Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 1 • 1 �1 March 6, 2007 • TIGARD Rohr Jet .Fire Protection 1935 Silverton Rd. NE Salem, Or. RE: FIRE SPRINKLER SYSTEM Project Information Building Permit BUP2007 -00061 Construction Type: NA Tenant Name: Goodwill Occupancy Type: M Address: 13920 SW Pac. Hwy. Occupant Load: NA Area NA Stories: 1 Hazard: Ord Haz 2 • Commodity: Mixed The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; National Fire Protection Association, Standard 13 (NFPA 13)2002 edition and the State of Oregon Fire Code (OFC) 2004 edition. The submitted plans are approved subject to the following. FLUSHING The fire service mains shall be completely flushed before connection is made to the sprinkler piping. The flow rate shall not be less than the hydraulically calculated water demand of the system including any hose requirements. Section 10.10.2.1 NFPA 13. HYDROSTATIC TESTING All piping and attached appurtenances shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for 2 hours. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. Section10.10.2.2:1 & Section 10.10.2.2.3 NFPA 13. GENERAL 1. A key box shall be installed in a location approved by the Fire Chief. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Section 506.1 OFC. Please contact Tualatin Valley Fire & Rescue for key box information at 503 - 612 -7010 2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so t•4 that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2 NFPA 13. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772 • c1 3. The spare sprinklers shall be kept in a cabinet located where temperatures will not exceed 100 degrees "F" at any time. A special sprinkler wrench shall be provided and kept in the sprinkler cabinet to be used in the removal and installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13. 4. The clearance between the deflector and the top of storage shall be 18 inches or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13 5. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13. 6. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the penetrating pipe for pipe sizes 1 inch through 3 '/2 inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. 7. All valves controlling the water supply for, automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored when the system serves more than 20 heads. Section 903.4 OFC • 8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water -flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OFC 9. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a, copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of • Tigard in tracking and 'processing the documents. Respectfully, r 1 i D an Nelson, Senior Plans Examiner r ` Page 1 of 2 • ,m. Randall Rieks - RE: Goodwill - New Building (Tigard - Site Development ReviewSRR2006- 00002) From: "Dalby, John K." To: "Randall Rieks" Date: Monday, November 27, 2006 2:03 PM Subject: RE: Goodwill - New Building (Tigard - Site Development ReviewSRR2006- 00002) The final version of the site plan (including fire hydrant locations) has been accepted by the fire district. If there have been any recent changes in the plan, a PDF copy must be submitted for approval by this office. The Tigard Building Department will be reviewing all building plans including the automatic sprinkler system. The fire district has no authority to approve or deny the construction of the building or the installation of any fire protection systems. You can obtain the application for the required KNOX box by calling 503 - 356 -4700. The Building Survey form is building information we require for our computer database. It can be downloaded from our web site at www.tvfr.com. Click on "Departments" and scroll down to and click on "Fire Prevention." When that downloads, click on "New Construction" and then click on "Forms and Brochures." The menu from which you obtain the survey form also contains instructions to help you. Hope this helps. John K. Dalby, Deputy Fire Marshal II Tualatin Valley Fire & Rescue, North Division 14480 SW Jenkins Road Beaverton, OR 97005 -1152 503 - 356 -4723 From: Randall Rieks [mailto:Randall @da- arch.com] Sent: Monday, November 27, 2006 10:46 AM To: Dalby, John K. Subject: Goodwill - New Building (Tigard - Site Development ReviewSRR2006- 00002) John, I wanted to touch base with you via email, since last week (Left you a voicemail) regarding our Goodwill Industries new Retail /Donation Center in Tigard, OR. (13900 SW Pacific Highway). We received the city's SDR notice of decision report and we are also wanting to submit for bldg. permit very soon, and I have a couple of questions for you. SDR2006- 00002: In the report, the city states that prior to issuance of Site Permits a condition of the following must be met: 'The applicant shall provide final written approval from TVFR for the proposed site plan, fire hydrant configuration and fire suppression system." file: / /C:\Documents and Settings\Administrator\Local Settings \Temp\XPgrpwise \456AF01... 2/14/2007 Page 2 of 2 • Do I need to submit to you our final site utility plan that indicates the location of the fire hydrants (w/ reflective hydrant marker note) to you in order to receive the final written approval? I believe our civil engineer (Ray Engel - Westech Engineering) provided the fire flow worksheet to you back in June of this year, in order to get a prelim. approval of the fire hydrant location so we could initially submit our application into the city. Also the fire sprinkler system for inside the building will be a bidder design system. This design /work has not been awarded to a Oregon Fire Sprinkler contractor yet. We plan on noting on our cover sheet that this will be a Deferred submittal in accordance with IBC Section 106.3.4.2 (FDC, VAULT AND FIRE LINE TO BLDG. is indicated on our engineers site utility plan - Sized per fire flow worksheet) Who do I need to contact to get the order form for the Building Knox Box? BUILDING PERMIT SUBMITTAL: Per the City of Tigard Building Division Plan Submittal requirement sheet, they list that a extra set of the Fire Department Building Survey be provided. What is this survey? Is it a form, I need to fill- out? If so, how do I get a copy? We will be submitting as part of the bldg. permit documents a Fire, Life & Safety floor plan as well as a Fire, Life & Safety Site plan (On the site development plan). Thank you for taking the time to answer my questions. Sincerely, Randall Rieks Project Manager DEFFENBAUGH & ASSOCIATES P.C. 388 State Street, Suite 840 Salem, Oregon 97301 Ph: 503.585.0222 Fax: 503.585.3131 For more information about Deffenbaugh & Associates, visit our website at www.da- arch.com This electronic message transmission, including any attachments, and CADD drawings, contains information from Deffenbaugh & Associates, P. C. The information is intended to be for the use of the individual or entity named above. Due to the potential that the information set forth may be modified by other parties, unintentionally or otherwise, Deffenbaugh & Associates, P.C. Architecture reserves the right to remove all indication of ownership and /or involvement from each electronic display. Any use or reuse by others, without written verification by Deffenbaugh & Associates, P.C. Architecture for the specific purpose intended, will be at the user's sole risk, and without any liability or legal exposure of Deffenbaugh & Associates, P.C. Architecture. The user shall, to the fullest extent permitted by law, indemnify and hold harmless Deffenbaugh & Associates, P.C. Architecture from all claims, damages, losses, and expenses, including attorney's fees arising out of or resulting therefrom. Reproduction of any architectural renderings, models, site plans, floor plans, etc. prepared by Deffenbaugh & Associates, P.C. Architecture is prohibited without the inclusion of Deffenbaugh & Associates, P.C. Architecture as an acknowledgment. file: / /C: \Documents and Settings\Administrator\Local Settings \Temp\XPgrpwise \456AF01... 2/14/2007 2S 1 03DD 2S 1 03DD • .. ., ....-; - 1 '' - '''''''''''''' - • f.:–:. ..), –1 L-7-..4-1 • .. - - Isri • - -• ir.......• , ... .t.. ' ' .- i' • ''', #-• Ira/ i j • .-.. 1 : • . - ' - - . 4"---- ! • .. ' - ' aLe - . ,.. l ei /°7' ,11 : ' -' - .o.c : -T - :, •ii jwi:', • �iy;;.'. r� m• .. t i / ''i.i.-.: • ' morr ,�+.y,��r�� sc�t . - !'if� .'uei!, �HNr. ; i r' • . J e l � 6I we I' t e l I / . � � 1 1 0� I 1 Z t 1 I ali il '_' i r.::g� . . SW -1_� a+--_: — -1 -- 1 d 1 �J 4 _ _ ' i FA► � a. "'• I i �.� +- : i � . - -aq , -" - ► „ r- ..---Y As.... e STREET i / WASHINGTON COUNTY OREGON �� l .m 1 —� IRHAVEN ° ! ° r 4.k. r ° r . D :. � ) '0 ° •' I - l� nr•. ,� , ti _YI I ' I Z. I j ,� '.f a 11M U114SECTIONO3 T2S MWW.N. ,..✓ , it , .� e , `i it ik 7 p lk m > .w Z eatltt . ., a ). •-' C .° • o; .n \ G i It , e . ` ue tlt� �t N� .,,r _ . / / f Td.� :7JLof: >3 1oi6:• e _-� I tl� 1� — ems , li I. i ' 1 i ? ce • ��•��. T ' 5 ___ j„, ' III' - % : "l. '_ ° / c . . .: � � 3 . 4;. � / ' , - .16 �' 9 I n II .0 °I . 0 7 5� - .,� � . f � a ::**M...:::::::::,4 IA y ti ' Y ` Y u 1 w a , j _ A �t��. y �7 / � 'uie4. Q W q u / " 1,,. � : •�.E!_7�N.•.�!e���•7�1ti � T. -4' - t .'1� r e (J I / A • \ 41 " - . c Z -f i f � rI• �'! EIC "�I /' ` /. I �:y ice. +. � M � ,. ��� .1:1 �1� rev — �_ L' t{p �— . _j+ee, 1 • �� / � aJe `° i SW FA ►P 1 i .. k. r,---T-----. \ , , m a I a" e 55 w I .m t et �' �Of Jf6:i /✓�.OiY/ �'' ,1645....., ! u n c it k e e y, FOR ADOTON I ISITEAT •e 7d \ a f +oo k • se VISIT i.'S.� q r • . 1 r . - .. • . . 3 ■ 4 r — °u... �ww.00.WMpeDS�Wm yyo .' . . 003 eteo 7 !1 '. •� 1f0f e 100 ` `. � _�,� / •- o: . • s ypp ..m j smp e, � .. P e ..» sr ' '1 70 - j am t ! jr . , ' \;,, � , .- Pena 11 ^ �' 6 a i1 f 9 I e \<i �,.. :'eo - '.Ab?I !i 2 . 774115M1* e .. deep I `' 4....1 „„e „„ .oD , - , , dope woo emo Ire u l +s In II m n n.. • =',. .-:::,13....:',:',.4;,',C.4.-..:...-,,-..igt 188D D43 9 p � 9� � es � , : ' : ' . ;4 . w__ °= ! • K ^. ' �"i. ` y � I .w•. 'I r 7 q e y , / / G , - .j C�weee TY,Cae Fiw: i8101DO — P f uaM1lee7JOfaR ,O,.1te,., ee1.000.Mm. e we ua o seep " - a . { ., » ego .. % Oeee 0 e �I l �' t `-' v ej„ a i �' . h SW m GARDEN � w � v' } i / / , :. ''.� G '° p 711,0 ,, e, : • --- ' ..•1t_TS-'• ' " i 1 n00 1I. '''r f 9 A ' r s 1 �4" y / / A P �r ' "''-f° •i 1 a • ,}1 .. „ .••• _ , � e 1 1 i a , :uo l ! I //// --. � 1 e + r,CAR[C)GRi4PhYYs; .. • z , , eoo Al ,' 996• e -: I PP T a x a t i o n • U4. • uoo • 1 - • . I repo e.eo�e 27.. 9 / err ' " w , I L ` "4 +• -- .,. —_ I I / , �,, ROT DATE: June 23, 2005 _sT — y �,,,,,,,,,,,,,,,,,, „ .� ' °� -r } -�` ';' ' _.mss•_ � FO�ASSE SM€ PUgPQ$ES fCR368I— i ... �I M _ rearms .... G ,.,w .r ML E G „--�,. –INN-- >-- —3W–M AtFYR6A@ ICR # . i a, „„...– _ �e..... e..e,.ow.. ........ . � .Tr j u.r COMIPm.roem r a nr�.e.amre.• 0 lib =waxed Ibribt F. te r. V•` /// /r r' Gw4 . , k• 1 114240 • 0 2S 1 03DD 2S 1 0 . i 2 Fire Marshal's Division Offices North - 14480 SW Jenkins Rd., Beaverton, OR 97005, (503) 356 -4700 South - 7401 SW Wash Ct., Tualatin, OR 97062, (503) 612 -7010 . ' Fire Flow and ,Hydrant" Worksheet - ., I This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction (AHJ) before any permits for new building construction, building expansion or fire hydrants will be issued by any building department within the TVF &R District. See the instructions for assistance completing this form or call one of the above numbers. Preparer Information Preparer Name: (Raymond C. Engel, P.E. I Phone: 1 503 - 585 -2474 I Fax: 1 503 - 585 -3986 I Architect / Engineer of Record: [Westech Engineering I Phone: 1503- 585 -2474 I Fax: 1 503 - 585 -3986 I General Building Information I '' lect Name: 'Goodwill Tigard I Project Address: 113880 SW Pacific Highway I City:ITigard I County: JWashington I Zip:197223 I Construction Type(s): I Type V -B I 0 Total Bldg Area: I 21,6531 sgft 0 0 Total Fire Area: I 21,653Isgft 0 Bldg Fire Flow: I O I Gallons Per Minute (Light Hazard) Describe Fire Area: (If more than one fire area, Include an 81/2 x 11 or 11 x 17 drawing Indlcatin the various fire areas) Retail area, product processing and office space. Goods are either sorted from on -site donations or from truck deliveries. Goods that are delivered are brought to the site in 4' sq. cardboard boxes stacked 2 high. Type of Occupancy or Use of Building: M, F -1 • P i A. ` Occupancy Hazard I Al Determine percent of each occupancy hazard in the fire area. Occupancy Hazard Class ire Area Total Fire Area ent of Fire Area Light Hazard 2003 SF / 21,653 SF x 100 - 9.25 % Ordinary Hazard Grp 1 7280 SF / 21,653 SF x 100 - 33.62 % . Ordinary Hazard Grp 2 12370 SF / 21,653 SF x 100 - 57.13 % Extra Hazard Grp 1 0 SF / 1 SF x 100 - 0 % Extra Hazard Grp 2 0 SF / 1 SF x 100 0 % Total Must equal 100% I 100 % I A2 Calculate Fire Flow Occupancy Hazard Class Factor Fire Area Fire Flow _ Bldg Fire Flow Light Hazard 1.0 x 9.25 % x 0 GPM - 0 GPM Ordinary Hazard Grp 1 1.2 x 33.62 % x_ 0 GPM - 0 GPM Ordinary Hazard Grp 2 1.3 x 57.13 % x 0 GPM - 0 GPM Extra Hazard Grp 1 1.4 x 0% x 0 GPM 0 GPM Extra Hazard Grp 2 1.5 x 0 % x 0 GPM - 0 GPM A3 Required Fire Flow I 0 GPM I • I B. Minimum Number of Fire Hydrants Required I Required Fire Flow 0 I 0 I No. of Hydrants Required l C. Reduction of Fire Flow - Reductions are based on the following: I Cl - Reduced by 25% for all Group R Occupancies without fire sprinklers (multiply by .75) C2 - Reduced by 25% for a NFPA 72 Fire Alarm System (multiply by .75) C3 - Reduced by 75% for NFPA 13 Automatic Sprinklers (multiply by .25) ID. Required Fire Flow I D1 - Group R occupancy I No Ix I 1 I L 0 GPM (Max. 3000 - Min. 1500 gpm) I D2 - Fire Flow 0 GPM x I 0.25 I L 1500 GPM (Max 3000 - Min. 1500 gpm) I E. Available Fire Flow to the Building I Test Results: ( 2918.60 I GPM Manually enter available fire flow here. Please attach documentation of the flow test that was made. It shall include date, time, location of static /residual and flow hydrants, and the tester's name, phone number and address. • _ _ _ _ _ • . Project: Test Date: Static Hydrant: Design GPM: Flow Hydrant: Design PSI: Ps Test Static Pressure Reading Available Pressure at Design GPM: 52.0 Pr Test Residual Pressure Reading PSI Headroom : 52.00 100% GPMr 671 Test Flow at Residual Pressure GPM Headroom : 3906 ERR Hyd. Coef.: Rot PSI: Outlet Diem. IN: JL Hyd. Flow: ‘1. Flaw Test 3 mammy Curve Q ea 50 - — 40 1—•— PSI Fa " I 30 20 • a 0 • 0 500 1000 1500 2000 2503 3000 3500 Howl:WPM • GOOdWE @ 59 Meted 030,2003 - FL OW AT SPECIFIED PRESSURE CALCLJE4 TION STATIC= 52 PSI 32.0 Ps -P=A RESIDUAL= 50 PSI 2.0 . Ps -Pr=B FLOW= 671 GPM 16.0 _ A/B =C PRESSURE= 20 PS1 4,5 - C^. 54=D AVAILABLE FLOW= 299880 GPM =FL OW D: • • • 4-g) 6 14 Pa - Do() Col i f ? Fire Marshal's Division Offices •Fe North - 14480 SW Jenkins Rd., Beaverton, OR 97005, (503) 0 2 /)/2^ South - 7401 SW Wash Ct., Tualatin, OR 97062, (503) 612 -70 : _ ) Fire Flow and Hydrant Worksheet This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction (AHJ) before any permits for new building construction, building expansion or fire hydrants will be issued by any building department within the TVF &R District. See the instructions for assistance completing this form or call one of the above numbers. Preparer Information Preparer Name: I Raymond C. Engel, P.E. Phone: 1503 585 - 2474 I Fax:1 503 - 585 -3986 Architect / Engineer of Record: IWestech Engineering Phone: 1503- 585 -2474 I Fax:1503- 585 -3986 I General Building Information iect Name: 'Goodwill Tigard I Project Address: 113880 SW Pacific Highway I City: 'Tigard I County: I Washington I Zip: 1 97223 I Construction Type(s): 'Type V -B 0 Total Bldg Area: I 21,653) sqft 0 0 Total Fire Area: ( 21,6531 sqft 0 Bldg Fire Flow: I 0I Gallons Per Minute (Light Hazard) Describe Fire Area: (M more than one fire area, include an 81/2 x 11 or 11 x 17 drawing Indicating the various fire areas) Retail area, product processing and office space. Goods are either sorted from on -site donations or from truck deliveries. Goods that are delivered are brought to the site in 4' sq. cardboard boxes stacked 2 high. Type of Occupancy or Use of Building: M, F -1 • 1A. Occupancy I Al Determine percent of each occupancy hazard in the fire area. Occupancy Hazard Class Fire Area I Total Fire Area ent of Fire Area Light Hazard 2003 SF / 21,653 SF x 100 - 9.25 Ordinary Hazard Grp 1 7280 SF / 21,653 SF x 100 - 33.62 % Ordinary Hazard Grp 2 12370 SF / 21,653 SF x 100 - 57.13 % Extra Hazard Grp 1 0 SF / 1 SF x 100 - 0 % Extra Hazard Grp 2 0 SF / 1 SF x 100 - 0 % Total Must equal 100% I 100 % I A2 Calculate Fire Flow Occupancy Hazard Class Factor Fire Area Fire Flow Bldg Fire Flow Light Hazard 1.0 x 9.25 % x 0 GPM - 0 GPM Ordinary Hazard Grp 1 1.2 x 33.62 % x 0 GPM - 0 GPM Ordinary Hazard Grp 2 1.3 x 57.13 % x 0 GPM - 0 GPM Extra Hazard Grp 1 1.4 x 0 % x 0 GPM - 0 GPM Extra Hazard Grp 2 1.5 x 0 % x 0 GPM - 0 GPM A3 Required Fire Flow I 0 GPM I I B. Minimum Number of Fire Hydrants Required I Required Fire Flow 0 I 0 I No. of Hydrants Required I L Reduction of Fire Flow - Reductions are based on the following: I Cl - Reduced by 25% for all Group R Occupancies without fire sprinklers (multiply by .75) C2 - Reduced by 25% for a NFPA 72 Fire Alarm System (multiply by .75) C3 - Reduced by 75% for NFPA 13 Automatic Sprinklers (multiply by .25) I D. Required Fire Flow D1 - Group R occupancy I No I x I 1 I ( 0 GPM (Max. 3000 - Min. 1500 gpm) I D2 - Fire Flow 0 GPM x I 0.25 I I 1500 GPM (Max. 3000 - Min. 1500 gpm) I I E. Available Fire Flow to the Building I Test Results: ( I GPM Manually enter available fire flow here. Please attach documentation of the flow test that was made. It shall include date, time, location of static /residual and flow hydrants, and the tester's name, phone number and address. Project: Goodwill Ind. Test Date: 06/27 Static Hydrant: McDonald & Hwy 99 Design GPM: 0 Flow Hydrant: McDonald & Hwy 99 Design PSI: 0.0 Ps 52.0 Test Static Pressure Reading Available Pressure at Design GPM: 52.0 Pr 50.0 Test Residual Pressure Reading PSI Headroom : 52.00 100% GPMr 671 Test Flow at Residual Pressure GPM Headroom : 3906 ERR Hyd. Coaf.: 0.90 Pitot PSI: 16.0 Outlet Diam. IN: 2.5 Hyd. Flow: Flow Test Summary Curve Q&7.86 - s0 —. _.--.- II 50 `...4` —; . re—Ps1 n i - • Design Patrd 5 10 , 0 500 1000 1500 2000 25700 3000 3500 Flowt2PM GoodWwII @ 50 Printed 6/3012005 FLOW AT SPECIFIED PRESSURE CALCULATION STATIC= 52 PSI 32.0 Ps-P=A RESIDUAL= 50 PSI 2.0 Ps-Pr=B FLOW= 671 GPM 16 A/B=C PRESSURE= 20 PSI 4.5 CA.54=D AVAILABLE FLOW= 2998.80 GPM =FLOWD • C ; 'Plz rto � LE S — Dc t=F= - roJ 91( cutA-f f Arc L_, 4 ..T,r_-s its — E;1 • is S CRD (4k a 4' F 12E emAtesfoce_ tUEEZ4DerkiLS O ?P.(Wg:- 00 Fi suA 5 civ r` To •R■ Sg- ._. R � � ��rr �r� (F-- I 1.1 E.� To S � � EX l7 Tj+1gU _ocEss rkr. MA f�K E.b 6)06+ wetEee - its Demo 1 A (.0 DA - �'�ss Cc-k1SrRUC.rtj Ft mv _t_ . 30AA(3aras 1(g "Zt Sw '1-(2.4&t1Q6-- CL EVIS 611 Ai- 4i sr MP FAcTO 2€ 6P FC? ect) e-c- 001 TS Pt-7, ( (Rca- F2Atu to. axire OAT C(0 N72-- - e\crie:42461R---71 e Mae PcP-EA . (es -4 , Z CD_E( 5( �s titcc f=o (z (a��FF 1� PZ • 1 4"R 7 E(6-H He.E, ALAP-Ai itkithiaak Ru t I q) Law Vcz-7 I �