Permit CITY OF TIGARD MECHANICAL PERMIT
II s COMMUNITY DEVELOPMENT Permit #: MEC2009 -00396
T I GARD 13125 SW Hall Blvd., Tigard OR 97223 503.639.4171 Date Issued: 08/11/2009
Parcel: 2S102CC00500
Jurisdiction: Tigard
Site address: 13500 SW PACIFIC HWY 90
Subdivision: Lot: 0
Project: Island Tan
Project Description: Install new 7.5 ton gas pack RTU and ductwork.
Owner: FEES
13500 PACIFIC CORP Description Date Amount
BY CAPOZZOLI ADVISORY FOR, PENSIONS Permit Fee 08/11/2009 $231.50
INC, 21500 HAGGERTY ROAD, SUITE 100 Plan Review 08/04/2009 $57.88
PHONE: 12% State Surcharge - Mechanical 08/11/2009 $27.78
Contractor:
AIR COMFORT INC
16055 SW 74TH AVENUE SUITE B
TIGARD, OR 97224
PHONE: 503 - 260 -7806
FAX:
Type of Use: COM
Class of Work: ALT Type of Const:
Occupancy Grp: Occupancy Load:
Stories:
Fuel Air Handlers
Fuel Types: Natural Gas Units < 10000 cfm:
Gas Pressue: Units > 10000 cfm:
Furnaces / Boilers & Compressors
Furnaces < 100K BTU: 0 -3 HP:
Furnaces >= 100K BTU: 3 -15 HP:
Floor Furnaces: 15 -30 HP:
Unit Heaters: 30 -50 HP:
Vents w/o Appliances: 50 or Greater HP:
Air Conditioning:
Heat Pump:
Appliances
Vent Fans: Vent Systems: Total $317.16
Hoods: Comm Incinerators:
Woodstoves: Gas Fireplaces: Required Items and Reports (Conditions)
Clothes Dryers: Other Mech Units:
Gas Outlets: Other Desc:
Duct Work:
Fire /Smoke Dampers:
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of ' •
issuance, • work is su • - ded for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon
Utility •tification Center. Tho - •- - • re set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy of the rules
or dir • ct questions to OUNC b • . Ilin • 0 •6.6699 or 1.800.332.2344.
l
Iss d By: ` `� �% "` ; i P ermittee Signature: 1 I'
/ 1 ,•'
Call 503.639.4175 by 7:00 a.m. for an inspection that business d .
This permit card shall be kept in a conspicuous place on the job site until comple 'on • pro/ • ct.
Approved plans are required on the job site at the time of each inspection.
Mechanical Permit Application RECEIVED FOR OFFICE USE oN1,Y
(
City of Tigard AUG 0 ¢ 2009 Received M � n Permit No.: (3 lJ69
•
13125 SW Hall Blvd., Tigard, OR 97223
Plan Review
Phone: 503.639.4171 Fax: 503.598.1960 'l
C CITY OF TIGAItD i Other Permit (a '2• r t : ,O6
T I G A R D Inspection Line: 503.639 Date Ready/By: ® See Page 2 for
Internet: www.tigard- or.gov BUILDING DIVISION Notified/Method: Supplemental Information
TYPE OF WORK COMMERCIAL FEE* SCHEDULE — USE CHECKLIST
❑ New construction ddition /alteration /replacement Mechanical permit fees* are based on the value of the work
performed. Indicate the value (rounded to nearest dollar) of all
❑ Demolition f 0 Other: mechanical materials, equipment, labor, Wtrad, and rofit.
CATEGORY OF CONSTRUCTION Value: $ /19 6r0
RESIDENTIAL EQUIPMENT / SYSTEMS FEES*
❑ 1- and 2- family dwelling ommercial /industrial ❑ Accessory building
For special information use checklist.
❑ Multi- family Master builder ❑ Other: Description . I Qty. I Ea. I Total
JOB SITE INFORMATION AND LOCATION Heating /cooling
Job site address: f . , 1 [�10 i
Air conditioning ho or heat pump
r ld-) I' ke C h w cot" (requires site plan showing placement) 14.00
City /State /ZIP: It l / /� b IL___ - Fumace 100,000 BTU (ducts /vents) 14.00
Ti 11 t� - Furnace 100,000+ BTU (ducts/vents) 17.90
Suite/bldg. /apt. no.: Project name: m
� %J b 74 Gas heat pump 14.00
Cross streeUdirections to job site: Duct work 10.00
Hydronic hot water system 14.00
I / 04 q 7 Residential boiler (radiator or •
hydronic) 14.00
Unit heaters (fuel -type, not electric),
in -wall, in -duct, suspended, etc. 14.00
Flue /vent for any of above 6.80
Subdivision: Lot no.:
Other: 10.00
Tax map /parcel no.: Other fuel appliances
DESCRIPTION OF WORK Water heater 10.00
Gas fireplace 10.00
) 5 1 Z f 7 • )"T'b) (' , n , jz- Flue vent for water heater or gas
N � fireplace 10.00
0 ti 777e 2 . __�'J .tom _ U ' Q{� /CL Log lighter (gas) 10.00
l `"'' V Wood/pellet stove 10.00
Wood fireplace/insert 10.00
❑ PROPERTY OWNER ❑ TENANT Chimney /liner /flue/vent 10.00
Other: 10.00
Name: Environmental exhaust and ventilation
Address: Range hood/other kitchen
equipment 10.00
City /State /ZIP: Clothes dryer exhaust 10.00
Single -duct exhaust (bathrooms,
Phone ( ) Fax: ( ) toilet compartments, utility rooms) 6.80
• ❑ APPLICANT ❑ CONTACT PERSON Attic /crawlspace fans 10.00
Other: 10.00
Business name:
11 .) ��e_.-- Fuel piping
Contact name: ^ i $5.40 for first four; $1.00 for each additional
Address: / F umace, etc.
Gas heat pump
City /State /ZIP: Wall /suspended/unit heater
Phone: ( ) Fax:: ( ) Water heater
Fireplace
E -mail: Range
CONTRACTOR Barbecue
Business name: ✓� ri �^ ��L Clothes dryer (gas)
r� ( } Other:
Address: / 4 U fr 3 _ t — 4 -K ,4 J /3 MECHANICAL PERMIT FEES*
City/State /ZIP: 77 4 29 9- IAA
Phone: ( ) Fax: ( ) Minimum permit fee ($72.50)
�3 '� p 7d-0 Plan review (25% of permit fee)
CCB lic.: g g 3 )�� State surcharge (12% of permit fee) ,l'')7. 68
Z � � TOTAL PERMIT FEE
Print name: signature: lication expires if a permit is not obtained within 180
I� a ys after it has been accepted as complete.
Print name: r . / , , - I J T— This p ermit a da pp Date: /� ?/��j • Fee methodology set by Tri -County Building Industry Service Board
1:\ Building \Permits\MEC•PermitApp.doc 01/19/07 44 6I7T (I 02JC0 /WEB)
Mechanical Permit Application - City of Tigard •
Page 2 - Supplemental Information
Commercial Fee Schedule:
Total Valuation: Permit Fee:
$1.00 to $2,000.00 Minimum fee $72.50
$2,001.00 to $5,000.00 $72.50 for the first $2,000.00 and $2.30
for each additional $100.00 or fraction
thereof, to and including $5,000.00.
$5,001.00 to $10,000.00 $141.50 for the first $5,000.00 and
$1.80 for each additional $100.00 or
fraction thereof, to and including
$10,000.00.
$10,001.00 to $50,000.00 $231.50 for the first $10,000.00 and
$1.35 for each additional $100.00 or
•
fraction thereof, to and including
$50,000.00.
$50,001.00 to $100,000.00 $771.50 for the first $50,000.00 and
$1.25 for each additional $100.00 or
fraction thereof, to and including
$100,000.00.
$100,000.01 and up $1,396.50 for the first $100,000.00 and
•
$1.10 for each additional $100.00 or
fraction thereof.
Note: All new commercial buildings require 2 sets of plans.
•
I: \Building\Permits MEC-PermitApp.doc 01/19/07 2
. • - " is ,
A4 e6 oRoti- � 3 9Co
Form 4a Project Name: IS L ui --pm) Page: I 4
SYSTEMS - GENERAL o-o I k a Part 1 of 6
Applicability 7/ G) ) G IL Plans/ Specs
Discussion of qualifying Show compliance by including a drawing sheet, detail number,
exceptions on page 4-25 specification section and subparagraph.
1. Applicablity (Section 1317) RECEIVED
Is this form required?
orm Required. Complete form if a new HVAC system is being installed, or components of i on G 0 4 2009
existing HVAC system are being replaced (I.e., equipment, controls, ductwork, and insulation.)
CITY OF TIGARD
❑ Exception. The building or part of the building qualifies for an exception from Matt bliliNG DIVISION
requirements. Applicable code exception is Section 1317.1. Portions of the building that
qualify:
Area: Exception ❑ -1 ❑ -2 ❑ -3
Area: Exception ❑ -1 ❑ -2 ❑ -3
Area: Exception ❑ -1 ❑ -2 ❑ -3
❑ Form Not Required. This project does not contain work required to comply with code.
2. Simple or Complex Systems (Section 1317.9 or 1317.10)
rmple System. Building contains only Simple HVAC System(s). Complete this form (4a) and
equipment efficiency worksheets as required. Form 4b is not required.
❑ Complex System. Project includes a Complex System. Complete this form (4a), form 4b and
equipment efficiency worksheets as required.
3. Equipment Performance (Section 1317.5)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
combustion heating equipment, or heat - operated cooling equipment.
T omplies. All new HVAC equipment have efficiencies not less than those required by code.
he following equipment efficiency worksheets are attached:
❑ -4a ❑ -4b ❑ -4c ❑ -4d ❑ -4e ❑ -4f ❑ -4g ❑ -4h ❑ -4i ❑ -4j
4. Duct Insulation and Sealing (Sections 1317.7 as 1317.8)
❑ No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums.
omplies. The plans and specifications call for all air - handling ducts and plenums to be insuted
a nd sealed as required by Sections 1317.7 &1317.8.
5. Distribution Transformers (Section 1316.1)
� No Distribution Transformers. The plans /specs do not call for new distribution transformers.
Complies. All new distribution transformers comply with efficiency, testing, and labeling
❑
requirements of Section 1316.1.1.
❑ Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion:
❑ -1 ❑ -2 U-3 ❑-4 U-5 U-6 U-7 ❑ -8 U-9 ❑ -10 ❑ -11 U-12 U-13 U-14
Attach relevant documentation for appropriate exception. The plans /specs show compliance in the
following locations:
I i ,
4 -1
Compliance with OSSC, effective 04/01/07
•
Form 4a Project Name: rst > Page:l
SYSTEMS - GENERAL Part 2 of 6
6. HVAC Controls (Section 1317.4)
6.1 System Thermostat /Zone Controls (Section 1317.4.1)
214 .• mplies. All new HVAC systems include at least one temperature control device responding to
temperatures within the zones.
❑ Exception. HVAC system qualifies for an exception from zone control requirements.
The applicable code exception is Section 1317.4.2, Exception ❑ -1 ❑ -2
Portions of the building that qualify: I ,
The plans /specs show compliance in the following locations:
6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3)
omplies. Systems must have at least one of the following features:
'' A• • ntrol Setback Complies. Each system is equipped with automatic control capable,of
reducing energy through control setback during periods of non -use or alternate use of spaces
❑ Equipment Shutdown Complies. Each system is equipped with controls capable of reducing
energy use through automatic shutdown during periods of non -use or alternate use of spaces_
❑ HVAC systems with equipment shutdown are equipped with at least one of the following:
❑ Programmable controls (1317.4.3.1 (1))
❑ Occupant sensor (1317.4.3.1 (2))
❑ Interlocked to a security system (1317.4.3.1 (3))
❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4))
❑ Exception. The building qualifies for an exception to the requirement for automatic setback or
shutdown controls. The applicable code exception is Section 1317.4.3 Exception ❑ -1 ❑ 2
The plans/specs show compliance in the following locations:
I
6.3 Control Capabilities (Sec. 1317.4.2.1)
omplies. Zone thermostats are capable of being set to the temperatures described in Sec.
prt
1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements.
The applicable code exception is Section 1317.4.2.1 Exception ❑ -1 ❑ -2
Portions of the building that qualify:
The plans/specs show compliance in the following locations:
6.4 Optimum Start Controls (Section 1317.4.3.2)
❑ Complies. Separate HVAC systems have controls capable of varying start-up time of system to
'
p. ps x
st meet temperature set point at time of occupancy.
ception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm.
The plans/specs show compliance in the following locations:
` .5 Heat Pump Controls (Section 1317.4.4)
ri 1 0 Heat Pump. The plans /specs do not call for a new heat pump
. • Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize
the use of supplemental heat as defined in Section 1317.4.4.
s >
, > The plans/specs show compliance in the following locations:
5 ,( WI .
4 -2
Compliance with OSSC effective 04 /01/07
i.
Form 4a Project Name: _,.1 ` 111J Page:
SYSTEMS - GENERAL Part 3 of 6
7. Economizer Cooling (Section 1317.3)
No Cooling. The building plans do not call for a new fan system with mechanical cooling.
ec
omplies. Each new fan system has an air economizer capable of modulating outside -air and
return-air dampers to provide up to 100 percent of the design supply air as outside air.
❑ Exception At least one new fan system qualifies for an exception. The applicable code exception
is Section 1317.3, Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5 ❑ -6 ❑ -7
If Exception 3 is selected complete the following:
(a) Total cooling capacity of exempt units (Btu /hr)
(b) Total installed building cooling capacity (Btu /hr) f
❑ Complies. Sum of exempt units rated at less than 54,000 Btu /hr is <240,000 or a/b
< 0.10 (10% of total building cooling capacity).
Unit Identifier of exempt units:
The plans /specs show compliance in the following locations:
Economizer Pressure Relief es Integration (Section 1317.3.1 and 1317.3.2)
7 ,,,: 7 : 1 :: o Economizers Required. Project does not contain a new fan system requiring economizers.
Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for
each fan system that will relieve the extra air introduced by the economizer.
l itIntegration Complies. Economizer is capable of providing partial cooling even when additional
mechanical cooling is required to meet the remainder of the cooling load.
❑ Exception: The applicable exception is Section 1317.3.2, Exception ❑ -1 ❑ -2
The plans /specs show compliance in the following locations:
9. Hot Gas Bypass (Section 1317.5)
o Hot Gas Bypass
11 Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in
table below.
Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity
Allowable Hot Gas Bypass
E .5 7) Rated Cooling Capacity Max Hot Gas Bypass
0
' y A240,000 Btu /hr 50%
�" >240,000 Btu /hr 25%
❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu/h
4 -3
Compliance with OSSC, effective 04/01/07
Form 4a Project Name: Cam, 'Y Page: I
SYSTEMS - GENERAL Part 4 of 6
10. Shutoff Dampers (1317.4.3.3)
�❑ Not Required. Shutoff dampers are not required on this project.
omplies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers
❑ Exception. The building qualifies for an exception to the motorized damper requirement. The
applic -able code exception is Section 1317.4.3.3 Exception ❑ -1 ❑ -2 ❑ -3 ID-4 ❑ -5
The plans /specs show compliance in the following locations:
10.1. Shutoff Damper Controls (Section 1317.4.3.3.1)
g 4, omplies. Outdoor air supply and exhaust systems shall be provided dampers that automatically
shut when systems or spaces served are not in use or during building warm -up, cooldown, or
setback.
❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems.
The plans /specs show compliance in the following locations:
0.2. Motorized Damper Leakage (1317.4.3.3.2)
omplies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate
of 4 cfm/ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998.
Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm/ft at 1.0 in
w.g. when tested in accordance with AMCA Standard 500 -1998.
The plans /specs show compliance in the following locations:
11. Piping Insulation (Section 1314)
�'• o New Piping. The building plans and specifications do not call for new piping serving a
heating or cooling system or part of a circulating service water heating system.
Complies. All new piping serving a heating or cooling system or part of a circulating service
K water heating system complies with the requirements of the Code, Section 1314.1.
Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ -1 1:1 -2
0
12. Occupancy Ventilation
omplies. Mechanical ventilation systems provide the required amount of ventilation specified
n Chapter 4 of the Oregon Mechanical Specialty Code.
i .
❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a
reg- istered architect or engineer as specified by Section 1203.4.1, Exception. Attach worksheet
The plans /specs show compliance in
the following locations: f /O V / P/,& a L 3r) c "-/ OA-
, The plans /specs show compliance
on the following pages:
4-4
Compliance with OSSC, effective 04/01/07
Form 4a Project Name: L y "" Page:
SYSTEMS - GENERAL Part 5 of 6
13. High Occupancy Ventilation (Section 1317.2.2)
0 Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve
areas having an average occupant load of 20 square feet per person or less from Table
1004.1.2 have a means to automatically reduce outside air intake.
Identify applicable systems:
Plans /specs indicate where equipment (i.e. carbon dioxide sensor) and sequence is specified:
0 Exception. HVAC systems are equipped with an energy recovery device with at least 50%
, recovery effectiveness.
No High Occupancy Systems. Project does not contain an HVAC system as described above.
14. Exhaust Air Heat Recovery (Section 1318.3)
0 Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2)
min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air
Cl Complies. Heat recovery system increases outside air temperature by 20 °F (Climte Zone /I) or
30 °F (Zone 2) and has provision to provide bypass during air economizer mode.
7( Exception. An HVAC system qualifies for an exception to this requirement. Applicable
exception from Section 1318.3 Exception 0 -1 0 -2 0 -3 0 -4 0 -5 0 -6 0-7
The plans /specs show compliance in the following
locations:
72i4 Large Volume Fan Systems (Section 1318.4.2.4)
of Regulated. The building plans or specifications do not call for fan systems over 15,000
CFM that serve a single zone and function for the purpose of temperature control.
0 Complies. Fan systems are equipped with variable frequency drive or two speed motor to
reduce airflow as required by Section 1318.4.2.3.
The plans /specs show compliance in the following
locations:
??
. Variable Speed Drives (Section 1317.10.3.1)
of Regulated. The building plans or specifications do not call for fan and pump motors 10
horsepower and greater that serve variable -flow air or liquid systems.
0 Complies. All fan and pump motors 10 hp and greater which serve variable -flow air or liquid
systems are controlled by a variable -speed drive.
0 Exception. The building qualifies for an exception to the variable -speed drive requirement.
Portions of the building that qualify:
Applicable code exception is Section 1317.10.3.1, Exception
The plans /specs show compliance in the following
locations:
1 Service Water Heating (Sec. 1315)
o New Water Heating. The building plans and specifications do not call for new water
heaters, hot water storage tanks or service hot water distribution systems.
❑ Complies. All new water heaters, hot water storage tanks or service hot water distribution
systems comply with the requirements of the Section 1315.
0 Exception. The applicable code exception is Section: Exception:
s'. •
7 ' Port of the building that qualify:
The plans /specs show compliance in the following locations:
4 -5
Compliance with OSSC, effective 04 /01/07
Form 4a Project Name: .�S / 7,-)3 4 Page:I
SYSTEMS - GENERAL Part 6 of 6
18. Swimming Pools, Spas and Hot Tubs (Section 1315.5)
o New Pools. The building plans and specifications do not call for new, swimming pools, spas or
ot tubs.
h .
❑ On /Off Controls Complies. Spa and hot tub heaters are equipped with a readily access
ON /OFF switch as required by Section 1315.5.1.
❑ Ventilation Controls Complies. Pool ventilation system is controlled based on humidity.
❑ Cover Complies. All heated pools, hot tubs and spas are equipped with a cover.
❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as
required by Section 1315.5.3.
❑ Exception. Heat recovery is not necessary as pool is heated by renewable energy or waste
heat recovery sources capable of providing at least 70 percent of the heating energy
required over an operating season.
19. Fume Hoods (Section 1317.2.1.)
• '`' i Fume Hoods. The building plans do not call for fume hood systems that have a total exhaust
rate greater than 15,000 cfm.
I Complies. Fume hood systems have at least one of the following features:
❑ Variable air volume hood exhaust and room supply systems capable of reducing exhaust
and makeup air volume to 50% or less of design values.
❑ Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no
warmer than 2° F below room set point, cooled no cooler than 3° F above room set point,
no humidification added, and no simultaneous heating and cooling used for
dehumidification control.
❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance
with 1318.3 - Exhaust Air Energy Recovery, without using any exception.
The plans /specs show compliance in the following locations:
•
2 . Parking Garage Ventilation (Section 1317.2.3)
tilli Enclosed Garages. The building plans and specifications do not call for enclosed Group S-2
parking garages with a ventilation exhaust rate greater than 30,000 CFM.
Complies. The plans and specifications call for carbon monoxide sensing devices as required by
Section 1317.2.3.
❑ Exception. Open parking garages.
21. Kitchen Hoods (Section 1317.11)
❑ Not Regulated. The plans /specs do not call for any new kitchen hoods with exhaust capacity
greater than 5,000 cfm each.
❑ Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at
least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b)
uncooled or evaporatively cooled.
The plans /specs show compliance in the following locations:
r 1rr ". N
- (11 `u
2 Outside Heating Systems (Section 1317.12)
o Outside Heating Systems. The plans /specs do not call for new permanently installed healing
systems outside the building.
❑ Complies. All new permanently installed outside heating systems are radiant gas fired systems
controlled by an occupancy sensor or timer switch as required by Section 1317.12.
4-6
Compliance with oSSC, eftedive 04 /01/07