Correspondence • '.- City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 November 9, 2007 RE: COMMERCIAL EXHAUST HOOD T I GARD Project Information Building Permit: MEC2007 -00562 Occupancy Type: A -2 Tenant Name: 7 Estella's Taqueria Construction Type: VN Address: 11945 SW Pacific Hwy. H104 Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following information shall be submitted prior to issuance of permit. 1) Provide all cut sheets for equipment to be installed. 2) Provide drawings showing" specific installation of hood and exhaust duct showing the dimensions of the duct and all clearances. 3) Show how all thread rod holding hood is attached to structure. 4) Show connections and clearances for exterior grease duct. Ducts exposed to the outside atmosphere shall be protected against corrosion in an approved manner. 506.2 OMSC A Performance Test shall be conducted upon completion and before final approval of the installation of the ventilation system. The performance test shall verify the rate of airflow to be in compliance with the approved plans. 507.17 OMSC The exhaust and make -up air system shall be electronically interlocked to ensure that the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC An automatic fire suppression system shall be provided to protect the surface of the heat - processing appliances and the exhaust system serving the appliances. 509.2 OMSC Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal.area. 307.1 OMSC Phone: 503.639.4171 • Fax: 503.684.7297 , • www.tigard - or.gov • TTY Relay: 503.684.2772 P ' Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. - Respectfully, toasork II an Nelson, • Senior Plans Examiner - City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 December 3, 2007 RE: COMMERCIAL EXHAUST HOOD T I GARD Project Information Building Permit: MEC2007 -00562 Occupancy Type: A -2 Tenant Name: 7 Estella's Taqueria Construction Type: VN Address: 11945 SW Pacific Hwy. H104 Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following � information shall be submitted prior to issuance of permit. 1) Provide all cut sheets for equipment to be installed. 2) Provide drawings showing specific installation of hood and exhaust duct -- �)R -- showing the dimensions of the duct and all clearances. 3) Show how all thread rod holding hood is attached to structure. / A �� 4) Show connections and clearances for exterior grease duct. `t tic 5) Please call me @ (503) 718 -2436. e-T Sv -ky g— 1 c157 Ducts exposed to the outside atmosphere shall be protected against corrosion in an approved manner. 506.2 OMSC A Performance Test shall be conducted upon completion and before final approval of the installation of the ventilation system. The performance test shall verify the rate of airflow to be in compliance with the approved plans. 507.17 OMSC The exhaust and make -up air system shall be electronically interlocked to ensure that the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC An automatic fire suppression system shall be provided to protect the surface of the heat - processing appliances and the exhaust system serving the appliances. 509.2 OMSC Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC Phone: 503.639.4171 • Fax: 503.684.7297 • • www.tigard - or.gov • TTY Relay: 503.684.2772 4. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, an el on, Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov City Of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 October 10, 2007 • • .• RE: COMMERCIAL EXHAUST HOOD T I GARD Proiect Information Building Permit: MEC2007 -00562 Occupancy Type: A -2 Tenant Name: 7 Estella's Taqueria Construction Type: VN Address: 11945 SW Pacific Hwy. H104 Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following information shall be submitted prior to issuance of permit. 1) Provide all cut sheets for equipment to be installed. 2) Provide drawings showing specific installation of hood and exhaust duct showing the dimensions of the duct. 3) Show how all thread rod holding hood is attached to structure. 4) Show connections and clearances for exterior grease duct. Ducts exposed to the outside atmosphere shall be protected against corrosion in an approved manner. 506.2 OMSC A Performance Test shall be conducted upon completion and before final approval of the installation of the ventilation system. The performance test shall verify the rate of airflow to be in compliance with the approved plans. 507.17 OMSC The exhaust and make -up air system shall be electronically interlocked to ensure that the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC An automatic fire suppression system shall be provided to protect the surface of the heat - processing appliances and the exhaust system serving the appliances. 509.2 OMSC Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 y ,. ' r- • Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, l D an Nelson, Senior Plans Examiner City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 December 19, 2007 RE: COMMERCIAL EXHAUST HOOD TI GARD Project Information • Building Permit: MEC2007 -00562 Occupancy Type: A -2 Tenant Name: 7 Estella's Taqueria Construction Type: VN Address: 11945 SW Pacific Hwy. H104 Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following information shall be submitted prior to issuance of permit. Ducts exposed to the outside atmosphere shall be protected against corrosion in an approved manner. 506.2 OMSC A Performance Test shall be conducted upon completion and before final approval of the installation of the ventilation system. The performance test shall verify the rate of airflow to be in compliance with the approved plans. 507.17 OMSC The exhaust and make -up air system shall be electronically interlocked to ensure that the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC An automatic fire suppression system shall be provided to protect the surface of the heat - processing appliances and the exhaust system serving the appliances. 509.2 OMSC Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC • All deep -fat fryers shall be installed with at least a 406 mm (16 in.) space between the fryer and surface flames from adjacent cooking equipment. 12.1.2.4 • Where a steel or tempered glass baffle plate is installed at a minimum 203 mm (8 in.) in height between the fryer and surface flames of the adjacent appliance, the requirement for a 406 mm (16 in.) space shall not apply. 12.1.2.5 Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, • shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. , When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. ciinc Respectfully, r5' Dan Nelson, Senior Plans Examiner (503) 718 -2436 dann @tigard -or.gov