CITY OF TIGARD
October 24, 1997 OREGON
Juliano Heating and Air Conditioning
2525 SE 176th Place
Portland, OR 97236
RE: Car Toys Mechanical Plan Review
11710 SW Pacific Hwy.
PC#: 10 -62c MEC #: 97 -0413
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
ENERG 6 111:10 l'N ° 4 , W-, q : . . 1 7,1;04
1. Submit completed applicable Forms 4a through 4j, and required duct insulation
Form 4a through 4c of the Energy Code Compliance Manual (Revised April 1996).
MECHANICAL y . „ '�� ;� �` ' ",
1. The attachment of permanent equipment (HVAC) supported by the building's
structural components shall be designed to resist the total design seismic forces
prescribed in Section 1603.2 of the Structural Specialty Code. Provide an
engineer's design specifying attachment requirements [OSSC, Section 106.3.2
and OMSC, Section 304.4].
2. The heat/ventilation system shall provide outside air per occupant in all portions
of the building [OSSC, Section 1202.2.1 and Table 12P].
A. Provide outside air specifications on the revised plans.
3. Each individual roof - mounted HVAC shall be permanently labeled as to the
areas it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped
with a power disconnect. A 120 -volt receptacle shall be located within 25' of
each unit [OMSC, Section 309.1].
4. Air moving systems (combination of units), supplying air in access of 2000 CFM
to enclosed spaces, shall be equipped with an automatic shut -off. The smoke
detectors shall be supervised when a fire detection or alarm system is provided
[OMSC, Section 608].