Correspondence 0 &Awl May 31, 2005 FILE COPY CITY OF TIGARD O REGON Custom Metal Fab Margi Williams 50602 birch Ave. Scappoose, OR 97056 RE: MECHANICAL — EXHAUST DUCT SYSTEM FOR TYPE 1 HOOD Project Information Building Permit: MEC2005 -00251 Construction Type: 5B Tenant Name: Sushi Hana Occupancy Type: B Address: 11705 SW Pacific Hwy Occupant Load: 20 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; The submitted plans are approved subject to the following. 1. Provide automatic fire suppression systems for to type 1 hood prior to final inspection. "Automatic fire suppression systems, including pre - engineered and engineered dry- and wet - chemical fire - suppression systems, shall be listed and labeled for specific use as protection for commercial cooking operations and shall be installed in accordance with Section 304.1." OMSC 509.2 2. Duct- to- exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; OMSC 506.3.2.3 3. Duct systems serving a Type I hood shall be constructed and installed so that grease cannot collect in any portion thereof, and the system shall slope not less than one - fourth unit vertical in 12 units horizontal (2- percent slope) toward the hood or toward an approved grease reservoir. OMSC 506.3.7 4. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code. Manufacturer's installation instructions shall be available on the job site at the time of inspection. OMSC 304.1 5. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 or structure shall be left in a safe structural condition in accordance with the Building Code. The cutting, notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1 through 302.5.3. 6. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 7. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Resp 11 , al Henzel, Senior Plans Examiner