Correspondence September 9, 2005 CITY OF TIGARD OREGON PMSI LLC Sara Holsey 21195 NW Evergreen Pkwy 204 s• Hillsboro, OR 97124 RE: TI MECHANICAL GAS LINE SYSTEM — JO ANN'S FABRIC Project Information Building Permit: MEC2005 -00545 Occupancy Type: M Tenant Name: Jo Ann's Construction Type: 5- B Address: 11945 SW Pacific Hwy #250 Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition. The submitted plans are approved subject to the following. 1. Gas piping systems under 14 inches water column pressure, shall be tested at a pressure of not less than 10 pounds per square inch gage. Test pressures shall be held for not less than 15 minutes with no perceptible drop in pressure. For welded piping, and for piping carrying gas at pressures exceeding 14 inches water column pressure, the test pressure shall be at least 60 pounds per square inch for not less than 30 minutes. OMSC C406.4.1 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Val Henzel, Senior Plans Examiner 13125 SW Hall Blvd., Tigard; OR 97223 (503) 639 -4171 TDD (503) 684 -2772