Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. •• Tigard, OR 97223
March 27, 2008
RE: MECHANICAL REFRIGERATION T I GARD
Project Information
Building Permit: MEC2008 -00150 Construction Type: 5 -B
Tenant Name: Daxing Seafood Occupancy Type: B
Address: 11945 SW Pacific Hwy. Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon
insignia of compliance located on the exterior side of the panel located nearest
the door prior to final inspection.
2) Every refrigerant - containing part of every system that is erected on the premises
shall be tested and proved tight after complete installation, and before operation.
Tests shall include both the high and low- pressure sides of each system and
shall not be pressured down until verification of the City of Tigard Building
Inspector.