Correspondence • ` b;
khy,4
April 16, 2004
CITY OF TIGARD
OREGON
Martin D. Sommers
Sommers Enterprises
PO Box 21086
Keizer, OR 97307
RE: MECHANICAL EQUIPMENT @ AUTO QUICKLUBE
Project Information
Building Permit: MEC2003 -00713 Construction Type: VN
Tenant Name: Quicklube Occupancy Type: B /S3
Address: 13545 SW Pacific Highway Occupant Load: 17
Area: 3799 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
Special Inspection: Special inspection is required for Epoxy Bolts and Structural
Welding. The special inspection agency of record shall furnish inspection reports to the
Engineer of Record, Havlin G. Kemp, the General Contractor, Sommers Enterprises. and
the City of Tigard, Building Division, attention Hap Watkins. All discrepancies shall be .
brought to the immediate attention of the general contractor for correction. The special
inspector shall submit a final signed report stating whether the work requiring special •
inspection was, to the best of the inspector's knowledge, in conformance with the approved
plans and specifications and the applicable workmanship provisions of the Oregon Structural
Specialty Code, Section 1701.3.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the appliance.
The shutoff valve shall be located in the same room and within six feet of the
appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC
3. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
•
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
- J
4. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
5. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
6. Smoke detectors shall be installed in return air systems with a design capacity greater
than 2000 cfm. Upon activation, the smoke detector shall shut down the air
distribution system. Smoke detectors shall be connected to a fire alarm system and
shall activate an audible and visible alarm at a constantly attended location. 606.2,
606.4 & 606.4.1 OMSC
7. Appliances shall be accessible for inspection, service, repair or replacement without .
removal of permanent construction. 306.1 OMSC
8. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
•
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and .. ssing the documents.
Respe ma
. Jock
Se »Plans Examiner
AI
Sommers Enterprises
Distributors of Shenandoah Waste Oil Furnaces
PO Box 21086 — Keizer, Oregon 97307
PH: 503 - 393 - 5315 Fax: 503 �+
Toll Free 1- 866 - 373 -HEAT RECEIVED
To: Brian Blalock/ City of Tigard APR a d 2004
From: Brian Pfaff/ Sommers Enterprises CITY OF TIGARD
RE: Tigard Quick Lube, Mechanical Equipment BUILDING DIVISION
Building Permit #: MEC2003 -00713
In reply to: Letter from January 2, 2004 concerning plan review. (Attached letter)
Please find enclosed all information/drawings required for you review for the issuance of the
mechanical Permits.
1. Structural calculations and details for attachment/anchorage of roof mounted AC -1
attached.
2. We have eliminated all appliances on the roof within 10 feet of roof edge, so no guard
will be necessary. Please refer to revised drawings submitted.
3. Details and calculations for the structural support of unit F -1 attached. A second
unit (F -2) has been added to revised drawings. A second structural support will be
installed for this second unit (F -2). The details and calculations apply to both structural
supports. Please refer to revised drawings submitted.
4. Detail 1/M2 has been revised and supmitted. Please refer to revised drawings submitted.
5. Equipment cut sheets are attached. ( yjf f torivsrf (ft -oz) — c rr $Nm, 713 fr -v'
6. Valuation for the project: $17,725.00
Sing= ely,
J n P ff
Sommers nterprises