Correspondence September 9, 2005
CITY OF TIGARD
OREGON
PMSI LLC
Sara Holsey
21195 NW Evergreen Pkwy 204
s• Hillsboro, OR 97124
RE: TI MECHANICAL GAS LINE SYSTEM — JO ANN'S FABRIC
Project Information
Building Permit: MEC2005 -00545 Occupancy Type: M
Tenant Name: Jo Ann's Construction Type: 5- B
Address: 11945 SW Pacific Hwy #250 Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC)
2002 edition. The submitted plans are approved subject to the following.
1. Gas piping systems under 14 inches water column pressure, shall be tested at a pressure of
not less than 10 pounds per square inch gage. Test pressures shall be held for not less than
15 minutes with no perceptible drop in pressure. For welded piping, and for piping carrying
gas at pressures exceeding 14 inches water column pressure, the test pressure shall be at
least 60 pounds per square inch for not less than 30 minutes. OMSC C406.4.1
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in
such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respectfully,
Val Henzel,
Senior Plans Examiner
13125 SW Hall Blvd., Tigard; OR 97223 (503) 639 -4171 TDD (503) 684 -2772