Correspondence (23) ( T4 �\ CITY OF TIGARD . O REGON October 26, 2001 GA Miller Architecture fILE C OPY . 2125 SW Fourth Ave., suite 516 Portland, OR 97201 Re: Quizo's Subs Project Information Address: 11705 SW Pacific Hwy., Suite M Permit No.: BUP2001 -00382 Occupancy: A -3 Construction Type: VN Occupant Load: 70 Sprinklered: No The City of Tigard Building Division has reviewed the submitted tenant improvement plans for the above referenced address in accordance with the Structural Specialty Code (OSSC), 1998 edition. The plans are approved subject to the following conditions. 1. The second required exit at the rear of this space shall be provided with panic hardware. Panic hardware may be omitted at the main exit door in accordance with the exception in OSSC Section 1007.2.5 and is provided with a readily visible durable sign with not less than 1 inch letters stating, "THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS." • 2. Exit signs shall be located at both required exits and an additional exit sign shall be located at the entrance of the hall that provides access to the rear exit. OSSC 1003.2.8. 3. Minimum 2A l OBC fire extinguishers shall be provided within the space so the travel distance to an extinguisher does not exceed 75 feet. UFC standard 10 -1. 4. Additional permits are required for plumbing, mechanical and electrical work. Work shall not commence on these portions of the project until such time as permits are issued by the City of Tigard Building Division. 5. A copy of the approved plans shall be on the job site at all times and available to the City of Tigard inspectors for inspection purposes. OSSC Section 106.4.2. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 6. A final inspection and Certificate of Occupancy is required prior to occupying for the intended use of this space. OSSC Section 109.1. 7. The Certificate of Occupancy and the approved Occupant Load Posting sign shall be posted in a conspicuous place on the premises and shall not be removed except by,the building official. OSSC Section 109.5. 8. The walk -in coolers shall bear a State of Oregon approved seal and any refrigeration lines, compressors or other mechanical attachments shall be reviewed and regulated under the mechanical permit by the City of Tigard Building Division. Sincerely, Gary Lampella Building Official c. File Oct.--22-01 03:44P GA MILLER ARCHITECTURE PC 503 827 7989 P.01 N‘ 1 4 A REVIEWED % / w / GA Miller ArchitechtreALA PC WINSTEAD & Assoc., Inc. • FAX TRANSMITTAL TO: Dave Csaszar COMPANY: The Quizno's Corporation FROM: Glen A. Miller AIA CSI DATE: October 22, 2001 RE: Quizno's — Tigard, Oregon Job No. 0109 -31 MESSAGE: Dave, attached is Addendum No. 1 for the above - referenced project. Please make certain the bidding Contractors receive this information. It must be incorporated into part of the Contract Documents. For the most part, it is in response to plan check review comments by the City. However, I inadvertently left out the Lighting Schedule. This is included as part of this Addendum. Thanks, Glen cc: Steve Winstead — City of Tigard (including Lighting Budget Calcs.) File Total number of pages in this transmission 4 including this cover page. If you do not receive all pages, please call (503) 827 -7979. Thank you. Copy to Follow in U.S. Mail: ❑ YES ❑ NO ® IF REQUESTED GA Miller Architecture ALA, PC • 2125 SW Fourth Avenue, Suite 516 Portland Oregon 97201 • (503) 827 -7979 r. Oct -22 -01 03:44P GA MILLER ARCHITECTURE PC 503 7989 P.02 • rj A IA 1 4 S\ GA Miller Architecture AlA PC Project: Quizno's Interior Tenant Improvement Location Tigard, Oregon ADDENDUM NO. One (1) Architect's Project Number: 0109 -31 October 22, 2001 To: Dave Csaszar -- Area Director, The Quizno's Corporation 840 Evergreen Road Lake Oswego, OR 97034 This addendum forms a part of the Contract Documents and modifies the original Project Manual and Drawings dated October 12, 2001. Acknowledge receipt of this Addendum. • This Addendum consists of one (1) page and one (1) pages of attachments. Drawings: • ITEM NO: Dwg. /Sht. NOTE: DESCRIPTION: 1. A -3 Clarify The night lights shown on the Reflected Ceiling Plan shall be un- switched, and provide light 24 hours a day. 2. _ A -2 Verify Verify the existing exit door at the back exterior wall (near Room 106). Remove door closer if one exists. Patch frame/wall as required. 3. A -5 Clarify The controls for the water closet indicated for h.c. accessibility shall have the controls on the open side of the water closet. 4. A -5 ADD Each restroom must be equipped with an accessible sign located near the door. 5. Verify Walk -in coolers and freezers each require a State of Oregon Compliance label. Contractor shall provide plans and specifications for permit and review purposes. 6. A -3 ADD Add the attached Light Fixture Schedule to the Contract Documents. 7. A -2,A -3 CHANGE Change gate at west end of Service 104 from a double swinging operation to a single swing inward toward the Service area. It cannot swing into the hallway. 8. A-2. A-4 ADD Add note at existing back exit door on Floor Plan and Door Schedule which reads: "Add panic hardware at this existing door." Specifications: ITEM NO: Division. NOTE: DESCRIPTION: 1. 15300 Delete Delete reference to providing an automatic sprinkler system. GA Miller Arrhitecture AlA PC • 2125 SW Fourth Avenue, Suite 516. Portland, Oregon 97201 • (503) 827.7979 FAX (503) 827.7989 • e -mail: ganut@pce:..com . Oct- 22 -,01 03:45P GA MILLER ARCHITECTURE PC 503 827 7989 P.03 The following items pertain to City of Tigard Plan and do not affect the project scope or budget: 1. The adjacent occupancies are: 2. No devices in this tenant space shall generate a glow, spark, or flame capable of igniting flammable vapors other than a gas water heater, which is located above the mop sink — over 18 inches above • the finished floor. 3. It is assumed no penetrations will occur at demising wall locations. If so, they shall be protected with a 1 -hr. rating sealant. • END OF ADDENDUM NO. 1 • • • • • • • • (, GL A MILL Q • r, / ,, • • tp% ORTLAND, ORE ON OF • • GA Miller Architecture AlA PC • 2125 SW Fourth Avenue, Suite 516, Portland. Oregon 97201 • (503) R27.7979 FAX (503) R27 -7989 • e-mail: ganw @pcez.com • Oct -22 -01 03:46P GA MILLER ARCHITECTURE PC 503 827 7989 P.08 Worksheet 5a Project Name: Page: LIGHTING SCHEDULE 'Enter the number - - - and type of lamps in. (a) (b) (c) (d) (e) (f) the luminaire. See Lamp' Ballast Table 5b for typical Lum. Fixture Luminaire Tab tamp codes. 'Enter the number ID Description No. Description No. Description Power ( 5X ) and type of ballasts in the luminaire. For. A Arr 1 3s -Itacv&erN1 - ZS W fluorescent and high intensity 1 .00A -re P-00D I • 150 W discharge lamps. typical ballast G 2 ' x 2' 7koFT 3 32- u,l T 8 €131V X abbreviations are: MAG STD for D 2' x 4' TkoT`F• 3 32.- W T-$ 95W X • Magnetic Standard •MAG EE for magnetic energy- efficient •ELECT for • electronic See Table 5b for . other ballast • abbreviations. • • • • • 5 -4 Lighting (1/96) Oct -22 -01 03:46P GA MILLER ARCHITECTURE PC 503 827 7989 • P.07 Form 5b Project Name:QuI? ?1loep Page: INTERIOR LIGHTING POWER - Occupancy Method Retail or (a) - (b) (c) (d) (e) (f) (9) Merchan- Max Lighting dise Floor Power Power Lighting Group Area Area Allow. Budget Power (n (W� ((c- d)xe)+f (Group M) If area is less than 2,000 ft 0 3.4 0 enter area in (c), this row M If area is between 2,000 and 6,000 ft enter 2,000 2.5 6,800 area in (c), this row II area exceeds 8,000 ft 6,000 1.7 16,800 enter area in (c), this row (a) (b) (c) (d) ( ''',41;,,t, (9) Uses Other Max . > _ Lighting Than Ceiling Floor Power t Power Group M Group Occupancy Use Height (n2) Allow. { Budget x • See p. 5-11 for under 15 feet ' . 98o 50 2. °l 1 0 instructions. I 1k zookA t 7 15 feet or more „ under 15 feet V" - . 15 feet or more' under 15 feet "'' °M 15 feet or more .;',, g:' 1. Total Interior Lighting Power Budget (Watts). Add amounts in column (g). 2 c17 p 2. Sum the page total(s) from Worksheet 5b. - Zr 936 3. Total linear feet of track lighting, I , — €',.. 4. Multiply line 3 by 50. ,10. 5. Total Interior Lighting Power. Add lines 2 and 4. - 2 - 13 3 ,, 6. Total Control Credit from Worksheet 5c. — 7. Total Adjusted Lighting Power (W). Subtract line 6 from line 5. 2 , 9 3 2 8. Does design meet the budget? Enter "Y" if line 7 is less than line 1, otherwise redesign. _ ,/ • • I 5 - 2 Lighting (1/96) • Oct -22 -01 03:45P GA MILLER ARCHITECTURE PC 503 827 7989 P.06 Worksheet 5b Project Name: Page: INTERIOR LIGHTING POWER 'Enter the quantity (a) (b) (c) (d) (e) (f) for every non- Lighting exempt luminaire. Luminaire Power Do not consider Room or Room or Plans Designatior Luminaire IC Quantity of Power (d) x (e) track lighting on this Sheet No. Luminaires' form. Track lighting ' I W 3 8S is accounted for on • Form 5b. A_3 Mew Coon -3 C 1 z 93 w 1,1 !(o A • 3 b 9 q3 W 837 1. Page Total. Total the amounts in column (f). 213 8 (1/96) Forms & Worksheets 5 - Oct -22 -01 03:45P GA MILLER ARCHITECTURE PC 503 827 7989 P.05 Form 5a Project Name: au f7 T. 1. Page: LIGHTING - GENERAL `fl 1. Interior Exceptions (Section 1316.1) # 131(9 • Z .S O No interior Lighting. The building plans do not call for new or altered interior lighting. Skip to Item 4, Exterior Building Lighting — General, below. Exceptions ❑ Exception. The building or part of the building qualifies for an exception from code lighting See a discussion of requirements. The applicable code exception is Section , Exception . Portions of the qualifying excep- building which qualify: (ions on p. 5 -7. 2. Local Shut -off Controls (Section 1316.1.2.1,1) O Compiles. At least one local shut -off lighting control for every 2,000 square feet of lighted floor area and for all spaces enclosed by walls or ceiling height partitions. This control(s) is detailed in the building plans on drawing number Exceptions ❑ Exception. The building or part of the building qualifies for an exception. The applicable code See a discussion of exception is Section 1316.12.1,1, Exception . Portions of the building which qualify: qualifying excep- tions on p. 5 -8. 3. Office Controls (Section 1316.1.2.1,2) Not an Office Occupancy over 2,0004quare feet. 40 +�t t wittaut O Complies. All Interior lighting systems are equipped with a separate automatic control to shut off the lighting and local override switching. These control(s) are detailed in the building plans on Exceptions drawing number See a discussion of Exception. The building or part of the building qualifies for an exception. The applicable code qualifying excep- exception is Section 1316.1.2.1,2, Exception . Portions of the building which qualify: lions on p. 5 -9 Definition 4. Exterior Building Lighting - General EXTERIOR No Exterior Building Lighting. Skip the rest of this form. BUILDING 0 Complies. Complete items 5 and 6 below. LIGHTING is lighting directed to illuminate the 5. Exterior Building Lighting Controls (Section 1316.1.2.2) exterior a the O Complies. The building plans require that all exterior building lighting is a ui ed with automatic building and P 9 P � 9 �9 9 q PP adjacent walkways controls described in Sec. 1316.1.2.2. These controls are detailed in the building plans on and loading areas drawing number with or without canopies. O Exception. The exterior building lighting is intended for 24 -hour continuous use. 6. Exterior Building Lighting Power (Section 1316.2.2) O Complies. The plans do not call for incandescent lamps greater than 10 watts for use in exterior building lighting. O Exception. The building plans indicate luminaires with incandescent lamps greater than 10 watts, but they are 5 percent or less of the total installed exterior lamps. (1 /96) Forms & Worksheets 5 -1 • 0 I - N .0 0 W N • C, r r m 1.101-1T PIX'Y'URE S E USE MARK MANUFACTURER CATALOG # DESCRIPTION LAMP VOLTAGE MOUNTING, REMARKS C A TRANSLITE TRIUMPH MPT- 241 -30" (ROUGE, FOREST GREEN, APRICOT) 61 -PIN HALOGEN CAPSULE 35 HATT COVERED 60 PENDANT SEE NOTES 43. ¢4 m B HUBBEL QUARTZLITE *CID -150 B QUARTZ- HALOGEN FLOODLIGHT W/ BRONZE FINISH 150 W 120 SURFACE NOTE 93 LAW WAIVED W al C LIGHTOLIER 2'X2' FLUORESCENT IN/ PRISMATIC LENS (3) F032 / 35K WATT 120 RECESSED NOTE *2 OR EQUIV. W • CO D LIGHTOLIER 2'X4' FLUORESCENT H/ PRISMATIC LENS (3) F032 / 35K HATT 120 RECC:TTCD NOTE a2 OR EQUIV. • I0 X -I PRESCOLITE EDX4R -1NH EMERGENCY LIGHT/EXIT LIGHT COMBINATION INCLUDED 120 SURFACE OR EQUIVALENT X -2 DUAL -LITE EZ -2 EMERGENCY LIGHT INCLUDED 120 SURFACE OR EQUIVALENT NOTES: !. REFER TO REFLECTED CEILING PLAN FOR LOCATION OF LIGHT FIXTURES AND CEILING TYPES. 2. ALL FLUORESCENT BALLASTS SHALL BE 'SCH' TYPE 3. FIXTURES (A) AND (B) MAY BE PURCHASED THROUGH GRAYBAR ELECTRIC, CONTACT PETER YOUNGDAHL: 303 -45S -1110 / FAX 303- 411 -I582. 0 4. FIXTURES TO BE RANDOMLY SPACED FROM b' -S' - 1' -4' AFF. • 48' OL. - NO TWO FIXTURES OF THE SAME HEIGHT OR COLOR SHALL BE SIDE BY SIDE. WINSTEAD AND ASSOCIATES _I ARCHITECTURE AND BUILDING CODE SERVICES, PC. P.O. Box 2198 Phme: 503- 723 -8003 Oregm City, Oregon 97045 Fax 503- 723 -8234 Email: planexamineca@aoLcam PLAN REVIEW COMMENTS 10 -22 -01 Project: Quizno's Subs Jurisdiction: Tigard Address:11705 SW Pacific Hwy. Permit #: BUP 2001 -00382 Job #: 1038.tig Background Information: 1. Winstead & Associates, Inc. has been retained to plan check this project on behalf of. 2. If there are any questions regarding this report, kindly direct them to Stephen Winstead at (503) 723 -8003. 3. The plan review is based on the State of Oregon Structural Specialty Code (OSSC); 1998 edition. 4. FOR RECHECK: Please forward revised documents to Winstead & Associates. Please include written responses to all plan check items. Client: GA Miller Architecture Address: 2125 SW 4 Ave. Suite 516 Portland, OR 97201 Phone: 503- 827 -7979 Fax: 503- 827 -7989 PROJECT DATA Occupancy Group: A3 (Restaurant) Construction Type: VN Floor Area: 1980 SF Auto. Sprinkler: Unknown Fire Alarm: Unknown ALLOWABLE AREA Base Occupancy Group: B existing structure Table 5 -B not applicable Yards: not applicable Sprinkler increase: Total area allowed: 1. GENERAL REQUIREMENTS: a. REMINDER: Secure clearances from Planning, Engineering, and Fire Departments. b. FIRE SPRINKLERS require separate review & permit by Fire Department. c. ALARM SYSTMS require separate review & permit by Fire Department. d. AMERICANS WITH DISABILITIES ACT (ADA): It shall be the responsibility of the project Architect, Engineer, Designer, Contractor, Owner, Lessee to research the applicability of the ADA requirements to this structure. reviews plans and inspects structures only for compliance with Chapter 11 of the OSSC, which may not include all the requirements of ADA. e. DEFERRED SUBMITTALS: Deferred submittals are those items that do not accompany the original documents but are necessary prior to issuance of a permit. Please contact the building official for approval of deferred submittals. In addition, please list any other items that are to be deferred submittals. Submittal documents for deferred submittal items shall be submitted to the architect or engineer of record who shall review them and forward them to the building official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. The deferred submittal items shall not be installed until the building official has approved their design and submittal documents. (Section 106.3.4.2). 2. PLANS AND DOCUMENTS: a. MISSING DOCUMENTS: 1. None noted except for differed submittals. 13. BUILDING CLASSIFICATION a. OCCUPANCY: 1. Group A Restaurant. The occupant load for the main eating area has been figured at approximately 832 sf/15 = 56. b. MIXED OCCUPANCY: 1. Please indicate the adjacent occupancies in order to determine if an occupancy separation wall is required as well as the rating. c. TYPE OF CONSTRUCTION: 1. The construction documents indicate a Type V -N. The specifications indicate an automatic sprinkler system is to be provided. Is this in lieu of 1- hour construction? d. HEIGHT AND NUMBER OF STORIES: 1. This is not an issue. e. LOCATION ON PROPERTY: 1. This is not an issue. £ ALLOWABLE FLOOR AREA: 1. This is a tenant improvement in an existing building. 14. OCCUPANCY REQUIREMENTS a. LIGHT, VENTILATION AND SANITATION: 1. Based on Table A 29 -A the occupant load is 750/30 or 25 which requires one fixture per sex. This has been met. 2. The mechanically operated ventilation system shall be capable of supplying occupancy ventilation air in accordance with Table 12 -A during such time as the building or space is occupied. The anticipated ventilation occupancy load, specifically for the design of occupancy ventilation, shall be documented on plans and specifications b. SPRINKLER REQUIREMENTS: 1. See above request for information. c. SPECIAL HAZARDS: 1. Storage and use of flammable and combustible liquids shall be in accordance with the Fire Code. This is a general note. Are there any class I, II or III -A liquids planned to be stored on site? 2. Devices generating a glow, spark or flame capable of igniting flammable vapors shall be installed such that sources of ignition are at least 18 inches above the floor of any room in which Class I flammable liquids or flammable gases are used or stored. This is a general note. 5. FIRE PROTECTION REQUIREMENTS a. FIRE EXTINGUISHERS: 1. Both placement and quantify per Fire Marshal. One (1) fire extinguisher rated at not less than 2A10B:C shall be in an accessible location and in plain view for every 3000 sq ft of floor area. b. FIRE SPRINKLERS: 1. The specifications indicate the building is sprinkled. Please clarify if this is so. This will need to be a deferred submittal. Plans are required for the sprinkler head modifications. 6. FIRE- RESISTIVE ASSEMBLIES: a. DEMIZING WALLS: 1. It is assumed that there is at least a one -hour separation between the tenants. All penetrations must be sealed with the same rating as the wall assembly. 7. EXITING: a. EXIT LIGHTING: 1. Any time a building is occupied, the means of egress shall be illuminated at an intensity of not less than 1 foot - candle at the floor level." This is a general note that needs to be indicated on the plans. b. DOOR ENCROACHMENT: 1. The short double acting door encroaches the hallway by more than 1/2 of the required width. This door will need to swing into the Kitchen area per OSSC Section 1004.3.4.2. 1 8. HANDICAPPED ACCESSIBILITY a. HANDICAPPED PARKING: 1. Please provide a site plan indicating location of accessible parking. This can be considered a deferred submittal. The City of Tigard shall verify site accessibility. b. ACCESSIBLE APPROACH: 1. The rear exit is required to have at least 12" minimum from the edge of the door to the interior wall when the door has a latch and closer. c. ACCESSIBLE CONTROLS: 1. The controls for the water closet indicated on the typical detail is required to be on the open side of the water closet.