Correspondence •
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
February 13, 2009 II
1111
. ..
RE: MECHANICAL REFRIGERATION T I GARD
Proiect Information
Building Permit: MEC2009 -00054 Construction Type: 5 -B
Tenant Name: Dollar Tree Occupancy Type: M
Address: 11945 SW Pacific Hwy. Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
Please provide valuation for all equipment as well as cost for labor for total valuation to
calculate permit fees.
1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon
insignia of compliance located on the exterior side of the panel located nearest
the door prior to final inspection.
2) Every refrigerant - containing part of every system that is erected on the premises
• shall be tested and proved tight after complete installation, and before operation.
Tests shall include both the high and low- pressure sides of each system and
shall not be pressured down until verification of the City of Tigard Building
Inspector.
When submitting revised drawings or additional information, please attach a copy of the
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard
in tracking and processing the documents.
Respectfully,
/2)PC( p
'r ,
Dan Nelson,
Senior Plans Examiner
(503)718 -2436
dann @tigard- or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
February 17, 2009
•
RE: MECHANICAL REFRIGERATION T I GARD
Project Information
Building Permit: MEC2009 -00054 Construction Type: 5 -B
Tenant Name: Dollar Tree Occupancy Type: M
Address: 11945 SW Pacific Hwy. Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon
insignia of compliance located on the exterior side of the panel located nearest
the door prior to final inspection.
2) Every refrigerant - containing part of every system that is erected on the premises
shall be tested and proved tight after complete installation, and before operation.
Tests shall include both the high and low- pressure sides of each system and
shall not be pressured down until verification of the City of Tigard Building
Inspector.
When submitting revised drawings or additional information, please attach a copy of the
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard
in tracking and processing the documents.
Respectfully,
...5
Dan Nelson,
Senior Plans Examiner
(503)718 -2436
dann@tigard-or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772