RE: REPLACEMENT HVAC UNIT
Project Information
Building Permit: MEC2004 -00306 Construction Type: NA
Tenant Name: West Coast Bank Occupancy Type: B
Address: 11675 SW Pacific Highway
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
1. Each appliance shall be provided with a shutoff valve separate from the appliance.
The shutoff valve shall be located in the same room and within six feet of the
appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC
2. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
3. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
4. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
5. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
6. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC