /120 °F, 4,5 °C /49 °C I ` . • Non - corrosive sleeve factory installed in saddle. "• Caution: This device is not intended for applications in explosive • environments. Sizes Available: Steel Pipe schedules 10 thru 40, sizes 2" thru 8" - BS 1387 pipe 50mm thru 200mm Note: For copper or plastic pipe use Model VSR -CF. Service Use: Automatic Sprinkler NFPA -13 U.S. Pat. No. 3921989 One or two family dwelling NFPA -13D Canadian Pat. No. 1009680 Residential occupancy up to four stories NFPA -13R _ _ Other Patents Pending National Fire Alarm Code NFPA -72 Potter Electric, Rd., 1990 Optional: Cover Tamper Switch Kit, Stock No. 0090018 GENERAL INFORMATION INSTALLATION: See Fig.2 The Model VSR -F is a vane type waterfiow switch for use on These devices may be mounted on horizontal or vertical pipe. wet sprinkler systems. It Is UL Listed and FM Approved for On horizontal pipe they should be installed on the top side of the use on steel pipe; schedules 10 through 40, sizes 2" thru 8" pipe where they will be accessible. The units should not be in- (50mm thru 200mm). stalled within 6" (15cm) of a fitting which changes the direction of LPC approved sizes are 2" thru 8" (50mm thru 200mm). the waterfiow or within 24" (60 cm) of a valve or drain. The unit may also be used as a sectional waterflow detector Drain the system and drill a hole in the pipe using a circular saw on large systems. in a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm The unit contains two single pole, double throw, snap action t2mm). All other sizes require a hole with a diameter of 2" ±1/8" switches and an adjustable, instantly recycling pneumatic re- (50mm t2mm). tard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. Clean the inside pipe of all growth or other material for a dis- The flow condition must exist for a period of time necessary to tance equal to the pipe diameter on either side of the hole. overcome the selected retard period. Roll the vane so that it may be inserted into the hole; do not bend ENCLOSURE: The unit is enclosed in a general purpose, die- or crease it. Insert the vane so that the arrow on the saddle cast housing. The cover is held in place with two tamper resis- points in the direction of the waterflow. Install the saddle strap tant screws which require a special key for removal. A field in- and tighten nuts alternately to an eventual 50 ft -lbs. (68 n-m) of stallable cover tamper switch is available as an option which torque (see Fig. 2). The vane must not rub the inside of the pipe may be used to indicate unauthorized removal of the cover. See or bind in any way. bulletin no. 5400775 for installation instructions of this switch. Specifications subject to change without notice. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146.4161 • Phone: 800-325-3936/Canada 888-882 -1833 •www.pottersignal.com PRINTED IN USA MKT. #8800001 - REV W PAGE 1 OF 2 MFG. #5400781 -7/02 (. . .. VSR -F f."--` P po VANE TYPE WATERFLOW \ i Th Symbol of Protection ALARM SWITCH WITH RETARD FIG. 1 FIG. 2 SWITCH TERMINAL CONNECTIONS OPTIONAL TAMPER SWITCH DO NOT LEAVE COVER OFF FOR • CLAMPING PLATE EXTENDED PERIOD OF TIME TERMINAL RETARD ADJUSTMENT: TO CHANGE TIME TURN KNOB (EITHER DIRECTION) I['0 ` TIGHTEN NUTS FOR DESIRED TIME DELAY. USE THE MINIMUM Ar it / ALTERNATELY TO AN AMOUNT OF RETARD NECESSARY TO PREVENT til : r' OF TTDROUE�� -Las (68 ^ m) l*C'tk."....). FALSE ALARMS, A - B - SETTING 15 USUALLY - ' ADEQUATE FOR THIS, FACTORY IS SET TO 'Er. I : t _, TO INSTALL, DRILL HOLE AS INDICATED: (. PIPE SIZE HOLE SIZE �� CO OeC. /O25 - Y" to 2 1/2' 1 1/4' +1/8' 1/16 f7\ MOUNT ON PIPE SO (50mm to 65mm) (33mm t2mm) I I�1� POINT ON SADDLE CAUTION: POINTS IN DIRECTI ON 3 to 8 2 - tt /8- OF WATERFLOW An uninsulated section of a (eomm to 200mm) 50mm ±2mm) single conductor should not ' , OPPOSI o RE C TION be looped around the fermi- Cover Tamper v OF WATERFLOW i • nal and serve as two sepa- (with cover in place) rate connections. The wire ?in) DIRECTION OF must be severed, thereby WATERFLOW I providing supervision of the c ( (OW \. \ APPROX. RETARD SETTINGS (IN SECS.) ( connection in the event that °" 0 A B C 0 E the wire becomes dislodged DWG. 8767 -30 Ns sonato-2 o- o 10-25 2 CO ,35.5.5 50 -70 40 -G0 from under the terminal. FIG. 3 TYPICAL ELECTRICAL CONNECTIONS NOTES: FIG. 4 1. The Model VSR -F has two To remove knockouts: Place switches, one can be used to screwdriver at edge of knock- 2 offs o operate a central station, pro- outs, not in the center. a0sc w.IAM ON FRC MK 1 prietary or remote signaling ° m unit, while the other contact is O O D . \ -. i . v , used to operate a local audible mil am a. N NE am or visual annunciator. ' 1;c I '(c?' � ��I ICc3 1 2. Acondition of LPC Approval of ,�, . — ° this product is that the electri- NC L¢ IC O ■0 NO ON MT 1C CC µ .mac Q cal entry must be sealed to 1 — �, INN' MN MI U i I Mt m1'90'5 r0- A 0901= eo wow AL exclude moisture. a -1p t n Og11Z I. r 04176.1 ' I GO t i 0. '1 WW1 �°` 3. For supervised circuits see ° rib 'Switch Terminal Connec- tions° drawing and caution owc. ne1-4 ' note (Fig. 1). APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterliow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. TESTING The frequency of inspection and testing for the model VSR -F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and /or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR -F is not recommended or advisable. A minimum flow of 10 gpm (38 Lpm) is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. ( PRINTED IN USA MKT. #8800001 - REV W PAGE 2 OF 2 ) MFG. # 00781 -7/02 �a, -0066 BELLS P POTTER PBA -AC & PBD -DC The Symbol of Protection . UL Listed, FM Approved • Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm) Voltages Available: 24VAC • 120VAC 12VDC (10.2 to 15.6) Polarized ®POnrR 24VDC (20.4 to 31.2) Polarized ..a. a ' Service Use: Fire Alarm 7...m-2m. tar-79 General Signaling BurglarAlarm Environment: Indoor or outdoor use (See Note 1) -40° to 150 °F (-40° to 66 °C) N itmit (Outdoor use requires weatherproof backbox.) Termination: 4 No. 18 AWG stranded wires 6" BELL SHOWN Finish: Red powder coating Optional: Model BBK -1 weatherproof backbox These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power con- sumption and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on a model BBK -1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK -1, Stock No. 1500001. ALL DC BELLS ARE POLARIZED AND HAVE BUILT -IN TRANSIENT PROTECTION: SCE TYPICAL dB MINIMUM dB CURRENT INCHES VOLTAGE MODEL NO. STOCK NO. AT 10 FT. AT 10 FT. (mm) (MAX.) ( ( ( ( 6 (150) 12VDC PBD126 1708012 .12A 85 76 8 (200) 12VDC P813128 1708012 .12A 90 78 10(250) 12VDC PBD1210 1710012 .12A 92 78 6 (150) 24VDC PBD248 1706024 .08A 87 76 8 (200) 24VDC P80248 1708024 .08A 91 79 10(250) 24VDC PBD2410 1710024 .06A 94 79 8(150) 24VAC PBA246 1808024 .17A 91 76 8(200) 24VAC PBA248 1808024 .17A 94 78 10(250) 24VAC PBA2410 1810024 .17A 94 76 B (150) 120VAC PBAl208 1606120 .05A 92 82 8(200) 120VAC PBAl208 1808120 .05A 99 82 10 (250) 120VAC PBAl2010 1810120 .05A 99 85 Notes: 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150 °F ( -34° to 66 °C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146 -4161 • Phone: 800 - 325 -3936 /Canada 888 - 882 -1833 • www.pottersignal.com PRINTED IN USA MKT. #8850001 - REV 0 PAGE 1 OF 2 MFG. #5400776 - 12/01 . BELLS . PPOTTER PBA -AC PBD -DC ® . • The Symbol of Protection . . - _ DIMENSIONS . INCHES (mm) ' • . FIG: ' BELLS FIG. 2 WEATHERPROOF BACKBOX • . • BOX I-LAS ONETHREADED 1/2" CONDUIT ENTRANCE - I c - )0' 121 - O 3 3/8' S' Li..._ ( 250) 8" 5 3/ - (86) (127) _ uni (200) 6" I (tab) (150) I. L7 on) _ 1 I , -10 5/8 - 3 8 (86) (41) 4 1/4' • 2 11/16 (68) OWG. ,776 -1 • (108) DWG. 8776 -2 FIG. 3 WIRING (REAR VIEW) D.C. BELLS (OBSERVE POLARITY) A.C. BELLS RED (IN) RED (OUT) WIITE (IN) WARE (OUT) FROM CONTROL PANEL TO NEXT BELL FROM CONTROL PANEL r igrOl PRECEDING BELL U r‘1111111 al OR END-OF-R UNE PRECEDING BELL W II BLACK (It) _' BLACK (OUT) BLACK (IN) �' BLACK (OUT) • fly:): WHEN ELECTRICAL SUPERAEDON IS REQUIRED USE IN AND OUT LEADS AS SHOWN. WREN ELECTRICAL SUPERWSION 6 REQUIRED USE IN AND OUT -LEADS AS SHOWN. NOTES: NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS. 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY 2. RED WIRES POSITIVE ( +) • AFTER LAST BELL. 3. BLACK WIRES NEGATIVE ( -) 2. END -OF -LINE RESISTOR IS NOT REQUIRED ON A.C. BELLS. • DWG. #776 -3 INSTALLATION 1. The bell should be mounted a minimum of 8 ft. (2,4m) from the floor or as close to the ceiling as possible. 2. Remove the gong. 3. Connect wiring (see Fig. 3). - 4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down): • 5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all area as designated by the authority having jurisdiction). PRINTED IN USA MKT. #8850001 - REV Q PAGE 2 OF 2 MFG. #5400776 -12101 • • • y Pa ad7 -oo66� MODEL 1000 TESTANDRAINfr 3/47 1 /4 1 /2 2" , t[t�k� -NA+� tY '��'.� 7'�'' u ar �sr Y {. Y' :i I rT �. 4 C __ ___ ' L ,.�z `tx�r. 1 n(H t t7) � ir ' f d „ 1 1 ' u"y rw d e l i Z � " { i a rte nh r I I 11 , .. 1 agl s2 4 g l5i '`' 2 r -{ ?K "' F( ,lt i -! n, ` § im .Y,, �I I .. _ !) _. 1i ORIF1 +1 E n � r � � C� �' � I ti f " R � {.. i i : •..>•. „ - I. - -c'' S , r �- ..rNCr, 4 '1'14%. � ' A % ;-.,, , R 9 1 s � t t F t I 9� I s I rf l' TESTA IN �(' dhi f � t F , 9 III fLtS III IAYIN LAlf fkAIIIN9E L. s3ii ! I�y�l '' tP t I I1 'i '' ! V� 'i' i GM {r c1 t, 9 t It t id. y ;c r r — ' ' 9 x I ' iy ! ! f ,.l' r i r , . ,r ° ✓'fa ir S 4 Y d i Y � Z}e*,r i o f it _ ', i i i T r n`Y d. ;~`1N 4 7!` t iy S p t t`�ii �Il �l tl � S • � C . t � r{. l0 I , t_ 5 err ='�`+ 7 "}I � ' p'' ,;�``I f • f US'A PATENT, #4741361 rAND OTHERPATENTS-PENDING r ❑ The AGF Manufacturing Inc. Model 1000 TESTANDRAIN Provides Both The Test Function And The Express Drain Function For A Wet Fire Sprinkler System. • ❑ The Model 1000 Complies With All Requirements Of NFPA -13, NFPA -13R, And NFPA -13D. ❑ The Model 1000 TESTANDRAIN Is A Single Handle Ball Valve That Is Light Weight And Compact, Includes A Tamper Resistant Test Orifice, Integral Tamper Resistant Sight Glasses, And Is 300 PSI Rated. ❑ Available In A Full Range Of Sizes From 3 /4" To 2" NPT & BSPT, With All Specifiable Orifice Sizes 3 /8", 7 /16 ", 1 /2 ", 17 /32 ", 5 /8" (ELO), 3 /4" (ESFR) and K.25. ❑ The Orifice Size Is Noted On The .Indicator Plate And The Valve Is Tapped For A Pressure Gauge. ❑ The Standard Model 1000 TESTANDRAIN Valve Includes A Pressure Gauge Port . Tapping And Can Be Ordered With A Relief Valve As A Model 1011 Or 1011T ❑ Locking Kit Available Which Provides Superior Vandal Resistance And Prevents Unintentional Alarm Activation. OVt pur New 4L I OC e 0' visit us � 4 0 5,, Gr on the Internet �f at www.testandrain.com MODEL 1000 300 PSI YL 6.4> . AP 3/ 1" 11/4" /2° 2" PLAN VIEW FRONT VIEW /VERTICAL INSTALLATION A ■ 1 FROM BRANCH 1 I �� GAUGE INLET 8 :111.1 \/ .. / PROVIDED um NEI ■--- D i - !M .711i TO DRAIN i ` � 1 -- .--. 1 STREET EL ow as FRONT VIEW /HORIZONTAL INSTALLATION .... ' TO DRAIN t -E -►I -► 1CS 1 I 1 STREET EL - Milli OR PIPE I = I . . y TO DRAIN F -- H - " APIA •� % In ,-----r RIGHT HAND /STRAIGHT INSTALLATION TO DRAIN I . _ n O I. ■ G APPROVALS: ...... ❑ UL and ULC Listed ❑ FM Approved except 3/4" ORIFICE SIZE ❑ NYC -BSA NO.720 -67 -SM AVAILABLE- 3/8", 1 /2", 17 /32", ELO(3 /8"), ESFR(3 /4'T' and IG'5 *Avallable on II/2' to 2" size units only. ❑ CA. State Fire Marshall DIMENSIONS - INCHES SIZE A B C D E F G H MATERIAL LIST 3 „ 5 2 8 1 m " 3 5 3 /16 r1 s.65mm 933233 _855.38 1 3as3 4 .12 m; 6 m 162.4 PART: MATERIAL: 1 n 5 1 /16 " 1 1 /2 " 2 3 /l6" 3 5 /8" 3 3 41" 1 13 /16" 4 9/16" 6 3 128mm 37.58mm 85.65mm 9323mm 85.88mm 45.30mm 117.12mm 16262mm HANDLE STEEL 1 1/ 4 n 5 7 /16" 12/16^ 2 9 /16" 4 1 /4" 3 5/16" 160.15/16n 6 " 5 9/16" 5 1 STEM ROD BRASS 137. 70mm mm 65 96mm 1 o8 36mm 82b4mm 9mm 141a 9mm 1 92 2 8m m BALL C.P. BRONZE 1 1 n 6 7 /16" - 14 13 /16 " 3 1 /4 " 5 1 /16 " 3 7 /8 " 2 5 /8 " 8 1 /4 10 7 / 8 " S BODY GH LASS BRONZE AN /2 1 6338mm 45 50mm 8 15omm 127 99.1 66.97 206 278.60mm VALVE G SEAT IMPREGNATED TEFLON 2n 6 7 /16" 1 13 /16 " 3 1 /4 " ' 5 1 /16 " 3 7 /8" 2 5 /e" 8 1 /4" 10 718" HANDLE LOCK TE SPRING STEEL 163.38mm 4550mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm * *3/4" Valve UL listed only. USA PATENT AND OTHER PATENTS PENDING - UL US11NG EX4D19 AGF Manufacturing Inc. JOB NAME: 100 Quaker Lane, Malvern, PA 19355 _ F T: (610) 240.4900 / F: (610) 240 -4906 ARCHITECT: Ema Info ®t effim, drain .com Web: www.testandraln.eom ENGINEER: Reliability, Versatility, Code. Compatibility MADE IN USA CONTRACTOR: R RherPAr K and TEBTmORAIN we registered eadeeta"re of AGF 3/02 MODEL 7000 AP PRESSURE RELIEF VALVE The AGF Manufacturing Inc. Model 7000 is a UL Listed /FM Approved Relief Valve Designed Specifically For Fire Sprinkler Systems, It Relieves Excess System Pressure Caused By Surges Or Temperature Changes. The Model 7000 Complies With The Requirements of NFPA -13 That Stipulates A Pressure Relief Valve Be Installed On All Gridded Systems And Downstream Of All Pressure Reducing Valves. The Model 7000 Is Included With Our TESTANDRAIN Model 1011, 1011T and 3011 Inspector's Test Valves. UL Listed Pressure Relief Valve EX 4533 (N) ❑ UL Listed And FM Approved. 4 ❑ Bronze Body With Stainless Steel Spring. ❑ Integral Flushing Handle To Remove Debris Causing Leaks � Through Valve Seat And Disc. F ❑ 1/2" IPT Inlet And Outlet. l„ 1 ❑ Factory Set At 175 PSI.* C ,F ❑ 165 PSI Through 205 PSI Available for Special Applications � y . tv, With Other Settings Available.* • * Note: It is important to note that the pressure rating of the relief valve indicates an _- i A operating range of pressure for both opening and closing of the valve. Standard relief H valves are required to OPEN in a range of pressure between 90% and 105% of their rating. The valves are required to CLOSE at a pressure above 80% of that rating. �y ate; ; The relief valve should be installed where it is easily accessible for maintenance. Care x� ' should be taken that the relief valve CANNOT be isolated from the system when the "t system is operational. A relief valve should NEVER have a shutoff valve or a plug downstream _.: L,�.._..,_.. of its outlet. "-- B -' bou out New AutoC-40 1 3 /4 " 1" 3 5/16" Gr eta on t he te rnet S. at A B 43.97mm 25.03mm 82.84mm www.testandrain.com . The AGF Manufacturing, Inc. provides many different products to address a variety of job conditions. Please contact our office for advice and products modified to solve specific job conditions. Call Our Office For New Product Information. Thank You For Using Our Products. .. AGF MANUFACTURING INC. JOB NAME: 100 Quaker Lane ARCHITECT: MADE IN U.S.A. Malvern, PA 19355 USA Telephone: (610) 240 -4900 ENGINEER: Fax: (610) 240-4906 CONTRACTOR: 9/01 www.testandrain.com Mechanical Pressure Measurement Bourdon Tube Pressure Gauge Type 111.10SP Sprinkler Gauge 6 yPao6-7-0o06,1 Standard Series WIKA Datasheet 111.10SP Applications �� t' i I' f � " 40 50 .60 ' 1 . \ • Fire sprinkler systems E Suitable for all media that will not obstruct the pressure � � 30 70 SPRIN system or attack copper alloy parts " ~ 20 841, r" ^' \ 0 ATER • ' 250 ' <==- psi Q _, 4> Special features APPROVED Iv • UL- listed (UL -393) • Factory Mutual (FM) approved tJ • Reliable and economical Standard Features Bourdon Tube Pressure Gauge Type 111.10SP Design Pressure connection EN 837 - & ASME B40.100 Material: copper alloy 1/4" NPT lower mount (LM) Sizes 4" (100 mm) Movement Copper alloy Accuracy class * 3/2/3% of span (ASME B40.100 Grade B) Dial White aluminum with stop pin; black and red lettering Ranges 0/80 psi, retard to 250 psi (air) Pointer 0/300 psi (water) Black aluminum Working pressure Case Steady: 3/4 of full scale value Black polycarbonate Fluctuating: 2/3 of full scale value Short time: full scale value Window Snap -in clear polycarbonate Operating temperature Approvals Ambient: -40 °F to 140 °F ( -40 °C to 60 °C) UL listed (UL -393) Media: 140 °F ( +60 °C) maximum Factory Mutual Temperature error Additional error when temperature changes from reference temperature of 68 °F (20 °C) ±0.4% for every 18 °F (10 °C) rising or falling. Percentage of span. Bourdon tube Material: copper alloy C -type WIKA Datasheet 111.10SP • 03/2005 Page 1 of 2 IWIKAIj ® Part of your business Optional Extras Dimensions (not all options are UL or FM approved) A. C —{ • Brass restrictor Lr . • Friction -fit cover ring (requires steel case) • Glass window (requires steel case & friction ring) • Black- painted steel case . • Stainless steel case • Special case colors • Nickel- plated connection • Custom dial layout • Special threaded connection 11 I A W(sq) ES • Custom dial layout T(NPT) • Other pressure scales available: bar, kPa, MPa, kg /cm and dual scales • Size A B C E L T W Weight 4" mm 100 83.5 30 11.5 3.75 14 in 4.0 3.29 1.18 0.45 0.15 1/4" 0.55 0.35 lb. Page 2 of 2 WIKA Datasheet 111.10SP 03/2005 ordering ugdn ! W 1 KA Pressure gauge e mo model / Nominal size / Scale range / Size of connection / Optional extras required Specifications and dimensions given in this leaflet represent the state of engineering at the time of printing. Modifications may take place and materials specified may be replaced by others without prior notice. WIKA Instrument Corporation 1000 Wiegand Boulevard Lawrenceville, GA 30045 Tel (770) 513 -8200 Toll -free 1- 888 -WIKA -USA Fax (770) 338 -5118 E -Mall info@wika.com www.wika.com & 14 ea o67- bQO CQ/ .7 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 001/020 SWAY BRACE FITTING - MODEL E Part p077 � 1 1 r;t SIZE - Pipe to be braced: 1" thru 8" Steel SCH 7 thru 40 IPS. Pipe used for bracing: 1" and 1 1/4" SCH 40 IPS. MATERIAL - Carbon Steel. FINISH - Plain, Electro- Galvanized, H.D.G. and Stainless Steel. LISTINGS c u us EX 2625 Listed only for use with other AFCON bracing products. OSHPD pending. PATENT - No. 3,570,794 FUNCTION - Sway brace fitting of a lateral sway brace assembly, consisting / additionally of AFCON 70 series attachment fitting and pipe brace element forming a complete sway brace assembly '/1111■1.. INSTALLATION - Per NFPA -13. Arrange adjacent lateral sway braces to form a 4 -way. ASSEMBLY - Place Model E over pipe to be braced. Insert brace pipe through MODEL "E" under channel bracket, leaving 1" minimum extension beyond. Tighten both hex nuts until gage spring lays flat or torque to 65 in. -lb. FEATURES * UL Horizontal Load Ratings: 2015# Sch. 10 thru 40, All Sizes 655# Sch. 7 - 1" thru 4" 1500# Sch. 7 - 6" 4N/ * Visual inspection, proper installation when gage spring lays flat. ORDERING - Part #, pipe size to be braced, brace pipe size and finish. 6/05 6...... ...... • 7 gz • P.O. Box 3365 South El Monte, CA 91733 626.444:0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER . . ; i.i,„„r„.,--\\\ ) i i / l \� //' �'/ IMPERIAL MAX REC. METRIC' • 112 and 314 inch pip 1 thru 4Inch pipe e PIPE - ROD LOAD LBS. PIPE ROD LISTED FOR STEEUCPVC 5 thru 8lnch pipe 1/2 3/8 400 _ 10 3/4 318 400 20 10 1 3/8 400 25 10 11/4 3/8 400 32 10 11/2 3/8 400 40 1.0 . 2 3/8 400 50 10 SIZE - 1/2 thru 8 inch pipe. 21/2 318 600 65 10 MATERIAL - Carbon Steel, Mil. Galvanized to G -90 spec. 3 3/e 600 80 10 LISTINGS - O 3/8 10 C G US EX 2551 31n 600 0 Approval guide - Pipe Hangers 4 1000 100 to CONFORMS WITH: Federal Specification WW -H -171 (Type 10, 5 1/2 1250 125 12 Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10). 6 1f2 1250 150 12 MAXIMUM TEMPERATURE - 650 °F. • 8 1/2 1250 200 12 FUNCTION - Pipe hanger component for use on steel, CPVC or • Order Part #300m copper piping. Note: 16." Ring Hanger not <FM> approved INSTALLATION - Per NFPA -13, 13R and 13D. FEATURES- . * Sized and listed exclusively for use with #310 Surge Restrainer. * Band edge is offset for EASY pipe insertion. * Custom fit swivel nut for better retention in ring body. pipe A B * Full length knurl on swivel nut for better , 1 1 P 1 w 2.1782 WM ORDERING - Part #, pipe size. — -T 1 In an ae,.o B 2 2.4548 32516 AI i 2fa 74220 4.1145 . ,,,�1 W 7.7845 4.4311 4 42332 AM Y. I 82888 6.8145 5 7.5388 62210 s 8/05 ::a it. w -_ •,,, AW.J, • ,Z00z • • 1 . • BEAM CLAMP 3/4 MOUTH • - • 4/ SIZE - 3/8" and 1/2" rod. V MATERIAL - Ductile iron with hardened cup point set screw and jam nut. FINISH - Plain, Electro - Galvanized and H.D.G. and Stainless Steel. LISTINGS - c \&us EX 2551 Q Approval guide - Pipe Hangers V CONFORMS WITH: Federal Specification WW H -171E Type 19 and 23 and ' Manufactures Standardization Society ANSI/MSS -SP -58 Type 19 and 23. FUNCTION - Hanger assembly attachment to steel flange with thickness of less than 3/4 ". INSTALLATION - Per NFPA -13 with set screw up or down. Install in V V accordance with ANSI/MSS- SP -69. Torque - 3/8 "= 60 inch pounds. Torque - 1/2 "= 125 inch pounds. In the absence of a torque wrench, engage set bolt finger tight then additionally tighten 1/3 turn. FEATURES * Maintains CONSTANT HANGER CENTER -LINE, with set screw up or down. * Flat throat back prevents twisting during installation. ORDERING - Part #, rod size and finish. P' 12/03 .7 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 162 UNIVERSAL RESTRAINING STRAP Nut optional, if insufficient rod dimension • SIZE- One size fits both 3/8" and 1/2" rod or set screw. Available lengths 4" and longer. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - c O us EX 2551 PATENT - No. 5,897,088 FUNCTION - To enhance hanger attachment in areas subject to Earthquakes. INSTALLATION - Install tight to structure and component parts Minimum return on strap: 1" L- dimension is measured from hanger rod center to the strap end. FEATURES * Fast installation for new construction or retrofit. * Requires no hanger disassembly to install. IMPORTANT NOTE: "No Nut Is Required" When installed tight to structure and component parts. (See drawings I � provided) _ ORDERING - Part # and L- dimension. 11/04 /: // 6 (, Pa06 - 000(9/ . D UNITED BRASS WORKS, INC. N III III 714 S. Main St. , Randleman, NC 27317 1S09001 Tel: 800 - 334 -3035 Fax: 800 - 498 -4696 www.ubw.com REGISTERED COMPANY • Model 80 Ball Valve . Double Female (Complies with MSS- SP110 -92) 200 lbs. WSP @ 406 ° Max 400 lbs. WOG * 100% Pressure Tested Threaded Ends * Blowout Proof Stem 1 /4" - Full Flow 3 /4" - 2" Large Port Diameters f F 0 0 . MATERIAL LIST , __ : ° IMII NO. DESCRIPTION MATERIAL _ o 1 Lever Plated Steel w/ vinyl grip n '%\ 2 Stem Brass 3 Jam Nut Plated Steel ' 3� 4-mj 0 4 Packing Nut Brass I'lll , I'l O 5 Packing Sleeve Brass 'I 6 Packing Graphite Non -Asb. Il l'II,II, ,�ItII� 7 Bevel Washer Steel / / /�i:'- 7 A . 8 0-Ring Buna 0 9 Tail Piece ('/" - %z ") Brass 0 Tail Piece (3/4" - 2 ") Bronze 09 10 Body Bronze Qo 11 Ball Chrome Plated Brass C D 12 Nest PTFE B i SHIP QUAN. SIZE A B C D E F WT. (lbs.) PER CTN. '/." 0.38 1.86 0.92 0.94 1.58 3.31 0.52 12 3/8" 0.38 1.86 0.92 0.94 1.58 3.31 0.52 12 Y2" 0.50 2.17 1.06 1.11 2.28 4.23 0.78 12 3 /." 0.63 2.05 1.20 1.31 2.38 4.23 0.98 12 1" 0.81 3.27 1.67 1.59 2.55 4.23 1.59 6 - 1 '' /." 1.00 3.48 1.72 1.77 3.19 5.47 2.47 4 - 1 Y2" 1.25 3.97 1.95 2.02 3.38 5.47 3.50 4 2" 1.50 4.41 2.14 2.27 3.56 5.47 5.00 2 2 G 14 e 007 - a oo ('f IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS 10.03 VICTAUUC IS AN 1509001 CERTIFIED COMPANY FireLock® Fittings - PRODUCT DESCRIPTION • FireLock® products comprise a unique system specifically designed for fire protection services. FireLock . full -flow elbows and tees are a CAD - developed, hydrodynamic design that has a shorter center -to -end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. 1 :• ,; FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 �., couplings. ^ s. - Patented ' 2 See Victaulic publication 10.01 - „ for details. DIMENSIONS 1•C to E No. 001 No. 003 No. 002 No. 006 I '� a Fitting Size 90• Elbow 45° Elbow StratghtTee Cap U C to E Actual Cr- p - C ®O Nominal Outside C to E Weight C to E Wight C to E Weigh Thi428813 W Ight J,,�' Diameter Diameter Inches Each Inches Each Inches Each Inches Each t o E Incheslmm Incheslmm mm Lbs/kg mm 119/41 mm Lbs/ mm kg Lbs/kg 1_ ie No. 001 No. 003 1V, 1.660 - - - - - - 0.82 0.3 32 42.4 - - - - - - 21 0.1 C 1 1.900 2.75 1.2 1.75 0.9 2.75 2.0 0.82 0.4 ta - to E 1 40 48.3 70 0.5 45 4.1 70 0.9 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 �- -� 0 i7�• -w - C /,(I 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 3.1 = ,i = . to 11 / 6' 2 7 3.0 3.00 1.4 2 57 5 1.02 3.00 1 .6 0.88 1 22 No. 002 No. 006 76.1 mm 3.000 3.00 3.30 2.25 2.4 - - - - 76.1 76 1.5 57 1.1 - - - - 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 BO 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - - 108.0 102 2.6 76 2.3 102 3.4 - - 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 159 mm 6.250 5.50 12.6 3.50 9.2 3.50 17.9 - - 158.8 140 5.7 89 4.2 140 8.0 - - 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 23 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 0 REGISTERED TRADEMARK OF VICTAUUC - 0 COPYRIGHT 2038 VICTAUUC - PRINTED IN USA - MU MICAS-67PJUx 1539 REV F United States • Phone: 1-800-PICK-VIC (1 -810. 742.5842) • Fax: 610.250 -8817 • e -mail: pickvic@vioaulic.com Canada • Phone: 905. 884 -7444 • Fax: 905 -884 -9774 • e -mail: viccanada@viclaulic.cam Europe • Phone: 32- 9- 381 -1500 • Fax: 32 -9 -380 -4438 • e -mail: vicetro@vidaulic.be UK • Phone: 44(0)1438741100 • Fax: 44(0)1438313883 • e -mail: viceuro@viclaulic.be Central and South America • Phone: 610 - 559 -3300 • Fax: 610.559 -3608 • e -mail: vital @victaulic.com Cta1 U 1 i C Australasia • Phone: 86.21- 54253300 • Fax: 86 -21. 54253671 • e -mail: vicap@victaulic.com • • 10:03', FLOW DATA Frictional Resistance - - Fitting Size Equivalent Feet/meters of Straight Pipe Actual StraightTee Nominal Outside No. 002 • Diameter Diameter 90° Elbow 45° Elbow • Incheslmm Inches/mm No. 001 No. 003 Branch Run • • 1 1.660 1.5 0.8 3.7' 1.5 • 32 42.4 0.5 0.2 1.1 0.5 • 1 1.900 2.2 1.1 5.5 2.2 • • 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 2 2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 . 76.1 1.4 0.7 3.4 1.4 • 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 . 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 • 1.3 6.4 2.6 . 159 mm 6.250 9.4 . 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 .7.6 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 t The flow data listed is based upon the pressure drop of Schedule 40 pipe. • MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A -536, grade 65 -45 -12 • Fitting Coating: Orange enamel . • • Optional: Hot dipped galvanized • • • This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications. designs and standard equipment without notice and without incurring obligations. 2 FireLock Fittings • IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS ;-' vicauOC• IS AN ISO BS1 CERiIFED COMPANY Style 009 FireLock EZTM Rigid Coupling • • VIC 1 -r Gasket System • PRODUCT DESCRIPTION • • The Style 009 Fire Lock EZ rigid coupling is a revolutionary patent - pending new way to join fire protection j piping systems in the quickest manner possible. The unique design permits the installer to assemble a joint without disassembling the bolts, nuts, gasket and housings. This installation -ready coupling is easily r e '",---------c: - `j I , , stabbed on pipe grooved to Victaulic specifications, which speeds and eases assembly. The Style 009 '; coupling reduces effort and eliminates the potential of dropped fasteners. The Style 009 provides rigidity with its angle bolt pad design. The Style 009 is rigid and does not - accommodate expansion, contraction or angular deflection. Support and hanging requirements 1 ;!,, correspond to NFPA 13 Sprinkler Systems. �� ° = Style 009 FireLock Q rigid couplings with the Vic -PlusTm Gasket System are recommended for use �" ONLY on fire protection systems. Patent Pending Vic-Plus Gasket System: Vli® em hi d c o pipe systems are hydrostatically ictau coffers tested. a The gasket Vic Plu System ch requires (patented) no fiel is lubri dry, clean , and n wet non toxic. It reduces that assembly CI. US © time Substantially and eliminates the mess and chance of over - lubrication. Please refer to the latest copy of the Victaulic Feld Installation Handbook (1 -100) for supplemental and for dry pipe fire protection systems. See Victaulic • publication 10.01 for details. DIMENSIONS . Y re-Z-1 Dimensions I Inches/trim / ,., al Actual Max. Max Allow. ( re assembled � - , ,. Nominal , Outside Work 0 ut BoltM condition Joint Assembled �� IJj �� _� . �� Sim Diameter Press. • Load' Sep. f End Pipe End No.- Sim ) Wet. Ea Inches/ram Inctteslmm PSIIkPe LOON InJmm Inches/mm X Y X Y Z LbsJkg \ Ito 1 '/. 1.660 300 649 0.10 3 3.13 4.93 2.86 4.83 1.93 1.5 Style 009 Pre - assembled 32 42.4 2068 2888 2.54 2 - /s X 2 80 125 73 123 49 0.7 (Stab in condition) 1 1.900 - 300 851 0.10 2 - 3/e X _ 2 3.38 5.16 3.11 5.07 1.86 1.7 40 48.3 2088 3787 2.54 86 131 79 129 47 0.8 2 2.375 300 1329 0.12 3 , 3.88 5.81 3.59 5.68 1.86 1.9 Y �i Z 50 60.3 2068 5914 3.05 2 " / X 2 / 2 99 148 91 144 47 0.9 A I i 2 ' /z 2.875 300 1948 0.12 3 4.36 6.21 4.08 6.10 1.87 2.0 65 73.0 2068 8888 3.05 2 - /e X 2 1 /2 111 159 104 155 48 0.9 0 3 4 300 300 2886 .12 , � � e0 88.9 2068 12842 X 3.05 2 - 3 /a X 2' /z 5.03 6.88 4.70 6.72 1 2.3 0 4771 � 100 403 2068 21230 0 4.32 2 3/e X 2 6.5 9 E 206 5.5 4 8.01 2 1 .8 . Style 009 Joint Assembled • r© t Refer to notes on below. • • NOTES . • Working Pressure and End Load are total, from all Internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. See page 2 of this document for Listed /Approved ratings on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY. the Maximum Joint Working Pressure may be increased to 1'/2 times the figures shown. t The.ellowable pipe separation dimension shown is for system layout purposes only. FireLock EZ couplings are considered rigid connections and will not accommodate ex- pansion or contraction of the piping system. 0 Number of bolts required equals number of housing segments. NOTE: When assembling Style 009 couplings onto FireLock end caps, take additional care to make certain the cap is fully seated against the gasket end stop. Please make certain the 4' No. 006 cap includes an 'EZ' mark on its reverse side to ensure compatibility. WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. - All products shall be installed In accordance wit h current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. S REGISTERED TRADEMARK OF VICrAUUG - O COPYRIGh1T 5 VICTAUUC - PR@RED iN U.S.A. -WU NNCAS C30AX 3995 REV B United States • Phone:1 -800- PICK -VIC (1-800-742-5842) • Fax: 610- 250 -8817 • e -mail: pickvic®vidaulic.com Careda • Phone: 905 - 884 -7444 • Fax 905-884 -9774 • e-mail: vicranad®victaulic.com Europe • Phone: 32 -9-381 -1500 • Fax 32-9- 380-4438 • e -mail: viceuro@vidaulic.be UK • Phone: 44(0)1438741100 • Fax 44(0)1438313883 • e -mail: viauro®victaulicbe , ��^ ■ LI . �, � Central and South America • Phone: 610- 559 -3300 • Fax 610 - 559 -3608 • e -mail: vical@victaulic.com v Australasia • Phone: 86-21-54253300 Ext 202 • Fax: 86-21- 54253671 • e -mail: vicap®victaulic.com 10A0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A -536, grade 65- 45-12. Ductile iron conforming to ASTM A -395, grade 65- 45 -15, is available upon special request. • Housing Coating: Orange enamel • Gasket: • Grade "E" EPDM - Type AA FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories • of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure using the Grade "E° Type A Vic - Plus Gasket System. Bolts/Nuts: Heat - treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A - 183. "Standard Style 009 gasket approved for dry pipe systems to- 40°F/-40°C. Based on' typical° pipe surface conditions, supplemental lubricant is recommended for services Installed below D'F/-18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water. Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. LISTINGS /APPROVALS t* The information provided below is based on the latest listing and approval data at the time of publication. Listings /Approvals are subject to change and /or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Pressure Rating - psi Pressure Rating - psi • Pressure Rating- psi Pipe Size Pipe Size Pipe Size Sch. Inches UL ' ULC FM Sch. Inches UL ULC FM Sch. Inches UL ULC Fld 5 1 - 2 175 175 175 EZT 1 2 300 300 300 MT 1 - 2 300 300 300 10, 40 1 4 300 300 300 FF 1 - 4 300 300 300 MLT 1 2 300 300 300 BLT 1 300 300 300 FLF 1 4 N/A N/A 300 ST 1 - 2 N/A N/A 300 DF 1'/4 - 4 300 300 300 FLT 1 - 2 N/A N/A 300 STF 1 4 N/A N/A 300 DT 1'/4 - 2 300 300 300 FLTL 1'/4 - 2 N/A N/A 300 TF 2 4 N/A N/A 300 EF 1 - 4 175 175 175 GL 1 - 2 300 ,300 300 WLS 1 - 2 300 300 300 EL 1 - 2 300 , 300 300 G5 1 - 2 175 175 175 WST 1 2 175 175 175 ET40 1 2 300 300 300 G7 1 - 2 300 300 300 XL 1 - 2 300 300 300 EZF 3 - 4 300 300 300 MF 1 - 4 300 300 300 • PIPE SCHEDULE NOTES: 5 refers to Listed/Approved Schedule 5 steel sprinkler pipe 10 refers to Listed /Approved Schedule 10 steel sprinkler pipe 40 refers'to Listed /Approved Schedule 40 steel sprinkler pipe BLT refers to Listed/Approved BLT steel sprinkler pipe manufactured by Allied Tube & Conduit OF refers to Listed/Approved Dyna -Flow steel sprinkler pipe manufactured by Allied Tube & Conduit DT refers to Listed/Approved Dyne- Thread steel sprinkler pipe manufactured by Allied Tube & Conduit EF refers to Listed /Approved Eddy Flow steel sprinkler pipe manufactured by Bull Moose Tube Company EL refers to Listed /Approved Eddylite steel sprinkler pipe manufactured by Bull Moose Tube Company Er40 refers to Listed/Approved Eddythread 40 steel sprinkler pipe manufactured by Bull Moose Tube Company • EZF refers to Listed/Approved EZ -Flow steel sprinkler pipe manufactured by Northwest Pipe Company • EZT refers to Listed/Approved EZ- Thread steel sprinkler pipe manufactured by Youngstown Tube Company FF refers to Listed/Approved Fire -Flo steel sprinkler pipe manufactured by Youngstown Tube Company FLF refers to Approved Fireline Fireflow steel sprinkler pipe manufactured by Western International Forest Products FLT refers to Approved Fireline Rapid- Thread steel sprinkler pipe manufactured by Western International Forest Products FLTL raters to Approved Fireline Rapid - Thread Light steel sprinkler pipe manufactured by Western International Forest Products GL or MLT refers to Listed/Approved GL and MLT steel sprinkler pipe manufactured by Wheatland Tube Company G5 or G7 refers to Llsted/Approved GAL 5 and GAL 7 steel sprinkler pipe manufactured by Idod Systems, LLC MF refers to Listed/Approved Mega-Row steel sprinkler pipe manufactured by Wheatland Tube Company MT refers to Listed /Approved Mega -Thread steel sprinkler pipe manufactured by Wheatland Tube Company STF refers to Approved Steady- Thread steel sprinkler pipe manufactured by AMS Tube Company ST refers to Approved Steady -Flow steel sprinkler pipe manufactured by AMS Tube Company ' TF refers to Approved Tex -Flow steel sprinkler pipe manufactured by Tex Tube Company WLS refers to Llsted/Approved WLS steel sprinkler pipe manufactured by Wheatland Tube Company WST refers to Listed/Approved WST (schedule 5) steel sprinkler pipe manufactured by Wheatland Tube Company XL refers to Listed /Approved XL steel sprinkler pipe manufactured by Allied Tube & Conduit t Listed /Approved for wet and dry pipe systems. Victaulic recommends the use of Style 009 rigid couplings on systems operating above 0°F / -18 °C. For rigid pipe connections in systems operating below esF/-18°C Victaulic recommends Style 005 RreLock rigid couplings with Grade °L° silicone gaskets. *Please refer to the Victaulic Field Installation Handbook (1 -100) for details concerning when supplemental lubrication is required. 2 Style 009 FireLock EZTM Rigid Coupling IPS CARBON STEEL PIPE - GROOVED COUPLINGS 06.0$ VICTAULIC• IS AN ISO 9001 CERTIFIED COMPANY • Style 750 Reducing Coupling PRODUCT DESCRIPTION . The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed to replace two . couplings and a reducing fitting, the Style 750 features a special reducing gasket for pressure responsive �;. ",. „,. }p;, ,, ` g P P 9 P P 9 P P g ? sealin A steel washer which revents telesco in of the smaller i e inside the lar er i e Burin ft , , ;:.r ;` . vertical systems assembly is available upon request. 0 . i . WS rrh i 5 1 .. See Vctaulic publication 10.01 111°11 for details. Hill f Exaggerated for clarity DIMENSIONS r Y k-Z ►I film. Max. Allow. Fr. Dimensions Ap Work End Pipe Q Ihheheslmllllhneters Wgt. .���. Nominal Size Pros. Load End f Per Pipe Batt/Nut � • ` i r ■ El Inches PSP Lbs.* Sep. to. Cplg. InJR. No. - Size Lbs. _ (� mm kPa N mm Deg. mmlm Inches X Y Z kg \` tv) 2 X 1 350 1000 0 - 0.07 0 57' 0.20 2 - 3/ X 2 3.38 5.28 1.88 2.7 50 X 25 2410 4450 0 - 1.8 17 85 134 48 1,2 X 1 350. 1000 0 - 0.07 0 ° 57' 0.20 2 - 3 !e X 2 3.38 5.28 1.88 2.0 X 40 2410 4450 0 - 1,8 17 85 134 46 1,0 2 X 2 500 2215 0 - 0.07 0° 47 0.16 2 3 / B X 2 4.00 5.93 1.88 3.1 I Y .-Z 65 X 50 3450 9850 0 - 1,8 14 102 151 48 1,4 ^\ 76,1 mm X 2 350 1550 0 - 0.07 0 °- 47• 0.16 2 1/2 X 23/4 4.38 6.63 1.88 4.6 riir r.r, M� 11 1 1 1 `I � II` 11 3 X 2 350 1550 0 - 0.07 0 °- 39' 0.13 2 - X 23/3 4.75 7.13 1.88 4.9 \`� dm X 50 2410 6900 0 - 1,8 11 121 181 48 2.2 X 2'h 500 3250 0 - 0.07 X 65 3450 14460 0 - 1.8 0° 39 . 0.13 2 1 /2 X 23/, 4.75 7.13 1.88 4.3 11 121 181 48 2,0 88,9 mm X 76,1 mm 350 2275 0 - 0.07 0° 39 . 0.13 2 1 /2 X 23/4 4.75 7.13 1.88 4.2 2410 10125 0 - 1.8 11 121 181 48 1,9 4 X 2 350 100 X 50 2410 1550 D O 3 2 3 1 °- 19' 0.28 2 - /9 X 31/4 6.25 59 2 26 2.2.1 57 3 ,7 X X 2 65 2 2410 10125 O o 2 3 1 °- 19' 0.28 2 - 5 /s X 3 6 58 8.90 26 2.25 3 .9 X 3 500 4810 0 - 0.13 1 ° 19 . 0.28 2. X 3'/. 6.00 8.90 2.25 6.7 X 80 3450 21400 0 - 3,2 25 152 226 57 3,0 114,3 mm X 76,1 mm 350 2275 0 - 0.13 1 . - 19 . 0.28 2 - 5 / e X 31/ 6.25 8.90 2.25 6.9 X 2410 10125 0 - 3.2 2 5 159 226 57 3.1 5 X 4 350 5565 0 - 0.13 1 • 3. 0.22 2 3/ i X 41/4 7.18 10.70 2.13 11.2 125 X 100 2410 24765 0 - 3,2 1 9 182 272 54 5.1 6 X 4 350 5565 0 - 0 . 1 3 0 ° - 52' 0.18 2 - 3 /4 X 41/4 8.63 11.90 2.25 16.7 150 X 100 2410 24765 0 - 3,2 15 181 302 57 7,6 X 5 350 X 125 2 10 8500 0 0.13 0 °- 52' 0.18 2 - 3 /4 X 41/ 8.31 13 Z0 2.25 12.9 165,1 mm X 4 350 5565 0 - 0.13 0 °_ 55' 0.19 2 3 / 4 X 41/ 8.63 11.90 2.25 15.2 X 100 2410 24765 0 - 3,2 16 219 302 57 6,9 8 X 6 350 12000 0 - 0.13 0 ° 38' 0.13 2 - 7 /8 X 5 10.81 14.88 2.50 22.4 - 200 X 150 2410 53400 0 - 3,2 11 275 378 64 10.2 - Refer to notes on page 3. Style 750 Reducing couplings should not be used with end caps (A60) in systems where a vacuum may be developed. Contact Victaulic for details. 4D REGISTERED TRADEMARK OF WCTAUUC - 0 COPYRIGHT 2005 VICTAUUC - PRIMED IN USA -SKU OWCAS68AO3IP 1535 REV 0 Victaulic Company of America • Phone: PICK -VIC (1- 800 - 742 -5842) • Fax: 610 - 250 -8817 • e -mail: pickvic@vittaulic.com Victaulic Company of Canada • Phone: 905. 884 -7444 • Fax: 905 -884 -9774 • e -mail: viccanada@victaulic.com Victaulic Europe • Phone:32-9-381-1500 • Fax: 32-9-380-4438 • e -mail: viceuro@viclaulic.be jctaulice Victaulic America Latina • Phone: 610- 559 -3300 • Fax: 610. 559 -3608 • e -mail: vical@vkxaulic.com Victaulic Asia Pacific • Phone: 86 -21- 58855151 • Fax: 86-21- 58851298 • e -mail: vicap@victaulic.com • 06.08 . • FLOW DATA Head Loss Flow Reducing Flow Expanding The head loss across Style 750 D Equiv. Pipe 'v. Pipe Reducing coupling is very Nominal Si Inc Length Nominal Sim Length hes small and is essentially the m m S Feet/m mm� S Feeten same as for standard short 2 X 1 5.9 1 X 2 2.7 body reducing pipe fittings. 50 X 25 1,8 25 X 50 0,8 Equivalent lengths of standard x 1 'h 2.0 1 Vh X 2 1.9 weight steel pipe are shown in X 40 0,6 40 X 50 0.6 the tables. All data is based on 2'h X 2 1.9 2 X 2 1.0 water flowing at ambient ss x So o,s so x ss o.3 - temperature. 76.1 mm X 50 0.6 X 76,1 mm 0.30 3 X 2 5.5 X 3 3.5 8o x 50 1.7 x 80 1.1 X 2 �h 3.8 X 4 3.0 X 65 1.2 x 100 0,9 3.8 2 65 X 3 2.5 88,9 mm X 76.1 mm 1.2 ss x eo 0.8 4 X 2 6.0 X 4 3.0 100 x 50 1,8 X too 0,9 X 65 fi,e 76.1 mm X 88.9 mm 0.8 X 3 6.0 X 114.3 mm 3.0 X BO 1.8 0.9 114,3 mm X 76,1 mm 6.0 3 X 0 .8 0 1,8 BO X 100 0.8 5 X 4 3.0 4 X 5 3.3 • 125 X 100 0.9 100 X 125 1.0 6 X 4 6.0 X 6 4.6 150 X 100 1,8 X 150 1.4 X 5 4.5 X 4.6 X 125 , 1.4 X 165,1 mm 1,4 165,1 mm X 4 6.0 5 X 6 2.3 X 100 LB 125 X 150 0.7 8 X 6 7.3 6 X 8 6.0 200 X 150 2,2 150 X 200 1.8 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A -536, grade 65- 45 -12. Ductile iron conforming to ASTM A -395, grade 65- 45 -15, is available upon special request. Housing Coating: Orange enamel • Optional: Hot dipped galvanized and others Gasket: (Specify choice °): • Grade "E" EPDM EPDM (Green color code). Temperature range -30 °F to +230 °F ( -34 °C to +110 °C). Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil -free air and many chemical services. UL classified in accordance with ANSI /NSF 61 for cold +86 °F ( +30 °C) and hot +180 °F ( +82 °C) potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade "T' nitrile Nitrile (Orange color code). Temperature range -20 °F to +180 °F ( -29 °C to +82 °C). Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150 °F ( +66 °C) or for hot dry air over +140 °F ( +60 °C). *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which . are not recommended. • Optional: Assembly Washer: Galvanized, carbon steel • Bolts/Nuts: Heat - treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A -449 and physical requirements of ASTM A -183. • 2 Style 750 Reducing Coupling I ,r 6 y e ao-7- _0006,, FIG. 351 90° Elbow - Straight Ai .Star - g Fire Products Division of anal' Inmmaeonal . =� L Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet a . APPROVED • For Listing / Approval details contact your AnvilStar'"' Representative. FIGURE 351 90° ELBOW STRAIGHT Weight Size A B block gals. B NPS/DN In./mm la /mm Ibs,/kg Ibs./kg A-1 I 1/4 in I 0.16 0.17 8 13 2 2 0.07 0.08 3 r9 9 /16 1 /16 0.25 0.26 f 1 ill 1 10 14 24 0.11 0.12 BA 1h nA, 1 0.4 0.41 I - iiiiiiiiiiiiii 15 17 29 0.18 0.19 3 /4 '3/46 13/46 0.6 0.61 20 22 33 0.27 0.28 1 13/46 11/2 0.92 0.95 25 24 38 0.42 0.43 1 11/2 1 1.4 1.5 32 29 44 0.65 0.66 11/2 13/46 113/46 2 2 40 33 49 0.88 0.91 2 1 2 3.1 3.2 50 40 57 1.4 1.5 21/4 1 2 4.9 5.1 65 47 68 2.2 23 3 2 3 7.2 7.4 80 56 79 3.3 3.4 4 2 /16 3% 12 13 100 68 98 5.5 5.7 5 3 41/4 21 - 125 84 114 10 - 6 3 51/4 31 33 150 98 130 14 15 8 5 6 65 67 200 132 167 29 30 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are • Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME -B16.4 (except plugs 1 /4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Dimensions also conform to Inspected Fire Protection Equipment and Materials" issued by Federal Specifications, WW- P- 501(except plugs and bushings the Underwriters' Laboratories, Inc. WW -P -471). NOTE: See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most cement listings and apprarals. • PROJECT INFORMATION: APPROVAL STAMP: Project: Date: I Phone: • Architect / Engineer: Contractor: Address: - Notes 1: Notes 2: Anvil Cast Si Malleable Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule . = ��� IL REV. 03.03.06-001 go to www.anvllstar.com or contact your local AnvilStar representative • FIG. 352 90° Reducing Elbow AMi�Star- Fire Products Division of Anvil' International ti. ANVIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet . FIGURE 352 90° REDUCING ELBOW 0 �© Size A B C 0 Weight Weight A B C 0 black black . APPROVED NPS/DN NPS/DN In /mm In. /mm In/mm Inimm Ibs./kg NPS/DN NPS/DN Inimm Inimm In./mm In,/mm lbs./kg For Listing / Approval 1 /4 6 h 3 /4 1 1 1 /46 0.4 1 11/2 1 11 2 2 3.7 details contact your 1 h 8 16 19 27 21 018 2 h 40 33 47 62 62 _ I7 AnvilStar°"' Representative. 15. 34 54 11 /16 1 1 0.34 fmnt 4 2 19716 114 29A6 29716 4 10 16 17 27 21 0.15 50 40 48 65 65 I.8 3/4 l/ 41 /16 1 /16 1 1 0.51 1 1% 2 2 %6 2 6 20 15 17 22 32 32 0.23 32 41 59 75 75 2 7 1/2 11A6 15/16 1 11 0.67 11/2 1% 2 2 2% 5.7 f a 1 3/4 1 16 4 35 35 0.3 3 40 51 59 �5 1 5 2.6 5 /4 lA6 Ad 1/1d 1/16 0.76 80 2 1% 274 2 2 5.7 20 22 24 37 37 0.34 5p al 51 75 ?5 2.6 2 1 2 /16 3 3 6.4 I/ 11 A6 1 1 1 1 1.1 15 11 27 38 33 0.49 65 48 56 78 78 2.9 1 3 74 1 1 1% 1% 1 3 3 2 2 3 3 8.9 32 20 22 29 41 41 0.46 90 80 56 62 86 86 4.1 ;._D---.1 1 1 3/46 1 1 1% 1.2 2 2 2 3% 3% 12 � I 25 ?a 29 43 43 0.55 50 56 15 92 92 5 1/2 3 /4 1 1% 1 1.5 2 2 2 3 3% 11 J 15 - 19 32 41 41 0.69 4 65 56 70 92 92 5.1 3 /4 4 1 1116 11 A6 1.6 100 3 216 2 16 34 34 11 t 1 - 20 22 33 47 47 A6 0.7 80 56 i 8 92 92 _ 4.8 40 1 1 1/4 1116 1116 1.4 31 216 2 3 3 12 25 25 32 47 47 0.65 90 62 68 94 94 5.4 1 1 1 1 1 1.7 21/2 2146 31/2 4% 4% 20 32 30 32 48 48 0.19 65 73 89 111 III 9 • 1/2 1 1 1% 1 2.2 5 3 21 3 4% 4% 19 15 30 37 35 35 I 125 80 73 87 111 111 8.6 34 1 11/2 2 2 2.2 4 21 3 4% 4% 16 20 33 38 51 51 1 100 73 84 III 111 7.5 2 1 11/26 1 2 2 2.1 3 236 31 41 41 19 50 25 27 37 51 51 0.9 80 59 98 124 124 £8 11/4 1 1 21/46 21/46 2.3 6 4 213/46 31/2 4 4 24 32 30 37 52 52 1.1 150 100 73 98 125 125 11 11/2 136 11/2 21/2 21/2 2.6 5 3 31 5 5 27 40 , 33 , 38 , 54 54 i.2 125 86 98 127 127 12 1 1 1 2 2 2.9 8 6 ' 4 51/2 6% 6% 51 2 25 25 44 59 59 1.3 200 150 106 130 162 162 23 . 65 1 1 /16 1 2% 2 3.4 • 32 30 44 60 60 1.5 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME -816.4 (except plugs 1 /4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Dimensions also conform to I Inspected Fire Protection Equipment and Materials" issued by Federal Specifications, WW- P- 501(except plugs and bushings i the Underwriters' Laboratories, Inc. WW -P -471). I NOTE: See the Technical Data section for pressure- temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: • Date: I Phone: Architect / Engineer: - Contractor: Address: Notes 1: Notes 2: . Anvil Cast & Malleable Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule, :i �InM REV. 03.03.06-002 go to www.anvllstar.com or contact your local AnvilStar representative 4 FIG. 358 Straight Tee A - attar' Fire Products Division of Anil* international (4).---- /�M/IL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet APPROVED • For Listing /Approval FIGURE 358 STRAIGHT TEE details contact your AnvilStartet Representative. Weight Size A B • block golv. NPS/DN In./mm In/mm lbsikg Ibs./kg y, l 13n6 0.22 0.23 i 8 13 22 3 18 sh 1 0.35 0.36 `,. 1� 1 %16 - 1% 0.56 0.16 0.58 T 0.56 15 17 29 0.25 0.16 3/4 13 /16 1 0.84 0.85 20 7 1 _ 33 0.38 039 1 t5A6 11/2 1.3 1.3 25 24 38 0.57 0.59 11/2 1 1 2 2.1 32 29 44 0.9 0.9 192 1 1 2.7 2.7 B�;�B --1 4 33 49 f 1 2 1.2 _ I - _ 2 1 2 4.1 4.3 .A� - A� 50 40 57 1.9 ? 21/2 1 2 6.7 6.8 65 A I B 6. 1 68 3 3.1 ._'; - 1- - --- ; f C j 3 2 3 10 10 80 56 79 4.5 4.6 31/2 2 3 13 14 90 62 87 6 6.3 4 2 3 16 17 100 68 95 7.4 71 5 3 41/2 27 28 125 84 114 12 13 6 3 5 41 41 I50 98 130 19 19 8 5 6 79 81 • 200 132 167 36 37 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME -816.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Dimensions also conform to 1 Inspected Fire Protection Equipment and Materials" issued by Federal Specifications, WW- P- 501(except plugs and bushings ; the Underwriters' Laboratories, Inc. WW -P -471). NOTE: See the Technical Data sedion for pressure - temperature ratings. See AnvilStar Web site For the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: • Date: I Phone: Architect / Engineer: Contractor: Address: Notes 1: Notes 2: Anvil Cast & Malleable Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule, REV. 03.03.06 go to www.anvilstar.com or contact your local AnvilStar representative *4W% FIG. 359 Reducing Tee AN% Star r (ii-r. . Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet YL .. <© D E1 . APPROVED I For Listing /Approval p»�: } ;111 details contact your - -- - ' AnvilStarTM" Representative. C i FIGURE 359 REDUCING TEE Size ElE1111 8 ©III Weta I Sae MEIN D © F Weig t black alv. black ga Iv. NPS 1NNPS 1 f ®mrownwiu1 gor® ®igon lbs. ! lbs. • NPS 1NNPS INN c ®eii ®® ®®®M ®� I n. mm lbs. , lbs. 11��111HINE 0.26 18 25 �migia 1 32 4 3 R 0.49 - lh lh ������� 0.56 7 11111111111111 1 35 0.41 - 15 15 iiiiiiiiis 324 0.68 - s 20 1 t 3/ 0.91 - ® ® ®i!!� 1 16 045 25 2 4 4 HH 1 38 049 - 1 3 4 l��HN�N� 0.79 36 15 HHH 32 2. 3h 0.89 - 5 111111111111111111/ 0.69 1 20 20 ����� 1 /le 0,45 - 111111111111111111111 00..7354 25 25 2 6 ?4 24 36 1 37 1 38 0.51 - 2 D 11111111111i11111111111 0 0 - . 6 2 2 8 7 1/4 1 16 11 /16 2Q 1 1 1 35 0,46 3 1131111111111111111111 0.34 7 15 n 11/46 12 6 1 32 4 1 32 , 3 0. 0.47 ri1✓l6 ®liwi 1 0.76 34 - 2 5 /4 will ��ii 1 37 6 0 -1111111E1111111 1/16 0.99 - 1/4 1h h h 1 1/16 1 /t6 1'/16 1.5 3? 0.45 32 29 29 24 43 43 40 0.68 - 11/2 1 1 1 1 1 1 1.8 - 40 32 32 25 47 47 41 0.63 - MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are ; Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME -B16.4 (except plugs ( 1 /4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Dimensions also conform to 1 Inspected Fire Protection Equipment and Materials" issued by Federal Specifications, WW- P- 501(except plugs and bushings i the Underwriters' Laboratories, Inc. WW -P -471). 1 NOTE: See the Technical Data section for pressure - temperature ratings. See AnvilStar Web site for the most current listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: Date: I Phone: Architect / Engineer: Contractor: Address: ., Notes 1: Notes 2: PAGE 1 OF 5 Anvil Cast & Malleable Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule, _ AMY'L REV. 03.03.06-006 go to www.anvllstar.com or contact your local AnvilStar representative FIG. 3 5 9 Reducing Tee /��r Star ° Fire Products Division of Anvil' International O r ) AniviL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet ® 0 , 4> i4 , -- --,-- , APPROVED F For Listing / Approval* details contact your - AnvilStarTM Representative. FIGURE 359 REDUCING TEE (cent.) Size UDU D ©U Wei t s Size nil , I) © F Wei9 t block � block a Iy NPS IN NPS 41 NPS 1 ®MIETAi,1 ®I®lufl ®�® „II I I lbs.I, N' ON NPS DN NPS 1 11=1111101111=117.1M1111= In. mm lbs. • lbs. 5 HHH 13 .6 INN 045 - 1 40 W 1 3 3 1 49 6 1.5 - s 15 HIM 1 n H� 0.63 - 32 5 0 � 1 ;6 2/16 5 1 3.1 - =241,5 52 1 37 4 H 1 29 1111111/1/1 0.14 - 15 HIl 1 3 1 136 1 43 6 U. 8 - 20 El III 111 11111 lil El 0.8 1 40 2 / 0 HH�H 1 44 Or38 - 1.4 e/4 1 MI ��E1 �� 1.4 - 1 ®® 12 1 I 1 1 6 2.1 2 20 23 1 (Coot.) 11h 25 32 41 1 47 1 1 1/4 1.7 - h 2.4 - 3Z ������ 0 32 40 1/e HH 1/4 1 36 1 32 4? 48 1.1 - 15 H HH 4 332 H 0.58 0.5. 5 HH]H ? 1 3 . 5 - /4 EINE 1/16 1.4 - 2 1 As 2h6 236 4.2 - 20 37 H 0.62 - 65 47 62 56 1.9 - - 1 32 1 25 11111111111111111111 0.69 0. 1/2 1 40 ft Ella 1 38 1 1 54 1 - 25 32 m ' 1 43 36 1 0.81 - 16 5 1 06 11 1 06 57 2/4 3.3 - - 1 40 ® 11111111i11/11111111 2 6 1 2 31 4 1111111M 1 25 6 2.5 - 50 1111111111111®1/11 2.7 = 3 /4 1 h min H 1 h 2N - 3.4 t< 20 40 38 2 54 1.5 h 111111111111111111151 1. 5 36 1 /16 1'A6 2/4 WO 2/4 3.3 - 15 U. 57 50 Hi it I 7 H I1I1HHNH 0 61 - 25 51 2.7 - 1 1 11111111111111 1 36 1.7 -• 174 1 38 48 1 La 2 36 2.9 - 3. 25 43 0.78 32 52 1.3 - 1 40 �� . �� 2 1 3 - 50 2 5 1 40 4 6 1 32 1 38 51 54 1. 3 - - 2 0® ��ii� ii 2.8 _ 2 1'36 136 136 2/4 ® 2/4 3.5 - 50 ® 1.3 50 40 37 40 57 57 1.6 - 12 32 � ' 1 Egli 0.88 - 2h M 1 1 0 6 2 65 5 1 2 2 .2 - - 15 3.7 - 1 40 M 1 /4 H 1496 1 43 36 2.1 5 HE 1 76 1 � 2 2.5 - FA -‘ 1 40 11311111111111111111 11311111111111111111 11311111111111111111 11311111111111111111 2 1 2 - 20 NE 136 1 m 1 4 96 2.5 _ 40 15 H� 1 32 4 Ella Ella 1 4 3 6 0. - 1 3 7 25 1111111M11 1111111M11 5 1 2.1 - '5 20 HH 1 1111111/1 1111111/1 0.77 1 32 HH�H 256 2.3 - 25 ®���� U..6 1 40 HH 1 3 8 2 H 2/e 3.4 - 1 161111111/111111/ 161111111/111111/ 1/ 2/4 en 274 1.1 0 . 9 - 11/4 2 1 36 1 36 1 36 2 50 40 37 40 57 57 1.7 - 1 1 i 40 �1(��HHs� 1 6 2 4 0 2.3 32 m _ 55 H 1116 2' 6 5 � 2 26 4.5 _ 5 HHHH®® 2 .3 22 .9 6 �� 1 4R 2.3 2.4 1 h Nil 174 BIEN 1.7 1 2 /4 Bin 136 1'36 in 1 36 2.5 - • 40 5 32 0.76 0.77 8 50 20 ® 37 40 49 1.1 - 1 20 H1iHH 1 31 6 H 0.81 - 2 1 40 2 1111111111/111 51 1. 1 - 32 � 5 ®IeH�iH 1 47 0.89 0.9 1 32 HH�� 2 5 6 3 4 - 1324 NH 32 4 EIHH 2 1 3 - 1 40 HH 1 38 5 1 54 3.2 .5 - PAGE 2 OF 5 Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, REV. 03.03.06007 go to www.anvllstar.com or contact your local AnvilStar representative FIG. 359 Reducing Tee A Star" Are Products OMolon of Anvil* International /ANVIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet ® C - D-4-E A-J.- 13 I iiillq: . APPROVED --f-' J • F For Listing / Approval details contact your ‘----- '- , , AnvilStarTM Representative. FIGURE 359 REDUCING TEE (cow.) Weia t Size mina D E F block poly. Size A flfl D ©f Weig t black !ale. N' INN' IN NPS I 0},911,7 ® PM11 In. mm M. mm In. mm lbs. lbs. NPS DN NPS 1 N N' DN In. mm ®® ® ® ® ®I 1L 1 lbs. 1 2 1/16 'lug � 2/6 1/e 2/4 3.7 - 1 1 Hid 1 h d� s 6 2A6 4.5 - iiii 40 5c 2 40 ® 57 54 57 1.. zs zs - 2h 1/11611111 I � 2'/16 2/16 2/16 5.5 - 1/4 46 i RI i � 2/16 4.8 - • from) 6 65 65 62 2.5 21h 21 32 22 ® 52 7.2 - h 1 lh Ih 1/ 22.1 2.8 65 65 1h 16 246 5.1 - I5 37 7 38 38 48 1 . 2 1 . 3 1111111111111 40 24 ® 62 2.3 - /4 Nun 1'/16 1'46 1 16 2.9 - (Cool.) (Cod 1 1/16 1'/16 2116 2/16 5.9 6 2 2 40 40 49 1.3 50 40 40 62 02 2.7 2.7 50 77 1 1111111111 1111111111 1/4 1/4 2 3 3.1 4 2/4 M 2/16 'sass 'sass 14 ®m 44 44 51 1.4 1.4 100 70 62 6.4 - (1910 2 1/4 . . 1716 1N 14 2/16 3.4 - - 1 1/2 3 2/e 2/4 Ill III 2 46 m 7.6 - 50 32 31 48 48 52 1.5 - 15 80 54 57 68 ® 3,4 - 1 40 11111E1 51 2 2 2 3.6 3.7 X 20 80 5 1111111111 2 8.3 2h 65 1 sim� 2'/16 216 2/16 5.2 5.4 1 3 2/s 54 m ® m 2 16 68 8.8 3.9 - 65 65 6 2 2.3 2.4 25 80 ® - 4 �® 2 /16 3 116 3 As 3h 16 - 7/4 3 24 ��� 2 46 M 8.5 - 100 62 94 94 89 1,3 32 80 54 73 3.8 -1h 2 ��� 2/16 24 2'/ 5.3 _ 1 h 2h l b Nil 2'116 M 7.7 - h 50 62 54 65 40 65 48 65 3.5 - 15 2h 111111/11/1 2 h6 2/4 2 A6 5.2 _ 71/2 3 24 �ii��� 8 .7 65 68 57 68 2.4 40 80 54 - /4 2h 1 /16 lila 2 16 2/4 2 /16 5.1 - I I4 vi �� 2/16 2 46 6.8 - 20 65 47 68 51 68 2.3 40 35 56 73 3.1 - 2 246 2A 2/16 5 - 2 1'/16 1'16 2/16 2/4 7.3 - 1 5D Him 246 54 65 2.3 - 2 SO 40 40 56 M . 57 3.3 - 25 24 1/1111161 2 46 246 2 46 5.4 - 50 2h 1/8 1 46 m 2'/16 en 7.1 - 65 68 59 68 2d 65 48 49 ® 65 3.2 - 1440 HH 246 1 16 2/16 4.3 _ 3 2/e 246 m 8.8 - 56 49 62 1.9 80 54 56 ® 4 - 1 11/4 2 HHH 2A6 24 2'46 5 - 1 1 1ll I��� 5.5 - 2 32 sn 62 54 bs 2.2 2s 25 5 5 - 65 265 h 1/1111111 2 46 2/b 2 46 5.4 - 1/4 1/4 ■11111111111 246 2/4 5.9 - 68 60 68 2.4 3 32 32 ® ® 52 70 2.7 1 40 0 . 246 1 1 6 246 4.2 " _ 80 1/2 1/e Ms 246 MI 2/16 2 46 6.2 6.3 56 4 9 62 1 . 9 2 40 35 ® 56 56 73 2.8 2.9 11/2 40 2 l h 2 2 24 2'16 4.8 - 65 2 1'16 m m �� 2A6 6.8 40 50 I 38 62 54 65 2.2 40 3.1 2h 1 /16 1 16 2 /16 246 2 46 5.8 - 2h 14 �ii� , 3 65 47 47 68 62 68 2.6 6 5 4 - .6 - S Iola 44 1 43 6 38 ? 56 /16 3 .6 - 90 54 ����� 4.1 - - sD ?0 � � 1 44 4 4 1 40 6 57 3 .6 - s _. 46��� 8 . 4 6 . 3 2 � ®H 1 u 6 1/4 216 3.9 _ 20 /4 ? 6 ��� 6 . 1 6 . 2 5 4. 4a 59 l.8 d 2.7 2.8 13/42 /4 11111111 2A6 14 2 ; 4.3 2/1 _ 52 48 1 25 25 1 ® m 216 57 2.8 6.3 6.5 3 lh 1E1 1E1 246 2 2 60 1.9 716 4A - 1/4 1/4 1/4 m ��� 6.8 - 2 40 56 51 62 2 - 3 / 4 32 32 ® 3.1 - 2 h 50 S 0 ' 216 2/4 2' 2 .3 - 80 1 it 2A6 1 216 3.2 7.3 II 62 51 6s 5 2.3 35 40 35 56 59 . 65 2h 65 # I � 2 /16 246 2 116 6 - 2 1'16 1'46 246 IIIIH 7.8 7.8 69 65 68 2.7 - 50 40 40 56 3.5 3.6 h H 1 16 1 46 246 4 - 2h 14 8.9 9 2 15 43 43 56 1.8 - 0 49 ���� 4 4.1 • 65 70 !l 1 44 1 2 �4 4.3 - 90 6 V��� 11 - PAGE 3 OF 5 Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, REV. 03.03.06-008 go to www.anvilstar.com or contact your local AnvilStar representative FIG. . 3 5 9 Reducing Tee AStar Fire Products Division of MNr International (‘.w),Alslyji Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet a C D-- 4 -E--1 F . ` I APPROVED c For Listing / Approval i _ details contact your AnvilStarTg Representative. FIGURE 359 REDUCING TEE (cow.) Size unto D ©0 Wei, t Size ling" 0 ©M Wei t .1, ,a1 black ,alv. NPS I N NPS 'N UPS I ETEMIETEMMETETIC GMOYtdTul lbs ! lbs. ! NPS ON NPS D NPS I In. mm ®�MUNTIM 'uCi1 ®/uTul lbs. ! bs. 8 0 8 0 100 1 68 6 Ells 3 94 6 5.8 - 50 1 4 36 1 48 70 2 68 6 2 6 . 5 89 5. 6 1 1 5 Ma 3M En 436 4/16 3/i 20 - 2 1 1 2 2 2 3 12 - (Eonl? (Ionl.) 125 4 110 110 95 9 - 2 65 48 48 67 15 73 90 5.3 - 1/4 3 111HH 336 HH 13 _ 50 3 2/4 2A6 2 36 HHH 13 - 32 80 81 5.7 80 57 6. 68 6.1 - 2 3h 0 90 �� 2M tI 59 - 00 2 0 HHHH $ 5 4 1 - 65 M 1 49 6 HH 1 7 3 6 1 4.8 - 65 1/8 48 111111111/11 3 5 - 2 80 11111E1111111/1 3 4 6 5 - 2% 30 57 4 H 8J 4 laid 59 - 65 3h 236 I 336 En 3M 13 - 65 4 2/4 2/4 iiii 3/4 16 - 90 62 87 8/ 5.7 100 70 70 95 71 - 4 100 •, 1411E1 3 94 6.9 - 175 86 89 1 1 3 6 �� 102 22 0 - 3 1 H 236 H 236 8. _ 32 1/4 46 46 H�HH 9.7 4 I - I 0 0 (1 59 2 236 to 236 . 1 - • 1h 136 136 2 /16 236 24 336 10 - 50 62 65 3.9 - 40 37 37 68 62 60 4 4.6 - 2 65 5 ® �� 10 - 2 1 1 2 2 2 3 10 11 3 5 4.5 - 0 43 40 70 68 65 89 4.6 4.8 111111111161111111 6 BO 5, 5 1 - 80 65 1% 46 17/a 48 67 2 2 3 36 39A6 51 - 3h 2/16 KM 2/16 1111111111 14 _ 3 2/4 2/e 2 /16 11113161 13 - 90 62 I 67 6.3 BO 57 54 68 5.7 - 00 ���� 3 9 1 6 0 9 - 100 7 0 2 68 6 7 0 HUH 69 - 5 � 4 10 4 110 N 20 - 4 1/2 40 1/16 1 35 1 6 86 � I 4.6 - - ; inIIHHH 2 36 8 _ 100 2 36 1 /e 2 /4 EiHH 11 - I IS 3.6 50 17 41 70 a o _ 13 1 /4 1/i 6 8.6 - 3 2 1 36 24 3 23 3'36 12 - 32 32 32 I 3.9 - 65 65 51 49 6/ 76 7 3 90 5 4 - 1 h 2 36 8.9 - 3 3 2 2 2 3 3 3 15 - 40 �WN ri2 4 - 90 80 57 56 68 83 83 6.6 - 3 2 2 A6 9.9 - 3 2 2 11 ./td 2 3 3 3 14 - 90 31h 50 1 . 62 1/1111111 1/1111111 4.5 - 90 64 62 68 89 87 94 6.5 - (OA) 90 2 E i1, ���� 1 = 100 70 2 68 6 7 HUH 7,8 - 3 Ms 80 2 56 6 HHWH 5 4 - 115 86 3 84 6 2 73 6 Hu® 2 9 - 4 � 3, ii 14 = 4 1/4 1/4 mug 2A6 is 11 - 100 9 v 6.5 20 32 3? 59 4.8 - 5 5 H H� 410 4 10 WM 8 0 - 4 1 5 / ? 6 1/1111111111 4 0 7 4.9 20 100 Elm 2 0 4 3A 9 1 - 100 3 2 4 4d /4 25 6 WM 10 . 4.8 1 4 14 - lh 136 1 A 2 36 236 236 336 11 11 4 25 100 �� ' II , 14 1 - 40 37 37 68 62 62 84 .4.9 5.1 100 1/4 4 3/4 14 - 2 I% 1% 2 2 2 3 12 12 32 100 ����� 95 6.5 - 50 43 43 70 68 66 89 5.3 5.3 111/11111111111111 6 3 - 40 100 11 - 6 5 51 51 67 2 75 6 2756 3906 5.8 5.9 4 3 2/4 2/4 2 36 3/4 3/4 34 14 15 100 80 57 57 68 83 83 92 6.4 6 7 5 ' 3 3 2 4% 4 4 21 - 125 86 86 73 III III 102 9 - 6 34 3h 23 4 h6 4 6 436 26 - ISO 98 98 73 125 125 103 12 - PAGE 4 OF 5 Anvil Cast & Malleable Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule, REV. 03.03.06-009 go to www.anvllstar.com or contact your local AnvilStar representative V FIG. 359 Reducing Tee /� i .S Flre ®AniviL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet C D-4-E1 VI. . . 4::› __ __74-B1 T 1 . APPROVED C F For Listing / Approvals r. details contact your AnvilStars" Representative. FIGURE 359 REDUCING TEE (CONT.) Size illiEl 0 ©II 61ocWeig tee Size A n f D E F black gale. NPS IN NPS DN NPS D ronrcErngonrromonumfin 16x. , 16s. i NPS IN NPS i N' D In. mm ® ®In. mm In. mm In. mm In. mm lbs. , lbs. , 50 125 El El Ill El 108 44 2 0 2 4 700 24 3 2 75 6 9 8 4 10.3 102 4 30 - 114 2 5 EI N 44 4 /+ Ea 22 - 100 6 3 3 3 5 4 5 34 - 65 15 H1 ® 114 108 10 - 150 96 98 98 ISO 125 130 16 - � 2 - 1 14 14 398 23/4 23/4 114 22 - 8U 100 ��11® mil 6 150 4/103 16 p 1527 ® 31 - 3h 24 2' /16 3 /16 3/a 3A 44 30 - 14 - 5 90 67 65 97 98 95 124 14 - 3 80 MIN B3 11 ' 4/4 08 23 - 125 5 0 98 3 1 0 6 3/8 E 5 0 5/8 30 5 0 43 0 - 90 4 MIN 4 HIM 23 - 8 54 5/16 4/16 64 6 5'A6 66 - 100 102 lU 2 00 130 132 106 162 167 141 30 - 6 3 A6 4 Higgs 4/e 29 - 6 1/4 1/a H 3 /16 24 2/e 4 /16 22 - 150 97 102 117 13 150 '32 35 97 67 67 113 10 - 21 ® 3/16 4/4 22 - 2 1 6 MO 34 3 3 44 25 - 65 HI� 81 108 10 50 46 98 76 76 117 11 - Bo 111111111111131 4 10 / 8 24 - 65 51 ® 3 97 6 8 3 83 4 1 71 26 27 12 12 5 4 4� 2/4 � 4 3/4 MI 21 - 6 3 2. H 3 As 3A6 3'716 4 6 27 29 i25 10 100 70 102 95 9 150 30 60 m 97 90 90 122 12 13 4 /6 125 �11���� 2 1 6 2 - 100 7 ® 9 4 03 4/16 0 4 t6 32 34 150 laH®® 44 35 - 125 36 16 3 9 76 1 77 44 1 2 7 37 1h 2 /16 16 - 8 54 54 4 /16 64 6 5'A6 58 - 40 11611E111111 2 ® 1 2 0 130 130 106 162 162 141 26 - So 2 HHW 2 ? /1 5 6 El 7.9 - 17 2 8 5 5 5 6 6 6 64 - - 50 200 132 149 132 167 167 167 29 - 2 h 2/16 111161111611 4/4 19 - 4 8 5 51/2 5 6 6 6 61 - 65 52 108 8.5 - 100 200 132 140 132 167 167 167 30 - 5 125 3 la 2/16 HHH 4/4 20 - 5 5 4/16 Ea 5/16 5'/16 5'/16 64 78 - so s9 108 9.1 125 125 106 132 141 141 162 35 - 4 1151111111111/11111 24 - 5 4 A6 4/16 5 /16 5'A6 5'/16 6/a 77 - lU0 11 - 125 106 110 132 141 141 162 35 - El 150 3 /1 6 ® 57 35 - 150 150 4/16 06 41 1 0 54 30 1 41 5 41 1 33 - 8 5A6 5 /16 4A6 m 5'/16 68 - 8 5A6 54 5 6 6'A6 6'A6 6'A6 92 - 200 132 132 106 141 31 - 200 132 130 132 167 167 167 42 - 1 h 6 � 4A6 Ea 54 4 As M 35 - 8 2 2 2 5 3 3 5 44 - 40 150 103 130 119 16 - 200 50 52 52 130 87 87 149 20 - 2 6 m 4 � 54 4 A6 54 35 - 2' 2 /16 2 5 3 3 6 45 - 50 150 ® 102 130 119 130 16 - 65 59 59 129 94 94 152 21 - 2 h 6 11 �� 4 19 5 35 - 3 3 19 (3 1 1 4 65 - 6 65 150 ® f19 130 0 16 - 80 79 79 130 114 114 f56 56 25 150 3 4 NNE 4A6 4 4 A6 32 - 8 3 3 3 5 41/2 4 6 54 - 80 100 103 102 125 15 - 200 90 79 79 130 114 Ila 156 25 - 3h 6 HHH 54 4 /16 54 35 - 4 3 3 5 4 4 6 54 - 90 150 130 125 730 16 - 100 79 79 130 n4 n4 156 24 - 7 4 00 3 ���� 3'A6 32 _ 5 4A6 H 5 6 5' 5'A6 64 68 - 1no Bo 90 Ia 125 106 132 141 41 141 162 31 - 6 4A6 4A6 54 5'A6 5 64 66 - 150 106 106 130 141 141 162 30 - PAGE 5 OF 5 Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe w m schedule REV. 03.03.060010 go to ww.anvllstar.co or contact your local AnvilStar representative