Correspondence • March 16, 2006 Greg Heath a ' Universal Fire Equipment, Inc. 8049 SW Cirrus Drive Beaverton, OR 97008 RE: FIRE SUPPRESSION SYSTEM Building Permit: BUP2006 -10005 Construction Type: NA Tenant Name: NV House Restaurant Occupancy Type: NA Address: 13405 SW Pacific Highway The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition; and the State of Oregon Fire Code (OFC), 2004 edition. The submitted plans are approved subject to the following. • Each automatic fire suppression system shall have both automatic and manual actuation means. A manual activation device shall be located at or near a means of egress from the cooking area, a minimum of 10 feet and a maximum of 20 feet from the kitchen exhaust system. The manual activation device shall be located a minimum of 4' /z feet and a maximum of 5 feet above the finished floor. 509.3 OMSC • The actuation of the automatic fire suppression system shall automatically shut down the fuel or electrical power supply to the cooking appliances. The fuel and electrical power supply reset shall be manual. 509.4 OMSC • • A portable fire extinguisher shall be provided within a 30 foot travel distance of the cooking equipment. A Class K rated extinguisher is required if the cooking equipment involves vegetable or animal oils or fats. Section 904.11.5 OFC • Wet - chemical systems shall be inspected and tested at 6 -month intervals. Carbon Dioxide & Clean -agent systems shall be inspected and tested at 12 -month intervals. Sections 904.5, 904.8 & 904.10 OFC. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of con ction. 106.4.6 OMSC Respect , rian Blal Senior P s Examiner OFFICE COPY