Correspondence / fir
RECEIVED
SEP 1 0 1997 A'6
August 28, 1997 q
COMMUNITY DEVELOPMEN CI A Y OF T I GAR
Christensen Engineering
7150 SW Hampton Street #226 _ OREGON
Portland, OR 97223 •
RE: Car Toys Site Plan Review
11700 SW Pacific Hwy
PCI:: 8 -69c SIT #: 97 -0032
Submittal documents for the above referenced project have been reviewed for conformance with the
applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following
comments are noted:
I SITE_WORK : .... ...
1. Provide details on your approach to Carlson's report, page 4 (engineered fill).
H45 see, bv,../ZP TEp 7-1-fiCov4,4 4 E , N4K4L - NOTES.
2. Catch basins shall be trapped by using the inverted one - quarter bend or welded baffle. Provide
catch basins constructed to OPSC, Section 1108 specifications.
epic sjcr /o✓ /yo$ -Met Mks a6E.v PS 7 acv o1- .4vs.
3. Submit revised plans with details and specifications for the Lynch -type catch basin. The design
shall be in accordance with OPSC, Section 1108 requirements.
-- 5E4. AI.. 2 !+6 r vE ,
4. No building shall be constructed, altered, enlarged, moved or repaired in a manner that by reason
of size, type of construction, number of stories, occupancy or any combination thereof, creates a
need for a fire flow in excess of 3,000 gallons per minute at 20 psi residual or exceeds the
available fire flow at the site of the structure [UFC, Section 903.3].
A. Provide Fire Flow Testing pursuant to NFPA 291 using the enclosed "Hydrant Flow Test
Report Form."
pereszFq, E,v4r•vi6•UN 13 As -T/.v4 on. Tf/ S ; f &5e.A.7-5 Wla.i. 5
S B�+iTTiD froRTHw►TH
B. Complete the enclosed "Fire Flow Work Sheet" and forward to Tualatin Valley F and
Rescue, 4755.SW Griffith Dr. [P.O. Box 4755] Beaverton, OR 97076 [Ph. 526 - 2469], and
return a copy to the City of Tigard, attn. Plans Examiner.
— /N /to — E , Gimpy Te cl7r of r/4Ago FogT1fw/
Note: These documents shall be on file before a building permit will be issued.
•
Please submit two cosies of revised submittal documents and a letter indicating your response to the
above comments for review. Please call me at (503) 639 -4171 if you have any questions.
•
Sincerely,
•
eolse Pos in, CBO
PLANS EXAMINER
m: \prmsys\ document \sit97_00.32 \pc869c.doc . •
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
•
Car Toys Mechanical Plan Review
PC #: 10 -62c MEC #: 97 -0413
Page #2 °
Please submit two copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
uzikke
Ro ert Poskin, CBO
PLANS EXAMINER
•
ia..nman.m.mr u,avmc�me