March 7, 2003
Ann Short
5321 Windsor Terrace
West Linn, OR 97068
Re: Second Floor Storage Addition, Adult Classroom & Future Kitchen
Community of Christ Church
BUP2003 -00043
Project Information
Address: 13855 SW Pacific Hwy. Floor Area: 1,032 Sq. Ft.
Occupancy: B /S -1 Construction Type: VN
Sprinklered: No Fire Alarm: No
The City of Tigard Building Division has completed a review of the above
referenced project. This review was performed under the provisions of the State
of Oregon Structural Specialty Code (OSSC), 1998 edition and the Uniform Fire
Code (UFC) as amended by Tualatin Valley Fire & Rescue. The plans are
approved subject to the following conditions.
1. The stairway rise is shown as 8 inches and run is identified as 9 inches.
Since this is a private stairway, Exception 1 of OSSC Section 1003.3.3.3
can be utilized. However, there shall be a nosing provided of not less than
3 /4 -inch and not more than 1% inches if the riser is vertical. If the riser is
sloped, the minimum tread depth shall be 10 inches. OSSC Section
1003.3.3.3.
2. The design live load of 125 per square foot shall be posted in a
conspicuous place by the owner in the new storage area. The sign shall
be made of durable metal and shall be unlawful to remove or deface the
sign. The owner shall be responsible for keeping the actual load below the
allowable limit. OSSC Section 1607.3.5, Volume 2.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
17.
• {
•
•
,a
3. Doors shall be provided with lever type hardware that does not require
tight grasping, pinching or twisting to operate. OSSC Section 1109.9.8 and
1109.3.2.
4. Fire extinguishers shall be provided in accordance with UFC Standard 10-
1 and shall be located so the travel distance from any point to an
extinguisher does not exceed 75 feet.
5. A copy of the approved plan shall be kept on the site and made available
to the City of Tigard inspectors for inspection purposes.
6. A final inspection and certificate of occupancy is required prior to the
intended use of the addition.