Specifications b o 4 I ( e SIEMENS Fire Safety FireSeeker Model FS -250 Addressable Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS • One intelligent signaling line circuit (Style 4 or 6) • SureWire polarity insensitive loop wiring • Utilizes H -Series detectors and devices • Supports up to 252 addressable inputs AND signal /relay outputs SIEM ENS • Devices operate on standard wire, no twist or shield required • FirePrint application specific fire detection • 4 Class B/2 Class A NAC circuits €€ • Up to 6 amps of NAC power , I- • • Built in strobe synchronization protocol • One man walk test (silent or audible) ( � +�!1 • 80 Character backlit LCD display • Optional internal DACTcapable of transmitting point or group information = i • Programmable from front keypad or Windows based PC configuration tool • Built in RS -232 port for computer programming • 2000 event history log • Alarm, trouble, supervisory and power fail relays built -in FS -250 • Auto program feature makes system start-up faster • Maintenance and technician level passwords 0 , MEA and CSFM listed The FS -250 addressable fire alarm control panel is a maintenance level functions such as viewing history or small, low cost fire alarm panel suited for stand -alone system enable /disable are also accomplished through the operation in small to medium sized facilities. It features a membrane control buttons. Password protection of single addressable input device circuit and four notification maintenance level functions is present. The main system appliance circuits. The system is available with both a can support up to 38 AH battery sets, up to 10 AH will fit black or red enclosure, with operating controls and inside the enclosure. indicators behind a locked door. The FS -250 is Listed by Underwriters Laboratories. The basic FS 250 features a single addressable signaling line circuit (Style 4 or 6) capable of supporting up to 252 addressable input devices, whether they are detectors, Main System manual pull stations, or contact monitoring points. Each The FS -250 indicates alarm, trouble and supervisory detector can also have an optional audible detector base, conditions with an 80 character backlit LCD display and relay detector base, or remote lamp associated with it. integral system status LEDs. Acknowledge, alarm These auxiliary devices are completely controlled through silence, and system reset are accomplished with logic, and are not required to activate simultaneously with built -in membrane control buttons. Basic user and the detector. • CATALOG NUMBER 4306 • The system also has four class B or 2 class A Notification DCS 8, SIA DCS 20, Ademco Contact ID, 3/1 1400 Hz, 3/ Appliance Circuits built into the main board. Each circuit 1 2300 Hz, 4/2 1400 Hz and 4/2 2300 Hz. The FS -DACT has a capacity of 1.5 amps of 24VDC for powering horns, mounts within the FS -250 enclosure on an 8 -pin connec- strobes, chimes, and other notification appliances. The tion point on the main board. No external enclosure is total base system capacity for the four circuits is 3.0 required, and no wires are required between the panel amps and can be expanded to 6A. Each NAC is fully • and the dialer. Programming of account and dialing programmable, and supports standard and custom coded information is done as part of the system configuration: outputs of audible devices. Systems can be configured No external programmer for the dialer is required. to sound different codes on the same NAC to indicate different conditions. Municipal Tie/Leased Line s. The For installations that require connection to a municipal he FS -250 has four Form C relays on the main board for call box or a leased line, the Model FS -MT municipal monitoring alarm, supervisory, power fail and trouble tie module is used. The FS -MT provides a local energy conditions. Each relay is rated at 1 amp @ 28VDC. output for municipal call box connection and a reverse • Auxiliary 24VDC power is also available on the main polarity output for lease line connection. The unit board, with a capacity of up to 0.5 amps. mounts within the FS -250 enclosure on an 8 -pin connec- tion point on the main board. Configuration of the FS -MT The. LOOP . parameters is done as part of the system configuration. . The FS -250 utilizes the advanced P -2 protocol for the Programmable Relays detection circuit. The P-2 loops features include Programmable relays are available on the FS -250. A SureWireTM technology providing, 252 addresses (inputs remote processor board communicates with the main AND outputs), polarity insensitivity, response time under system board via an RS-485 communication network. 3 seconds, retrofit installations using almost any type of This processor board controls a relay board mounted wire (shielded, non - shielded, twisted, etc.) . adjacent to it. The relay board has eight Form C relay • You can install an FS -250 using any of the H- series P -2 contacts, rated at 1 amp @ 28VDC maximum. Model FS- devices including the HFP -11 FirePrint detector. But we RU relay unit contains one processor board and one relay also offer a new low -cost HFPO -11 detector that is a non- board to add eight relays to an FS -250 system. Each FirePrint photoelectric device for the less - demanding, processor board can support up to three relay boards more cost -competitive applications. simultaneously, for a total of 24 programmable relays per processor board. Additional relay extender boards are If you require two detector accessories, such as a relay available as Model FS -RE8. A total of eight processor or audible base AND a remote lamp, you can install the boards (including serial annunciator processor boards) can new ILED -HC or ILED -HW Intelligent Remote L.E.D. that be supported simultaneously by the FS -250. All pro- con be programmed to mimic the detector L.E.D. or can grammable relay processors and modules can be respond to panel logic (see ILED installation or catalog mounted in a Model FS -AE accessory enclosure. sheet for details.) _ . Programmable Serial Annunciator Drivers Optional Modules Programmable serial annunciator drivers are available on the FS -250. A remote processor board communicates Remote LCD Annunciator . with the main system board via an RS-485 communica- The FS -250 supports a remote LCD display called the FS- tion network. This processor board controls a serial RD2. This remote display uses the same 80 character annunciator driver board mounted adjacent to it. The backlit LCD display found on the main system' panel. The driver board has sixteen outputs for LEDs. All serial FS -RD2 has remote acknowledge, silence, and reset annunciator outputs are supervised. Model FS -SAU -2 capability, secured with a keyswitch. User and mainte- serial annunciator unit contains one processor board and _ nance level functions are also possible from this remote one serial annunciator driver board to add 16 LED drivers display. Maintenance level functions require the system to an FS -250 system. Each processor board can support maintenance password for. activation. The FS -RD2 up to four additional driver boards simultaneously, fora communicates with the main system board via an RS- total of 64 programmable serial annunciator drivers per 485 communication network. Up to sixteen FS -RD2 processor board. Additional serial annunciator extender remote displays can be supported on a single FS -250 boards are available as Model FS- SAE16. A total of eight system. The FS -RD2 mounts in.a 2 "deep 6 gang processor boards (including relay processor boards) can electrical box, and the plate on the display is suitable for be supported simultaneously by the FS -250. All pro- flush mounting. grammable serial annunciator processors and modules can be mounted in a Model FS AE accessory enclosure. Digital Alarm CommunicatorTransmitter (DACT) Communication between the FS -250 and a monitoring Programming/Configuration Options station is accomplished with the Model FS -DACT Configuration of the FS -250 can be accomplished in two Digital Alarm CommunicationTransmitter. The FS -DACT ways. The operator interface includes a 16 button keypad. supports two lines and four accounts, and can transmit This keypad can be used to configure all system param- serial information by point to the Central or Remote eters, including custom messages and logic, right at the station. Communication protocols available include SIA panel with no other configuration tools. Alternately, the • • J , Model FS-CT2 configuration tool can be used on a laptop Ordering Information computer to upload, download, and edit the system configuration. The Model FS-CT2 configuration tool Model Part includes a connection cable for use between the FS -250 Number Description Number and a 9-pin serial connection, and the FS- CT2'software. FS - 250R FS - 250, Single Loop Panel, Red 599 - 049346 Use of the FS-CT2 software requires a computer running FS - 250 FS - 250. Single Loop Panel. Black 599 - 049345 Windows 98, Windows 2000, or Windows XP The FS- FS - RD2 Remote Annunciator, Black 500 - 648980 CT2 tool can be used to generate configuration reports FS - RU2 Relay Processor Card 500 649308 and download and print history. FS - RE8 8 Relay Extender 500 - 699467 If an alarm or other system event occurs during system FS Serial Annun. Processor Card 500 649307 configuration, the event will cause the panel to annunciate FS 16 Output Annunciator Extender 500 699469 . the alarm and operate the appropriate outputs. FS AE Acc. Enclosure for Serial Drivers 500- 699470 • . Elm+ FS -DACT Serial DACT 500- 699464 Custom messages for system addresses consist of two FS - MT Municiple Tie Module 500 699462 lines of twenty characters each. The characters include FS - SFT - Semi Flush Trim, Red 500 648955 both upper and lower case letters as well as numbers, FS - SFT Semi Flush Trim, Black 500.648954 punctuation marks, and control characters. This fort S - NPE Nac Power Expander Transformer 500 - 649120 character custom message will be displayed for all eve HFPO Photo Only Detector 500 - 034800 at that address. FS- 250 -CON FS -250 Electronics package 500 - 649110 FS -250 -ENCL FS -250 Enclosure. Black 500- 648952 General Specifications FS- 250 - ENCL -R FS -250 Enclosure, Red 500- 648953 • Environmental Operating temperature: 32 -120 °F (0 -49 °C) Relative Humidity- 85 % @86 °F Primary Supply Primary input voltage - 120Vac (50/60 Hz.) Maximum primary input current - • 1.3 amp @ 120Vac • Secondary and Trouble Power Supply 24 volt lead -acid battery with 7 AH -38 AH capacity • Auxiliary Power Outputs Current - 0.5 amp resettable /non - resettable power outputs • Status System Relays 4 relays rated @ 1 amp, 28 Vdc resistive • • • NAC Circuits Rating per NAC circuit, 1.5A ea., 6 max. Battery Base cabinet will accommodate a 10A battery • set. Larger batteries will require separate enclosure • FS -250 Dimensions • 22" x 18" x 5 1/4" deep — enclosure only 22 9/32" x 18 3/8" x 5 1/4" deep — enclosure with door • • Wiring, Main Termination Board Typical Notification TyNotification ' 0 Appliance Circuit Appliance Circuit Style Z. Class A Style Y. Oass B t I , ` t • k it 0 Supervised. Power Limited Supervised, Power Limited ►i See Owners Manual for See Owners Manual for • } 9 8 = 17 am' Compatible Devices Compatible Devices � -, H_ }Lc" It HI" +a_ • 'P • . Nip • Addressable Device Orcuh MAO Style 4 or 0 Operation 24VDC nominal + ■ - • Wire Resistance-50 ohms max - ( M. see Line Resistance Graph) - , Supervised. Power Limited , 1 / - See Owner's Manual for Compatible Devices . • - NAC Rating: Alarm Voltage: 2dv FW nominal Is_:::; '• Max. Alarm Current 1.6AlNAC Bradt ; Max Ripple: 16VAC �1; -'r Max Wee Voltage Drop: 1.OVDC ■ . Mar_ Stm+dbyCurren 1.OmA I::r' . NOTE: ,r 1 i'- The maximum total cement for the FS-250 NACs is am and 8.QA sa ® 1 ; ,r... with the optional additional Transformer PM FS-NPE ® 1I 0 TM In Alarm Condition o o x> LPrinterMet,�ank O ;110 O J uit } i1t O = e I Addressable • Device circuit O O °,,.I } O 0 a • I Iq �O_} Ride( chcult 1 I . wit: ltgp�C 0 41 ( ( Metworlx I tl C } Drain 2 0 Circuit O O O J eaic }Reis*Circuit3 g R. 6 o f n } Relay Circuit 4 . I ... } cira ° No o }cart Seriallnterfaee Circuit • J (e. 4 24VDC nominal, 0.4 max Auxiliary Power Outputs Status Relay Contacts 04, X-) RS-485 levels 0.4A max 8/24VDC nominal (Shown In normal standby condition/ Who Type - Twisted Par For Data Unsupery cad, Power Limited IA 28VDC max Resistive For Power Wire Resistance -11 ohms/ line ( 4000' max) Maximum atnent of all =diary outputs Limited Source, Unsupervised Supervised, Power Limited. circuits. Serial interface Oran and See Owner's Manual for • rah boards Is: O.5A • Compatible Devices. • • • • • Fire Safety. Fire Safety . • 8 Femwood Road 2 Kenview Boulevard Florham Park NJ 07932 8/05 Brampton, Ontario Siemens Buildin Technolo ies T (973) 593 2600 5M Canada L6T 5E4 9 9 FAX: (973) 593-6670 SFS-IG Tel: (905) .799 -9937 August 2005 Fire Safety Website: www.sbt.siemens.com ✓ fis Printed in U.S.A. FAX: (905) 799 -9858 Supersedes sheet dated 1/04 J { SIEMENS Fire Safety FS -RD2 Remote LCD Annunciator for the FireSeeker FS -250 System ENGINEER AND ARCHITECT SPECIFICATIONS • 4 x 20 Character Backlit Display • System Status LEDs • Optional local sounder 5ics, � a ...,...�. ,., .. • Built -in lamp test button ? w .. • `' ' "„ • �° .v —fl O ' O Orf r+w • Integral System Control Capabilities (with keyswitch) • • • • Integral System Maintenance access (with keyswitch and password) • © UL Listed The Model FS -RD2 Remote Display is used for annunciat- Ordering Information ing system events remotely from the fire alarm control panel on the FireSeeker FS -250 system. The FS -RD2 Model will mimic the system status LEDs and the 80- character Number Description Part Number event message found on the main system panel. FS -RD2 Remote LCD display for the FS -250 500-648980 The 4 x 20 LCD backlit display will illuminate upon receiving any event from the system, or upon pressing any button on the FS -RD2. System Acknowledge, Silence and Reset Capabilities are available on the FS -RD2. The control functions must be enabled using the integral keyswitch. Up to sixteen supervised FS -RD2 annunciators can be used simulta- . neously on the FireSeeker FS -250 system. Mounting is accomplished using a standard 6 gang 2" deep electrical box. The FS -RD2 requires a 2 -wire data connection from the RS -485 port on the FS -250, as well as 24VDC power. Maximum wire loop resistance is 25 ohms. CATALOG NUMBER 4308 • • • • • • • • • • • • • • • • NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and /or service problems. • Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard • Florham Park, NJ 07932 1/04 Brampton, Ontario Siemens Building Technologies Tel: (973) 593 - 2600 5(vi Canada L6T 5E4 FAX: (973) 593-6670 SFS-IG Tel: (905) 799 - 9937 January 2004 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. - FAX: (905) 799 - 9858 supersedes sheet dated 6103 • • J • ' SIEMENS Fire Safety HFPO -11 Intelligent Smoke Detector Intelligent Smoke Detector for FS -250 Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS Model HFPL - .. • Polarity Insensitive with SureWireTM Technology • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability • Detectors are self- testing, completing diagnostics - every 4 seconds • Field cleanable chamber with replaceable chamber "`` 00 011Mimiy parts available • Multi -color detector status LED 1 • Low Profile Design • Two -wire operation HFPO - 11 • Compatible Model DPU field device (Shown with DB - 11 Base) programmer /tester unit • Supports software based automatic environmental compensation • Optional fully programmable relay base, audible base, and duct housing • 0 Listed Introduction Description The Siemens BuildingTechnologies, Fire Safety Division The HFPO -11 is a plug -in, two -wire, photoelectric smoke HFP -11 Intelligent Fire Detector provides the life safety detector and is compatible with the FS -250 control panel. industry with the most reliable detection system available Each detector consists of a dust resistant, field - cleanable today. The HFPO -11 uses state -of- the -art microprocessor photoelectric chamber and microprocessor based elec- circuitry with error check, detector self- diagnostics and tronics with a low- profile plastic housing.The HFPO -11 supervision programs. utilizes state -of- the-art ASIC circuitry and surface mount technology for maximum reliability. Every HFPO -11 • The HFPO -11 intelligent fire detector is compatible with . detector is shipped with a protective dust cover.The the Fire Safety Model DPU field device programmer/ HFPO -11 detector utilizes an infrared light emitting diode tester unit, which is a compact, portable, menu - driven (IRLED), and light sensing photodiode. Under normal accessory for electronically programming and testing conditions, light transmitted by the LED is directed away detectors, easily and reliably.The DPU eliminates the from the photodiode and scattered through the smoke need for cumbersome, unreliable mechanical program- chamber in a controlled pattern.The smoke chamber is ming methods, such as dials or switches and reduces designed to manage light dissipation and extraneous installation and service costs by electronically program- reflections from dust particles or other non -smoke ming and testing the detector prior to installation. The airborne contaminants in such a way as to maintain HFPO -11 fire detector is compatible with the FS -250 stable, consistent detector operation. When smoke control panel. enters the detector chamber, light emitted from the IRLED is scattered by the smoke particles and is received by the photodiode. CATALOG NUMBER 4309 • Communications within the detector itself and between manual stations, HTRI series interfaces, HCP output the HFP0 -11 and the control panel, or with the DPU field control devices, or HZM series of addressable, conven- device programmer /tester unit, are supervised and safe- tional zone modules. All HFPO -11 detectors can be guarded against disruption by reliable, microprocessor cleaned in the field, when required, by simply removing based error checking routines. Additionally, the micro- the detector cover and unsnapping the photo chamber. processor supervises all EEPROM memory locations and There is also the option of cleaning the interior of the provides a high degree of EEPROM failure fault tolerance. detector with a clean, soft cloth or brush, or replacing The HFPO -11 determines its operating status to be the labyrinth and bug screen included in the detector normal, in alarm, or in trouble depending on the difference maintenance kit, model DMK -11. between the alarm threshold values stored in the The HFPO -11 uses the low- profile surface mounting base, detector's memory and the detector's latest analog model DB- 11.This base mounts on a 4 -inch octagon, measurement.The detector then communicates changes square, or a single gang electrical box.The base utilizes in its status to the control panel. In addition, the FS -250 screw clamp contacts for electrical connections and self - control panel will sample the value of the HFPO -11's wiping contacts for increased reliability. The base can be analog signal over a period of time in order to determine used with the optional LK -11 detector locking kit which if those values indicate excessive buildup in the photo contains 50 detector locks and an installation tool, to chamber; if so, the FS -250 control panel will indicate that prevent unauthorized removal of the detector head.The the particular detector requires maintenance. DB -11 base has integral decorative plugs ti. cover the The HFPO -11 is listed as a self- testing device.The outer mounting screw holes. All HFPO -11 detectors are HFPO -11's visible light emitting diode (LED) flashes approved for operation within the UL specified tempera - green every 4 seconds to indicate it is communicating ture range of 32 to 100 degrees F (0 to 38 degrees C). with the control panel and that it has passed its internal self -test. Should.the.detector sense a fault or failure Application Data within its systems, the LED will flash amber and the Installation of the HFPO -11 series of detectors requires a . detector.will transmit that.information to the control panel. two-wire - circuit. In many retrofit cases, existing wiring • A quick inspection is sufficient to indicate the may be used. "T-tapping" is permitted only for Style 4 condition of the detector at any time. If more detailed (Class B) wiring. The HFPO -11 is polarity insensitive. This information is required, a printed report can be provided feature can greatly reduce installation an debugging time. from:the FS -250 panel indicating the status and settings HFPO -11 detectors can be applied within the maximum assigned to each individual detector. When the HFP0 -11 30 foot center spacing (900 sq. ft. areas) as referenced in moves to the alarm mode, it will flash red and to con- NFPA 72.This applications guideline is based on ideal tinue - flashing until the system is reset at the control conditions, specifically, smooth ceiling surfaces, minimal panel. At that same time, any user defined system alarm air movement, and no physical obstructions between functions programmed into the system are activated. potential fire sources and the detector. Do not mount Detector sensitivity, calibration, and identification detectors in close proximity to ventilation or heating and are dynamically supervised by the control panel. air conditioning outlets. Exposed joints or beamed The DPU Device Program/Test Unit accessory is used to ceilings may also affect safe spacing limitations for program and verify the detector's address.The technician detectors. Should questions arise regarding detector selects the accessory's program mode to enter the placement, observe NFPA 72 guidelines. Good fire desired address.The DPU automatically sets and verifies protection system engineering and common sense the address and tests the detector.The DPU operates on dictate how and when fire detectors are installed and AC power or rechargeable batteries, providing flexibility used. Contact your local Siemens Fire Safety distributor and convenience in programming and testing equipment or sales office whenever you need assistance applying almost anywhere. FirePrint in unusual applications. Be sure to follow - NFPA guidelines and UL approved installation When in the test mode, the DPU will perform a series of instructions, which are included with every Siemens diagnostic tests without altering the address or other Fire Safety detector, and local codes as for all fire stored data, allowing technicians to determine if the protection equipment. detector is operating properly.The HF P0-11 detector may be installed on the same initiating circuit with HMS series • J , Dimensions 8" Dla. 3/r ' 1 - 1 1/2' 1- 23/4' Dia. —I 4 1/8' Dia. NOTE: The new DB -11 E base has a diameter dimension of 4 1 /2 inches. Ordering Information Part ` Model Description Number ` HFPO-11 Addressable Detector 500-034800 t>_4 DB -11 Detector Mounting Base for Series 11 500-094151 DB -11E Detector Base (small) 500. 094151E AD-11P Air Duct Housing for Series 11 500-095656 AD -HR Air Duct Housing w/Relay for H -Series 500-033280 Intelligent Detector 08 -HR Relay Base for H -Series Intelligent Detectors 500-033220 ADBH -11 Audible base 500-033210 RL-HC Remote (red) alarm indicator- 4° octagon box mount 500-033230 RL-HW Remote (red) alarm indicator- single gang box mount 500-033310 LK -11 Base Locking Kit for Series 11 detectors 5006350 DMK -11 Series 11 Maint Kit (replacement labyrinth and bug 500-695338 bug screen) • • • • • • • • • • • NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. • Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 3/04 Brampton, Ontario Siemens Building Technologies Tel: (973) 593 -2600 5!vl Canada L6T 5E4 • FAX: (973) 593 -6670 SFS-G Tel: (905) 799 -9937 March2004 Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 Supersedes sheet dated 7/03 1 • SIEMENS Fire Safety HMS Series Intelligent Initiating Devices Manual Fire Alarm Boxes ENGINEER AND ARCHITECT SPECIFICATIONS HMS -S and HMS -D Intelligent Manual Fire Alarm Boxes for FireFinder XLS Control Panels • Durable Design • Shock and Vibration Resistant • Pull Down Lever Remains Down Until Reset • Custom Microcomputer ChipTechnology 1R E F ,I RE • Dynamic Supervision • Polarity Insensitive with SureWireTM Technology o.. - PUSH HERE Q • Reset with Allen Key THEN • No Break Rods Necessary i • TwoWire Operation PULLIDOWN PULL DOWN • Surface or Semiflush Installation SIEMENS SIEMENS • DPU Programs and Verifies Device's , Address and Tests Device's Functionality • Electronic Address Programming is Easier HMS - HMS - and More Dependable Single Action Station Dual Action Station • Single and Double Action Models Available • 0, Listed, CSFM, FM and NYMEA Submitted Introduction HMS -S and HMS -D intelligent manual fire alarm boxes The HMS -S and HMS -D manual fire alarm boxes provide the markets' most advanced method of operate with FireFinder XLS Series control panels. address programming and supervision, combined with sophisticated control panel communication. Each HMS The manual fire alarm box's microcomputer chip has manual fire alarm box incorporates custom microcom- the capacity of storing, in memory, identification puter chip. The microcomputer chip technology, and its information as well as important operating status sophisticated bi- directional communication capabilities information. with the control panel, achieves the state of an "Intelli- Siemens Building Technologies Inc., Fire Safety gent Initiating Device." Division innovative technology also allows all HMS Series Intelligent manual fire alarm boxes to be pro - Description grammed by using the Model DPU Programmer/ The HMS -S and HMS -D are constructed of durable Tester. The Programmer/Tester is a compact, portable, menu driven accessory which makes programming and molded polycarbonate material which is matte finished testing a manual fire alarm box device faster, easier in red with raised white lettering. The housing accom- and more dependable than previous methods. The modates a "pull- down" lever which, when operated, DPU eliminates the need for the device's mechanical locks in position indicating the manual fire alarm box addressing mechanisms, such as program jumpers, has been activated. The pull down lever remains down dipswitches or rotary dials because the DPU electroni- and locked until the manual fire alarm box is reset. cally sets the manual fire alarm box's address into The manual fire alarm box is reset only by opening the hinged housing cover with an alien key and then closing and locking the cover. CATALOG NUMBER 6306 • The HMS -S and HMS -D are fitted with screw terminals Ordering Information for connection to an addressable circuit. They can be either surface or semiflush mounted. Shipping Weight Part Model Description Lbs. kg. Number The HMS Series manual fire alarm boxes derive or MS -S. Addressable Manual Fire 2.0 .90 500-033200 their power, communicate information and receive Alarm Box Single Action commands over a single pair of wires. HMS -D Addressable Manual Fre 2.5 1.13 500- 033400 Alarm Box, Double Action The HMS Series.is compatible on the same circuit SB - SR Surface Mounting Box 1.5 .68 310 - 019860 . with all H Series. detectors, interfaces or addressable LTP ResetTool Package .5 .23 500 conventional zone modules. (Contains 2 tools) Mou Data - >. .< HOUSING •q 4 in HINGED TO NAMEPLATE �` T S &5R BACKPLATE.%••• . / 1 3,s In ` \ 5% ill. HOUSING \ 0 `? 1'� • , � �;t 1 • � 101 • 11 . . • .11 3 in DEEP . SW ITCH BOX LOCKING 0 (USER SUPPLIED) SCREW BACKPLATE SURFACE MOUNTING ENCLOSURE . \ V Electrical Ratings . Current Draw (Active or Standby): 1.5mA • NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss. damage. liabilities and/or service problems. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 1/03 Brampton, Ontario Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4 FAX: (973) 593-6670 SFS-IG Tel: (905) 799 -9937 January 2003 • Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 Siea,s assNeeteateaizoi SIEMENS Fire Safety HTRI Series FireFinder XLS and FS -250 Intelligent Initiating Devices Interface Modules ENGINEER AND ARCHITECT SPECIFICATIONS Intelligent Interface Modules for FireFinder XLS and FS -250 Series Fire Alarm Control Panels HTRI -S, HTRI -D, HTRI -R • Interfaces and Supervises Normally Open or Normally Closed Contacts • Integral SPDT Relay (up to 4 amps) on HTRI -R Model c. ,. ` • Dual Input on HTRI -D Model using a single address • Polarity Insensitive with SureWire Technology rr _ - __ t • Multi -color L.E.D. indicates status (green, amber, red) • Easy front access to programming port and wiring terminals e z % • Mounts 4 inch square 2 '/a deep box, or double gang box • Dynamic Supervision - sop � • Comes with 5x5 inch faceplate vi.„„ ~`"`�+ i • Two wire operation , I, t , • DPU Device Program/Test Unit programs and Verifies 4° '-•' e go f Device's Address and Tests Devices functionality - -. : ' • Electronic Address Programming is Easy and Dependable 4.• =- / • 0 ULC Listed -.- CFSM, FM, NYMEA Approved Introduction The HTRI Series Intelligent interface modules are de- monitor and report the status of the contact, while the signed to provide the means of interfacing direct shorting HTRI -R incorporates an addressable Form C relay. The devices to the FireFinder XLS and FS -250 Fire Alarm HTRI -R relay and contact device input are controlled at the Control Panel loop circuit. same address. For the control panel system, the relay The HTRI Series Intelligent interface modules provide the and input contact can be controlled as a separate function. market's most advanced method of address programming The relay typically used where control or shunting of external equipment is required. • and supervision, combined with sophisticated control panel communication. Each HTRI Series interface module The HTRI -D is a dual input module and is designed to incorporates a microcomputer chip. The HTRI Series supervise and monitor two sets of dry contacts. The microcomputer chip technology and its sophisticated Dual Input Module only requires one address but re- bi- directional communication capabilities with the control sponds independently to each input. The HTRI -D is ideal panel, achieve the state of an "Intelligence Device" for monitoring a water flow switch and its respective valve tamper switch. 'Description The HTRI has a multi -color Light Emitting Diode that The HTRI Series intelligent interface modules are flashes green when operating normally, amber if unit available in three models. The HTRI -S and HTRI -R are is in trouble condition, and red to indicate a change of designed to monitor a normally open or closed dry state. The HTRI -D flashes twice, once for each ad- contact. The interface module reports the contact's dress, the HTRI -R red L.E.D. indicates a change of status to the control panel. The HTRI -S model can only state in the relay. CATALOG NUMBER 6304 • The device's microcomputer chip has the capacity of Mounting Data storing, in memory, identification information as well as Addressable Interface Model HTRI -S, HTRI -D, HTRI -R important operating status information. mounts directly into a 4 inch square 2 'A deep box or Siemens Building Technologies, Inc., Fire Safety Division a double gang box (user supplied). A 5 inch square innovative technology allows all HTRI Series intelligent off -white faceplate is included with each HTRI. interface modules to be programmed by using the DPU SLOTS Device Programming/Test Unit. The DPU is a compact, FOR 4 MOUNTING G SH portable, menu driven accessory that makes program - SWITCHBOx ming and testing an interface device faster, easier and more dependable than previous methods. The DPU eliminates the need for mechanical addressing mecha- O • 0 nisms, such as program jumpers, DIP switches or rotary dials, because the DPU electronically sets the HTRI 111 HTRI S/ - D/ - R interface's address into the interface's microcomputer I) MODULE chip nonvolatile memory. Vibration, corrosion and other �C ; • conditions that deteriorate mechanical addressing mecha- nisms are no longer a cause for concern. MOUNTING g _ HOLES FOR The HTRI Series is fitted with screw terminals for J SWITCHPLATE connection to an addressable circuit. The HTRI Series is fully compatible on the same FireFinderXLS and FS -250 circuits with all intelligent H Series detectors, HMS Series addressable manual stations or any other addressable intelligent modules, MOUNTING SLOTS such as the HZM or HCP. FOR DOUBLEGANG All HTRI Series intelligent interface modules are swrrCHBOx UL listed. • Figure A Environmental operating conditions for all HTRI Series Mounting the HTRI S/ - / - R modules are 32 °F ( °C) to 120 °F (49 °C) with a relative humidity of not greater than 93% non -condensating. Ordering Information Electrical Ratings Shipping Wt. Current Draw (Active or Standby): 1 mA Model Description Lb. Kg. Part Number HTRI -R Relay Ratings HTRI -S Single Input l oz 2 500-033370 Resistive: 4A, 125 VAC HTRI -R Single Input w /Relay 7 oz 2 500-033300 4A, 30 VDC • •HTRI -D Dual Input 7 oz 2 500-033360 Inductive: 3.5A, 120 VAC (0.6P.F.) 3.OA, 30VDC (0.6PF.) 2.OA, 120 VAC (0.4PF.) 2.OA, 120 VAC (0.35PF.) 2.OA, 30 VDC (0.35PF.) NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage. liabilities and/or service problems. Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park NJ 07932 12/04 Brampton. Ontario Siemens Building Technologies Tel: 5M Canada L6T 5E4 9 Thli g FAX: (973) (973) 59 593.2600 66 70 SFSIG Tel: (905) 799 -9937 December 2004 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 Supersedes sheet dated 110.3 V r • ' . SIEMENS • Fire Safety HTRI - M Intell Dev Interface Modu For Use With the FireFinder -XLS Control Panel • ENGINEER AND ARCHITECT SPECIFICATIONS Intelligent Interface Modules For FireFinder"" XLS Control Panels • Interfaces and Supervises Normally Open (Fire Detection) or Normally Closed Contacts (Security Detection) . ` . • Compact Size Allows Mounting in Single Gang Box ! _# Behind Equipment ; • -Polarity Insensitive with SureWire''Technology • Operates with FireFinderXLS DLC Circuit — • InnovativeTechnology Supports Comprehensive r. 1� Li I System and Interface Communication • Dynamic Supervision 4/ karnatTlam a/J. 02M Lange OM s .• Two Wire Operation FE P/N • DPU Device Program/Test Unit Electronically S Programs and Verifies Device's Address andTests ., ,T w..O Device's Functionality "°"`" '""' , • 0 ULC Listed • CSFM, FM and NYMEA Pending Introduction The HTRI -M Intelligent interface module is designed Siemens Building Technologies, Inc.,Fire Safety to provide the means of interfacing direct shorting Division innovative technology allows all HTRI -M devices to the FireFinder XLS system's DLC loop intelligent interface modules to be programmed by circuit. using the DPU Device Program/Test Unit. The DPU is a The HTRI -M Intelligent interface module provides the compact, portable, menu driven accessory that makes market's most advanced method of address program- programming and testing an interface device faster, ming and supervision, combined with sophisticated easier and more dependable than previous methods: c The DPU eliminates the need for mechanical address- control panel communication. Each HTRI -M interface ing mechanisms, such as program jumpers, DIP module incorporates microcomputer chip technology switches or rotary dials, because it electronically sets and its sophisticated bi-directional communication the HTRI -M interface's address into the interface's capabilities with the control panel. microcomputer chip non - volatile memory. Vibration, corrosion and other conditions that deteriorate me- Description chanical addressing mechanisms are no longer a cause • The HTRI -M is designed to monitor a normally open or for concern. This HTRI -M is connected to the program/ closed dry contact and reports the contact's status to tester with cable programming 110-694927) cable provided with the the control panel. tester. This cable (P /N 110 694927) utilizes two (2) alligator clip connectors, to attach to the HTRI -M. The device's microcomputer chip has the capacity of storing, in memory, identification information as well The HTRI -M Series has five leads, one for grounding, as important operating status information. which are wired to the system with user supplied wire nuts. CATALOG NUMBER 6308 • The HTRI -M is fully compatible on the same XLS circuit with all intelligent H Series detectors, HMS • Series addressable manual stations or any other H Series addressable intelligent modules, such as the HZM or HCP. • • All HTRI -M intelligent interface modules have been UL and ULC submitted. Environmental operating conditions for all HTRI -M modules are 32 °F ( °C) to 120 °F (49 °C) with .a relative • humidity of not greater than 93% non- condensatirig. Ordering Information Model Shipping Weight Part • Number Description oz. kg. Number TRI - M Single Input 3.5 .1 500 HTRI - MC ULC Model for Canada 3.5 .1 500- 034000C Electrical Ratings • Current Draw (Active or • • • • • • • • • • • • • • • • NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either • expressed or implied with regard to loss. damage, liabilities and/or service problems. • - • Fire Safety Fire Safety • 8 Fernwood Road 2 Kenview Boulevard • Florham Park, NJ 07932 1/03 Brampton. Ontario Siemens Buildin T IeS Tel: (973) 593 -2600 5M Canada L6T 5E4 9 9 FAX:19731 593L6670 SFS -IG Tel: (905) 799 - 9937 January 2003 Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799 -9858 Su,xrsedes s 1201 • • SIEMENS Fire Safety Adapter Stand Alone Selectable Strobe ENGINEER AND ARCHITECT SPECIFICATIONS • The Adapter feature offers four field selectable candela strobe values — 15/75, 30/75, 75 or 110 AGENT RELEASE for ceiling and wall mount • Operates in either sync or non -sync mode • Low current draw • • Integral universal mounting - single gang, AGENT RELEASE double gang or 4" square box • Colors- red or off -white Agent Release Strobe • ADA/NFPA/ANSI compliant FIRE • P ® UL 1971 listed for both wall and ceiling mount -CSFM, FM and ULC Listed.'° • • Made in U.S.A., ISO 9001 certified ; ,. F F I • A Dual Sync Control Module or PAD -3 is only $ €t required to activate the Instant Sync feature, FIRE nothing to set or change at the strobe unit Adapter Strobe Adapter Strobe Bell Plate Description The U -MCS series and U- MCS -6090V, U- MCS- 6090V -W The U -MCS Series uses a terminal block for easy installa- strobes combine state of the art electronics to provide tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a reliability and low current draw to meet visual life safety pigtail (4 wire) connection. applications.The Adapter feature offers four field select- able candela settings - 15/75, 30/75, 75 or 110. Strobe Synchronization requires the Dual Sync Module or PAD -3. ® Detail — Adapter Engineering Specifications S selector switch The visual notification appliances shall be Adapter U -MCS Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The integral universal mounting plate of the U -MCS candela strobe appliance, or approved equal.They shall be provides for easy installation with single gang, double listed to UL1971 (Standard for Safety Signaling Devices for gang or 4" square box mounting.The lens construction the Hearing Impaired) for indoor applications, and shall be provides high candela output with low current consump- ADAMFPA/ANSI compliant. tion while meeting UL and ADA standards. The strobe shall produce a flash rate of one (1) flash per The U- MCS- 6090V, U- MCS- 6090V -W provides the same second over the Operating Voltage Range limits of 16 to strobe choices and is constructed of metal for mounting 32Vdc.The strobe light shall consist of a Xenon flash tube bell or chime devices to the plate. enclosed in a rugged, clear polycarbonate lens. Inputs The U -MCS Series & U- MCS- 6090V, U- MCS -6090V -W shall be compatible with standard reverse polarity circuit supervision by an FACP.The Strobe shall be of low use a Xenon flashtube with solid state circuitry for current design, and shall provide a minimum of four (4 ) maximum reliability and efficiency. Strobes have a rounded dome shape made of clear polycarbonate. CATALOG NUMBER 2550 field selectable strobe intensity settings, 15/75, 30/75, 75 NOTE: These notification appliances are UL listed and rated and 110 candela. All settings shall be UL 1971 listed for as "special application", which represents appliances which • both wall and ceiling mount applications.The selector have been investigated to operate as described in the switch shall be tamper - resistant. product's installation instructions. It shall not be necessary to remove the strobe from the mounting surface to select the strobe intensity. When Ordering Information synchronization is required, the strobe shall be compat- • ible with the Dual Sync Module, or other source of Stand - Alone Strobes - Wall Mount and Ceiling Mount Siemens BuildingTechnologies, Fire Safety Division Sync Modal Pad Protocol, and shall riot drift out of synchronization. Number Description Number - U -MCS . Multicandela Selectable Strobe- Red 500 - 699701 The U Series Stand - Alone Strobe shall have an U -MCS -W Multicandela Selectable Strobe - White 500. 699702 • integral universal mounting plate that shall allow mount- . . ing to single -gang, two-gang, and 4" square backboxes, Retro - Plate Wall Mount as well as FBX -S and FBX -F Surface Boxes. A cover trim , Model Part plate shall be included to enhance appearance.There shall . Number Description Number be no mounting holes o r screw heads visible. U - MCS - 6090V Retro Plate ' 500 699703 Multicandela Selectable Strobe Red The Series U- MCS -6090V, U- MCS -6090V W Strobe Plate U•MCS 6090VW Retro Plate 500 - 699704 • shall facilitate the addition of a strobe to a bell installation. Multicandela Selectable Strobe Red The Strobe Plate shall mount to a 4" square backbox for - flush mounting. - - Stand -Alone Strobes -Wall Mount and Ceiling Mount - for Agent Release U -MCS Specifications • Model Part • . Number Description Number Environmental U- MCS -AR Multicandela Selectable Strobe - Red 500 - 699146 32 °F to 120 °F (0 °C to49 at 85% RH For Agent Release Input Voltage . . 16-32 Vdc regulated or FWR • Mounting - Canadian Ordering Information Integral universal mounting plate mounts to single ' gang, double gang or 4" square box. Stand -Alone Strobes -Wall Mount and Ceiling Mount . Shipping Weight Model Part 9 oz. approx. • Number Description Number CU -MCS Multicandela Selectable Strobe- Red 500-699701C U -MCS Dimensions CU -MCS -W Multicandela Selectable Strobe -White 500- 699702C I 4v/8" 3-1/2' ' --1 3e Retro -Plate Wall Mount . Model • • .. Part F I R E Number Description Number CU- MCS- 6090V Retro Plate ' 500 699703C 1 I- — — 1 -` � Multicandela Selectable Strobe- Red • " 40 - �� CU•MCS 6090VW Retro Plate 500- 699704C �' � • Multicandela Selectable Strobe- Red . 1ti e1. ■ , �_ _ _ _ � Strobe Intensity Setting Strobe Current Draw F I R E ------- -- selector 15/75 cd 63 mA _ , Switch 30 /75 cd 84 mA 75 cd 143 mA 110 cd m 178 A • Typical Wiring ' • Do not Loop, - T' Tap or • + + branch connect signal • • circuit field wires. • From Control Pena! Cut wire run to provide POLARITY MARKING or Previous Device or I::;! to = r To Next Device �I IA STROBE s I — or Electrical Supervision. IS FOR SYSTEM IN For Synchronization from t Siemens ALARM. Sien S Protocol Source G :I li I E.O.L Resistor Use care when posltlonb u s Previous Device r ;; t ! a field wires so that minimum '6411i W - stress Is on the appliance. ' - Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard • Florham Park, NJ 07932 3/05 Brampton, Ontario Siemens Building Technologies Tel: 51N Canada L6T 5E4 g Thli g F 936 SFSIG Tel: (905) 799-9937 March 2005 Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 Supersedes sheet dated 6/04 • • • SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The Adapter /U - MCS feature offers four field _. selectable candela values — 15/75, 30/75, 75 or 110 for wall & ceiling mount • Sync strobes and sync temporal horns, with horn 11 silence on 2 wires • Distinctive temporal horn ._: • Internally adjustable volume control t • Low current draw • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, FM &NYMEA �_.ae - s.•, • UL 1971 listed for both wall and ceiling mount I • ADA/NFPA/ANSI compliant a 1 I . • Screw terminals accept 12 awg wire - • Synchronization requires Dual Sync Control Module or PAD -3 • Made in U.S.A., ISO 9001 quality crafted Description o to Detail - Adapter The U -MHU -1 G, U -MHU -1 G -W and U -MHU, U-MHU-W selector switch Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. The U -MHU -1 G, U -MHU -1 G -W mounts to a single g-, gang box, the U -MHU, U -MHU -W and U- MHU -MCS, U- MHU -MCS -W have a universal mounting plate for Max Volume 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U- MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a crowded electrical boxes.The Adapter/U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings — 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 The U -MHU -1 G, U -MHU -1 G -W, U -MHU, U -MHU -W and Listed operating range is 16 to 32VDC/FWRTemporal U- MHU -MCS, U- MHU -MCS -W are used on circuits with maximum UL measurements are 83.6 db at 24VDC/FWR. • steady power or a Dual Sync Control Module or PAD -3. Steady tone maximum UL measurements are 878 db at 24 Not for use on coded circuits. VDC/FWR taken in free air at 360° around the device and averaged. Typical readings are frontal sound readings taken Environmental with a dB meter with signal mounted on wall. Rated for 32 °F to 120 °F (0 °C to 49 °C) with 85% humidity indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. ( -W: White) Operating Voltage Range Limits NOTE: These notification appliances are UL listed and rated Horn: 16 Vdc orVFWR as "special application; which represents appliances which • Strobe: 16 Vdc orVFWR have been investigated to operate as described in the product's installation instructions over the voltage range of Typical Horn Ratings at 10 Feet* 16 - 32 VDC or VFWR. Temporal Horn — Maximum: 95 db @ 54 mA Strobe Intensity Setting Strobe Current Draw Minimum: 90 db @ 30 mA 15/75 cd 63 mA 30/75 cd 84 mA * Typical dBA ratings are frontal sound readings 75 cd 143 mA taken with a dB meter with signal mounted on wall. 110 cd 178 mA Dimensions Control Module Specifications: r-2414.1 1 r-t�e, ��,�, i. �� Maximum Current Output: 3 Amps Max. not .! „P to exceed NAC rating r e '- DSC Module OperatingVoltage: 16 to 32 Vdc orVFW ¢ OM ' e- l la DSC Module Operating Current: Non - Silenceable j Circuit side j_ I 55mA, Silenceable • Circuit side .005 Amps. Maximum Current Output: 3 Amps max. not to 4ar4 a, exceed Circuit rating i iiiii tOWOC,1 [117 1, 2 or 4 Square Mounting 4-3/4' a �; : : b L FIRE l -- • 0 selector ; 0 - 1 or 11 For wiring diagram for U -MHU Series Horn /Strobes refer to Installation Instruction Sheet • Ordering Information U -MHU Series Horn Wall Mount Low Volume HigtrVolume High Volume Model.Number. Description Part Number Horn Current Horn Curiedt dB Ratitig:O10' U- MHU -16. ELC Sync/Nan -Sync Horn 24VDC 500- 699591 30ma 54ina 95db U -MHU fG -W , ELC Sync /Non - Sync :Horn 24 VD( 500.699592 30ma 54ma 95db U -MHU ' ELC Sync/Non -Sync Horn 24VDC • 500=699594 30ma 54ma 95 db U -MHU•W ELC Sync/Non -Sync Horn 24 VDC 500- 699593 30ma. 54ma 95db Low Volume HighVolume High Volume Model Number Description Pen Humber Horn Current Ho'rn.Current dB Bating 010' -MH -MCS , ELC Sync /Non-Sync,Horn.w /Strobe:(Red) 500499587' 30ma. 54ma 95db U -MHU- MCS -W. ELC Sync /Pion- SyncHomia /Strobe`(Whitel 500.699588- 30ma. 54ma 95db *All current measurements made at 24VDC Canadian Ordering Information CU -MHU Series Horn Wall Mount Low Volume High Volume High Volume Model Number Description Part Mamba Horn Current Horn Current dB Rating @HY CU -MHU -1G ELC Sync/Non -Sync Horn 24 VDC 500;699591C lima 25ma 95db 'CU7MHU -1G -W ELC Sync/Non =Sync Horn 24VDC '500- 699592C , lima 25ma 95 lib CU -MHU ELC Sync/Non -Sync Horn 24VDC 500= 699594C lima 25ma 95db CU -MHU -W ELC Sync/Non=Sydc Horn Z4VDC 500 17ma 25ma 95db Low Volume High Volume High Volatile Model Number Description Part - Number Horn Current Horn Current dB Bating @10' CU= MHU -MCS ELC Sync /Non Syn¢Horn w /Strobe (Red) 50.0699587C lima 25ma 95db "CU- MHU -MCS -W EtC Sync /Non- Sync,Horn w /Strobe (White) :500.699588C limo 25ma 95db Wiring Diagrams Typical Wiring for U- MHU -1G and U-MHU for Synchronized Operation with DSC Dual Sync Control Module (Sync andSllenceable Operation) Polarity Shown In Alarm Condition Audible Control From oontrat_panel silenoeable Notification Appfanoe Cuouit (NAC,) 9 . o o < A udible Power `I MI 1 I t,.a. From control panel steady (n�p�n9) non -silen cable Notification Appliance Circuit (NA.C.)1 11.1!1 1,��? 1 Pal 1rr I j Individual wires (especially heavy al 1.'4.1 DS l i r I 0 _ I gain wire) should be bent at 90° 1..., " .. t r before attaching to screw. Wiring ocarwn M9 _- , should then carefully be pushed ani o a i- �- a back Into back box to minimize amn swe Al !' =i 0 , i stress on the terminal block. not usae in spec mixedovaaf!a //77 Supervised and, -^0 p o� powered by -- Non-Silenceable - _ •. • NAC. from Fire -+ To Next Devida Alai Control Unit - or E.O.L. Fig. 4- Typical Wiring for U- MHU -1G and U-MHtl for Non -Synchronized Operation Polarity Shown In Alarm Condition I From control panel.. steady sitenceable Notifidafion ApPtiance. Circuit (NAC.) . ; I Individual wires (especially heavy © - - - i , gauge wire) should be bent at 90° r Jumper Selection - i . r r r '—'� - before attaching to screw. Wiring On a 18rnpoal Hom r r should then carefully be pushed Off , Steady Horn + back into back box to minimize 0 _ stress on the terminal block. Jumper selection 111 Is enty for use in ' Non- synchronized 0124 operation — — • - * To Next Device . -- or EO.L Fig:.S Wiring Diagrams Typical Wiring for U- MHU -MCS for 'Synchronized Operation with DSC Dual Sync Control Module Audible Signal and Strobe on Same Circuit (Audible Signal and Strobe Synchronized), Audible Signal Silenceable Polar Sheen In Merin Corxfdion Note: When audible and strobe units ere powered from the samesotaoa, add the currents for both devices. Audi Co ntro Leave Jumpers at Place F rom i control panel seertceable Nolifieation Apptanoe CticuM (NA:C.) ( (Strobe ono Audbe Slprmi at. to �I SameCtrevaj Audible and Strobe - j =,..e;/ O 0 �� Ram cantor peva steatite ( P na1 830ppHarmpCieUit(NAC.) ` - !I, (...*•211.: j ,.., --z. _.... „... .. Ft." - „, - i l osc rs• I u 1 _I h i ISM dconvwwe I:0:1 l'. ! I . h Individual wires (especially o a l O i� � 0 y ranee wire) ano ild be r bent at e0° before dtt thing 3' '. �; carefully be pushed teen I_ L nacre alto I. Supervised ant ----..„/ _ I . r ��srisa J -. beck box to minimize'dtrese � ,' t On the terminal brook Ndn- seenoeable :MIAMI � �� li , I — I i I NAC. from Fire — — - - ._ - Alarm Control Unit • To Net Device JurttperSete - or E.O:L natured in srnduorekort Operation Fig. 6 • Typical Wiring for U41HU -MC6 for Non- Synchronized Operation Audible Signaland Strobeon Same Circuit Patty Shown'ln Alan Co dWon' Note; When audible and strobe units are powered frbtn the same tmtnme, add the currents for both devices. t eaveJum ers a Place From control panel. (Sesta andAudige Signal we to steady ai oeabie Notification Appliance Cecilia (MAC.) I operate on : Samecrrcttitl ilia mei J f t -t 5 I � I �r I I ,TI_.!_I. —I Ct i Norm: SpuraeSemeMrrboCav and I roaAO+AmroNatSm[a hda �. 1 1 ��II l i dual (especially Jumpe Setscrew' li r li O I ea rA should on a Temporal , T -...&.. _ _ "- !! w straw. Wiring shotdd then Offs j ki. '"'I' I + � I l; Ir�`i I , carefully be pushed :back Into 4∎ : MII _ 7'4n.r — J ! i 1 iri►fu' I:;' back box to minimize stress Jumper salesCort i a ili the teirnbtal block e �. N n -s ror - ; I , r_ I_l-�_.. �� Non-synchronized operation --e To Next Device ■ - or EiO.L Fig: 7 Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park, NJ 07932 3/05 Brampton. Ontario Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T5E4 9 9 FAX: (973) 593.6670 SFS4G Tel: (905) 799 -9937 March 2005 Fire Safety Website: www.sbt.siemens.comlris Printed in U.S.A. FAX: (905) 799 -9858 Supersedes sheet dated e/w SIEMENS Fire Safety DT -1358, DT -135F, DT-200R, DT-200F Thermal Fire Detectors ENGINEER AND ARCHITECT SPECIFICATIONS ;;'ice • 5 • 0 Listed • FM Approved Introduction Rate -of -Rise Principle of Operation: The Siemens Building Technologies, Fire Safety Division The rate-of -rise element consists of an air chamber, a Thermal Fire Detectors are fixed temperature or combina- flexible metal diaphragm and a moisture - proof, trouble - tion fixed temperature rate-of -rise type.The combination free vent which is carefully calibrated. detectors consist of two independently operated thermal elements.The rate-of -rise element is self- restoring. It is well known that air expands as it is heated, and con - However, the fixed temperature is of the non - restoring tracts as it is cooled. For normal, day-to-day fluctuations type of temperature, the expansion and contraction of the air within the chamber is automatically compensated by the Underwriter's Laboratories, Inc., recommends the "breathing" action of the vent. combination type thermal detector be used to protect a maximum of 2,500 square feet, and the fixed temperature However, when a fire occurs, air temperatures rise very type be used to protect a maximum of 625 square feet. rapidly and the air in the chamber expands faster than it Job conditions and engineering judgment, however, often can be vented.This creates a pressure which distends dictate closer spacing to provide faster detection. the diaphragm and closes electrical contacts. Mounting Data 13,8" 19/,8" _L 4 JUNCTION BOX MOUNTING SURFACE MOUNTING CATALOG NUMBER 6130 The rate-of -rise action is not related to any fixed tempera- Installation ture level, but responds with the utmost promptness Each detector includes a thermoplastic reversible mount- when the rate of temperature rise exceeds 15° per ing plate. In one position it easily attaches to a 4" octagon minute. If the heat is removed, the air within the chamber junction box, 3" octagon box or plaster ring. contracts and the switch moves to a normally open circuit position. In reverse, the plate can be used for open wiring without a junction box. A' / space between detector and mounting surface allows for wire connections. All mount - Fixed Temperature ing screws are concealed. Principle of Operation The detector simply attaches to the mounting plate with a In a slow developing fire, the temperature may not push and twist motion. No tools required. increase rapidly enough to operate a rate-of -rise element. In cases such as described a fixed temperature principle Engineer and Architect Specifications of operation is desired. The thermal fire detector shall be a Fire Safety The detector utilizes a fixed temperature element made Model (insert number). It shall operate at a of fusible alloy and is of the non-restorable type. temperature of degrees F (insert temperature).The detectors shall be listed by Underwriters' Laboratories, The fusible alloy will melt and activate the detector when Inc., and Factory Mutual for use with Siemens Building the surrounding air rises above the preset level of 135 °F Technologies, Fire Safety Division systems. or 200 °F. The external heat collector drops away when the detector is activated therefore giving a quick visual confirmation that the detector has alarmed. • Ordering Information Model Number I nn+ DT-135R OT-200R DT-135F DT-200F Description Rate -of -rise and fixed Rate -of -rise and fixed Axed temperature Fixed temperature temperature 135°F temperature 200°F only, 135 F only, 200°F Normal temperature Normal temperature Unusually violent Unusually violent fluctuations and ceiling fluctuations and ceiling temperature fluctua- temperature fluctua- Applications temperatures not temperatures exceed- tions and ceiling tions and ceiling exceeding 100 °F ing 100 °F but not 150 °F temperatures not temperatures exceed- exceeding,100 °F ing 100 °F but not 150 °F Identification on O Heat Collector • NONE GRAY RING GRAY SPOT GRAY SPOT AND RING Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park, NJ 07932 11102 Brampton, Ontario Siemens Building Technologies T FAX: ( (973) 593-6670 SFSIG Can November 2002 Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 supersedes Purer dated Woo